Alarm Triggers

Every alarm each device's map defines for the model ems_control_setting.json declares. Triggering writes the register the rule watches, so the simulator serves the condition and the EMS reports the alarm on its next poll.

Built 23:05:03
Devices
98
8 active
Triggerable
8
active and served by the simulator
Alarm rules
2704
across every device map
Firing now
0
as the EMS sees it
Active alarms from the EMS alarm report
Loading…
0 selected
ev_charger1 EV-CHARGER-001
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger2 EV-CHARGER-002
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger3 EV-CHARGER-003
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger4 EV-CHARGER-004
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger5 EV-CHARGER-005
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger6 EV-CHARGER-006
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger7 EV-CHARGER-007
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger8 EV-CHARGER-008
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger9 EV-CHARGER-009
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger10 EV-CHARGER-010
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger11 EV-CHARGER-011
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ev_charger12 EV-CHARGER-012
ev_charging_piles no register file declared setting says EVC1 switched off in the control setting the Register API does not serve this no reading yet
0 alarms defined
Code Severity Alarm Watched register Rule Writes
ac1 AC-UNIT-001
ac_units air_condition_unit/ac1/ac_register_full ac_alarm_code___ac_std.json EMS model AC_STD switched off in the control setting disabled in the simulator no reading yet
8 alarms defined by ac_alarm_code___ac_std.json
Code Severity Alarm Watched register Rule Writes
AC-1001 major Fault Active
Fault active: the input is asserted.
fault_active truthy
reset writes 0
AC-1002 major High Pressure Trip Count
High pressure trip count: number of events recorded since the last reset.
high_pressure_trip_count > 0.0
reset writes 0
AC-1003 major High Temp Alarm Count
High temp alarm count: number of events recorded since the last reset.
high_temp_alarm_count > 0.0
reset writes 0
AC-1004 major Low Pressure Trip Count
Low pressure trip count: number of events recorded since the last reset.
low_pressure_trip_count > 0.0
reset writes 0
AC-1005 major Low Temp Alarm Count
Low temp alarm count: number of events recorded since the last reset.
low_temp_alarm_count > 0.0
reset writes 0
AC-1006 major Sensor Fault Count
Sensor fault count: number of events recorded since the last reset.
sensor_fault_count > 0.0
reset writes 0
AC-ROOM-RH major Room Humidity High
Room relative humidity above 70%.
room_rh_percent > 70.0
reset writes 70
AC-ROOM-TEMP major Room Temperature High
Room temperature above 30 degC.
room_temp_c > 30.0
reset writes 30
ac2 AC-UNIT-002
ac_units air_condition_unit/ac2/ac_register_full ac_alarm_code___ac_std.json EMS model AC_STD switched off in the control setting disabled in the simulator
8 alarms defined by ac_alarm_code___ac_std.json
Code Severity Alarm Watched register Rule Writes
AC-1001 major Fault Active
Fault active: the input is asserted.
fault_active truthy
reset writes 0
AC-1002 major High Pressure Trip Count
High pressure trip count: number of events recorded since the last reset.
high_pressure_trip_count > 0.0
reset writes 0
AC-1003 major High Temp Alarm Count
High temp alarm count: number of events recorded since the last reset.
high_temp_alarm_count > 0.0
reset writes 0
AC-1004 major Low Pressure Trip Count
Low pressure trip count: number of events recorded since the last reset.
low_pressure_trip_count > 0.0
reset writes 0
AC-1005 major Low Temp Alarm Count
Low temp alarm count: number of events recorded since the last reset.
low_temp_alarm_count > 0.0
reset writes 0
AC-1006 major Sensor Fault Count
Sensor fault count: number of events recorded since the last reset.
sensor_fault_count > 0.0
reset writes 0
AC-ROOM-RH major Room Humidity High
Room relative humidity above 70%.
room_rh_percent > 70.0
reset writes 70
AC-ROOM-TEMP major Room Temperature High
Room temperature above 30 degC.
room_temp_c > 30.0
reset writes 30
ac3 AC-UNIT-003
ac_units air_condition_unit/ac3/ac_register_full ac_alarm_code___ac_std.json EMS model AC_STD switched off in the control setting disabled in the simulator
8 alarms defined by ac_alarm_code___ac_std.json
Code Severity Alarm Watched register Rule Writes
AC-1001 major Fault Active
Fault active: the input is asserted.
fault_active truthy
reset writes 0
AC-1002 major High Pressure Trip Count
High pressure trip count: number of events recorded since the last reset.
high_pressure_trip_count > 0.0
reset writes 0
AC-1003 major High Temp Alarm Count
High temp alarm count: number of events recorded since the last reset.
high_temp_alarm_count > 0.0
reset writes 0
AC-1004 major Low Pressure Trip Count
Low pressure trip count: number of events recorded since the last reset.
low_pressure_trip_count > 0.0
reset writes 0
AC-1005 major Low Temp Alarm Count
Low temp alarm count: number of events recorded since the last reset.
low_temp_alarm_count > 0.0
reset writes 0
AC-1006 major Sensor Fault Count
Sensor fault count: number of events recorded since the last reset.
sensor_fault_count > 0.0
reset writes 0
AC-ROOM-RH major Room Humidity High
Room relative humidity above 70%.
room_rh_percent > 70.0
reset writes 70
AC-ROOM-TEMP major Room Temperature High
Room temperature above 30 degC.
room_temp_c > 30.0
reset writes 30
ac4 AC-UNIT-004
ac_units air_condition_unit/ac4/ac_register_full ac_alarm_code___ac_std.json EMS model AC_STD switched off in the control setting disabled in the simulator
8 alarms defined by ac_alarm_code___ac_std.json
Code Severity Alarm Watched register Rule Writes
AC-1001 major Fault Active
Fault active: the input is asserted.
fault_active truthy
reset writes 0
AC-1002 major High Pressure Trip Count
High pressure trip count: number of events recorded since the last reset.
high_pressure_trip_count > 0.0
reset writes 0
AC-1003 major High Temp Alarm Count
High temp alarm count: number of events recorded since the last reset.
high_temp_alarm_count > 0.0
reset writes 0
AC-1004 major Low Pressure Trip Count
Low pressure trip count: number of events recorded since the last reset.
low_pressure_trip_count > 0.0
reset writes 0
AC-1005 major Low Temp Alarm Count
Low temp alarm count: number of events recorded since the last reset.
low_temp_alarm_count > 0.0
reset writes 0
AC-1006 major Sensor Fault Count
Sensor fault count: number of events recorded since the last reset.
sensor_fault_count > 0.0
reset writes 0
AC-ROOM-RH major Room Humidity High
Room relative humidity above 70%.
room_rh_percent > 70.0
reset writes 70
AC-ROOM-TEMP major Room Temperature High
Room temperature above 30 degC.
room_temp_c > 30.0
reset writes 30
ac5 AC-UNIT-005
ac_units air_condition_unit/ac5/ac_register_full ac_alarm_code___ac_std.json EMS model AC_STD switched off in the control setting disabled in the simulator
8 alarms defined by ac_alarm_code___ac_std.json
Code Severity Alarm Watched register Rule Writes
AC-1001 major Fault Active
Fault active: the input is asserted.
fault_active truthy
reset writes 0
AC-1002 major High Pressure Trip Count
High pressure trip count: number of events recorded since the last reset.
high_pressure_trip_count > 0.0
reset writes 0
AC-1003 major High Temp Alarm Count
High temp alarm count: number of events recorded since the last reset.
high_temp_alarm_count > 0.0
reset writes 0
AC-1004 major Low Pressure Trip Count
Low pressure trip count: number of events recorded since the last reset.
low_pressure_trip_count > 0.0
reset writes 0
AC-1005 major Low Temp Alarm Count
Low temp alarm count: number of events recorded since the last reset.
low_temp_alarm_count > 0.0
reset writes 0
AC-1006 major Sensor Fault Count
Sensor fault count: number of events recorded since the last reset.
sensor_fault_count > 0.0
reset writes 0
AC-ROOM-RH major Room Humidity High
Room relative humidity above 70%.
room_rh_percent > 70.0
reset writes 70
AC-ROOM-TEMP major Room Temperature High
Room temperature above 30 degC.
room_temp_c > 30.0
reset writes 30
ac6 AC-UNIT-006
ac_units air_condition_unit/ac6/ac_register_full ac_alarm_code___ac_std.json EMS model AC_STD switched off in the control setting disabled in the simulator
8 alarms defined by ac_alarm_code___ac_std.json
Code Severity Alarm Watched register Rule Writes
AC-1001 major Fault Active
Fault active: the input is asserted.
fault_active truthy
reset writes 0
AC-1002 major High Pressure Trip Count
High pressure trip count: number of events recorded since the last reset.
high_pressure_trip_count > 0.0
reset writes 0
AC-1003 major High Temp Alarm Count
High temp alarm count: number of events recorded since the last reset.
high_temp_alarm_count > 0.0
reset writes 0
AC-1004 major Low Pressure Trip Count
Low pressure trip count: number of events recorded since the last reset.
low_pressure_trip_count > 0.0
reset writes 0
AC-1005 major Low Temp Alarm Count
Low temp alarm count: number of events recorded since the last reset.
low_temp_alarm_count > 0.0
reset writes 0
AC-1006 major Sensor Fault Count
Sensor fault count: number of events recorded since the last reset.
sensor_fault_count > 0.0
reset writes 0
AC-ROOM-RH major Room Humidity High
Room relative humidity above 70%.
room_rh_percent > 70.0
reset writes 70
AC-ROOM-TEMP major Room Temperature High
Room temperature above 30 degC.
room_temp_c > 30.0
reset writes 30
ats1 ATS-001
ats_units ats/ats1/ats_register_full ats_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
3 alarms defined by ats_alarm_code.json
Code Severity Alarm Watched register Rule Writes
ATS-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
ATS-1002 major Source 1 Unavailable
Source 1 is not presenting a usable supply.
source_1_available falsy
zero may be ignored
reset writes 1
ATS-1003 major Source 2 Unavailable
Source 2 is not presenting a usable supply.
source_2_available falsy
zero may be ignored
reset writes 1
bessEnergyMeter1 bessEnergyMeter1
bess_energy_meters bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full bessMeter_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
3 alarms defined by bessMeter_alarm_code.json
Code Severity Alarm Watched register Rule Writes
BESS-1002 major Current Disturbance
Current disturbance: the waveform is outside the allowed distortion.
current_disturbance > 0.0
reset writes 0
BESS-1003 major Voltage Disturbance
Voltage disturbance: the waveform is outside the allowed distortion.
voltage_disturbance > 0.0
reset writes 0
BESS-1001 warning Alarm Code
Alarm code: the meter has raised an alarm code.
alarm_code truthy
reset writes 0
bmu1 Cl1_P1
bmu_units bmu/bmu1/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu10 Cl1_P10
bmu_units bmu/bmu10/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu2 Cl1_P2
bmu_units bmu/bmu2/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu3 Cl1_P3
bmu_units bmu/bmu3/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu4 Cl1_P4
bmu_units bmu/bmu4/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu5 Cl1_P5
bmu_units bmu/bmu5/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu6 Cl1_P6
bmu_units bmu/bmu6/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu7 Cl1_P7
bmu_units bmu/bmu7/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu8 Cl1_P8
bmu_units bmu/bmu8/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
bmu9 Cl1_P9
bmu_units bmu/bmu9/bmu_register_full bmu_alarm_code___bmu100.json EMS model BMU100 switched off in the control setting disabled in the simulator
8 alarms defined by bmu_alarm_code___bmu100.json
Code Severity Alarm Watched register Rule Writes
BMU-1001 critical Cell Overvoltage Alarm
Cell overvoltage alarm: voltage has exceeded the safe operating limit.
cell_overvoltage_alarm truthy
reset writes 0
BMU-1002 critical Cell Undervoltage Alarm
Cell undervoltage alarm: voltage has fallen below the safe operating limit.
cell_undervoltage_alarm truthy
reset writes 0
BMU-SOC-LOW critical Cell Stack SOC Critically Low
Battery stack state of charge below 3%.
soc < 3.0
reset writes 3
BMU-1003 major Communication Fault
Communication fault: the device has stopped responding.
communication_fault truthy
reset writes 0
BMU-1005 major Temperature Over Alarm
Temperature over alarm: temperature has exceeded the safe operating limit.
temperature_over_alarm truthy
reset writes 0
BMU-1006 major Temperature Under Alarm
Temperature under alarm: temperature has fallen below the safe operating limit.
temperature_under_alarm truthy
reset writes 0
BMU-1004 warning Pack General Alarm
Pack general alarm: the device reports this alarm as active.
pack_general_alarm truthy
reset writes 0
BMU-SOH-LOW warning Cell Stack SOH Low
Battery stack state of health below 80%.
soh < 80.0
reset writes 80
contactor1 CONTACTOR-001
contactors contactor/contactor1/contactor_register_full contactor_alarm_code.json EMS model ME231 no model-specific map
4 alarms defined by contactor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
CON-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
CON-1002 major Contactor Failed to Open
An open command was issued but auxiliary feedback still reports closed.
failed_to_open truthy
reset writes 0
CON-1003 major Contactor Failed to Close
A close command was issued but auxiliary feedback still reports open.
failed_to_close truthy
reset writes 0
CON-1004 minor Contactor Feedback Mismatch
Commanded state and auxiliary feedback disagree.
feedback_mismatch truthy
reset writes 0
contactor2 CONTACTOR-002
contactors contactor/contactor2/contactor_register_full contactor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
4 alarms defined by contactor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
CON-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
CON-1002 major Contactor Failed to Open
An open command was issued but auxiliary feedback still reports closed.
failed_to_open truthy
reset writes 0
CON-1003 major Contactor Failed to Close
A close command was issued but auxiliary feedback still reports open.
failed_to_close truthy
reset writes 0
CON-1004 minor Contactor Feedback Mismatch
Commanded state and auxiliary feedback disagree.
feedback_mismatch truthy
reset writes 0
contactor3 CONTACTOR-003
contactors contactor/contactor3/contactor_register_full contactor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
4 alarms defined by contactor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
CON-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
CON-1002 major Contactor Failed to Open
An open command was issued but auxiliary feedback still reports closed.
failed_to_open truthy
reset writes 0
CON-1003 major Contactor Failed to Close
A close command was issued but auxiliary feedback still reports open.
failed_to_close truthy
reset writes 0
CON-1004 minor Contactor Feedback Mismatch
Commanded state and auxiliary feedback disagree.
feedback_mismatch truthy
reset writes 0
contactor4 CONTACTOR-004
contactors contactor/contactor4/contactor_register_full contactor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
4 alarms defined by contactor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
CON-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
CON-1002 major Contactor Failed to Open
An open command was issued but auxiliary feedback still reports closed.
failed_to_open truthy
reset writes 0
CON-1003 major Contactor Failed to Close
A close command was issued but auxiliary feedback still reports open.
failed_to_close truthy
reset writes 0
CON-1004 minor Contactor Feedback Mismatch
Commanded state and auxiliary feedback disagree.
feedback_mismatch truthy
reset writes 0
contactor5 CONTACTOR-005
contactors contactor/contactor5/contactor_register_full contactor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
4 alarms defined by contactor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
CON-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
CON-1002 major Contactor Failed to Open
An open command was issued but auxiliary feedback still reports closed.
failed_to_open truthy
reset writes 0
CON-1003 major Contactor Failed to Close
A close command was issued but auxiliary feedback still reports open.
failed_to_close truthy
reset writes 0
CON-1004 minor Contactor Feedback Mismatch
Commanded state and auxiliary feedback disagree.
feedback_mismatch truthy
reset writes 0
door_sensor1 DOOR-SENSOR-001
door_sensors door_sensor/door_sensor1/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor10 DOOR-SENSOR-010
door_sensors door_sensor/door_sensor10/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor2 DOOR-SENSOR-002
door_sensors door_sensor/door_sensor2/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor3 DOOR-SENSOR-003
door_sensors door_sensor/door_sensor3/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor4 DOOR-SENSOR-004
door_sensors door_sensor/door_sensor4/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor5 DOOR-SENSOR-005
door_sensors door_sensor/door_sensor5/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor6 DOOR-SENSOR-006
door_sensors door_sensor/door_sensor6/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor7 DOOR-SENSOR-007
door_sensors door_sensor/door_sensor7/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor8 DOOR-SENSOR-008
door_sensors door_sensor/door_sensor8/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
door_sensor9 DOOR-SENSOR-009
door_sensors door_sensor/door_sensor9/door_sensor_register_full door_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
12 alarms defined by door_alarm_code.json
Code Severity Alarm Watched register Rule Writes
DOOR-OPEN-01 warning Door 1 Open
Door contact 1 reports the door open.
door_sensor_1_status truthy
reset writes 0
DOOR-OPEN-02 warning Door 2 Open
Door contact 2 reports the door open.
door_sensor_2_status truthy
reset writes 0
DOOR-OPEN-03 warning Door 3 Open
Door contact 3 reports the door open.
door_sensor_3_status truthy
reset writes 0
DOOR-OPEN-04 warning Door 4 Open
Door contact 4 reports the door open.
door_sensor_4_status truthy
reset writes 0
DOOR-OPEN-05 warning Door 5 Open
Door contact 5 reports the door open.
door_sensor_5_status truthy
reset writes 0
DOOR-OPEN-06 warning Door 6 Open
Door contact 6 reports the door open.
door_sensor_6_status truthy
reset writes 0
DOOR-OPEN-07 warning Door 7 Open
Door contact 7 reports the door open.
door_sensor_7_status truthy
reset writes 0
DOOR-OPEN-08 warning Door 8 Open
Door contact 8 reports the door open.
door_sensor_8_status truthy
reset writes 0
DOOR-OPEN-09 warning Door 9 Open
Door contact 9 reports the door open.
door_sensor_9_status truthy
reset writes 0
DOOR-OPEN-10 warning Door 10 Open
Door contact 10 reports the door open.
door_sensor_10_status truthy
reset writes 0
DOOR-OPEN-11 warning Door 11 Open
Door contact 11 reports the door open.
door_sensor_11_status truthy
reset writes 0
DOOR-OPEN-12 warning Door 12 Open
Door contact 12 reports the door open.
door_sensor_12_status truthy
reset writes 0
emergency_stop1 EMERGENCY-STOP-001
emergency_stops emergency_stop/emergency_stop1/emergency_stop_register_full emergency_stop_alarm_code.json EMS model ME231 no model-specific map
4 alarms defined by emergency_stop_alarm_code.json
Code Severity Alarm Watched register Rule Writes
EST-1002 critical Emergency Stop Activated
Emergency stop input is open: the physical stop has been operated.
emergency_stop_active truthy
reset writes 0
EST-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
EST-1003 major Emergency Stop Wiring Fault
The emergency stop loop reads neither open nor closed: check the wiring.
emergency_stop_wiring_fault truthy
reset writes 0
EST-1004 warning Manual Reset Required
The emergency stop has been released but is waiting for a manual reset.
manual_reset_required truthy
reset writes 0
ffrEnergyMeter1 FFR-METER-001
ffr_meters ffr_energy_meter/ffrmeter1/ffrmeter_register_full ffrMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting
5 alarms defined by ffrMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
fire_alarm1 FIRE-ALARM-001
fire_alarms fire_alarm/fire_alarm1/fire_alarm_register_full fire_alarm_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
3 alarms defined by fire_alarm_alarm_code.json
Code Severity Alarm Watched register Rule Writes
FAL-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
FAL-1003 major Fire Alarm Fault
The fire alarm panel reports a fault.
fire_alarm_fault truthy
reset writes 0
FAL-1004 major Fire Alarm Trouble
The fire alarm panel reports a trouble condition.
fire_alarm_trouble truthy
reset writes 0
fire_alarm2 FIRE-ALARM-002
fire_alarms fire_alarm/fire_alarm2/fire_alarm_register_full fire_alarm_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
3 alarms defined by fire_alarm_alarm_code.json
Code Severity Alarm Watched register Rule Writes
FAL-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
FAL-1003 major Fire Alarm Fault
The fire alarm panel reports a fault.
fire_alarm_fault truthy
reset writes 0
FAL-1004 major Fire Alarm Trouble
The fire alarm panel reports a trouble condition.
fire_alarm_trouble truthy
reset writes 0
fss1 FIRE-FIGHTING-001
fss fire_safety_system/fss1/fss_register_full fss_alarm_code___fss_std.json EMS model FSS_STD switched off in the control setting disabled in the simulator no reading yet
11 alarms defined by fss_alarm_code___fss_std.json
Code Severity Alarm Watched register Rule Writes
FSS-1007 critical Manual Release Active
Manual release active: the release input has been operated.
manual_release_active truthy
reset writes 0
FSS-1002 major Fault Counts Total
Fault counts total: number of events recorded since the last reset.
fault_counts_total > 0.0
reset writes 0
FSS-1003 major Gas Alarm Active
Gas alarm active: the fire-safety input is active.
gas_alarm_active truthy
reset writes 0
FSS-1004 major Gas Alarm Count
Gas alarm count: number of events recorded since the last reset.
gas_alarm_count > 0.0
reset writes 0
FSS-1005 major Heat Alarm Active
Heat alarm active: the fire-safety input is active.
heat_alarm_active truthy
reset writes 0
FSS-1006 major Heat Alarm Count
Heat alarm count: number of events recorded since the last reset.
heat_alarm_count > 0.0
reset writes 0
FSS-1008 major Release Count
Release count: number of events recorded since the last reset.
release_count > 0.0
reset writes 0
FSS-1009 major Smoke Alarm Active
Smoke alarm active: the fire-safety input is active.
smoke_alarm_active truthy
reset writes 0
FSS-1010 major Smoke Alarm Count
Smoke alarm count: number of events recorded since the last reset.
smoke_alarm_count > 0.0
reset writes 0
FSS-CANISTER major Suppressant Canister Low
Aerosol canister charge below 20%.
aerosol_canister_remaining_percent < 20.0
reset writes 20
FSS-1001 warning Abort Active
Abort active: the release sequence was aborted.
abort_active truthy
reset writes 0
flood_sensor1 FLOOD-SENSOR-001
flood_sensors flood_sensor/flood_sensor1/flood_sensor_register_full flood_sensor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
2 alarms defined by flood_sensor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
FLOOD-1-WET critical Flood Detected (Sensor 1)
Flood sensor 1 is wet.
flood_sensor_1_status truthy
reset writes 0
FLOOD-2-WET critical Flood Detected (Sensor 2)
Flood sensor 2 is wet.
flood_sensor_2_status truthy
reset writes 0
frequency_meter1 FREQUENCY-METER-001
frequency_meters frequency_meter/frequency_meter1/frequencymeter_register_full frequencyMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by frequencyMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
FREQ-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
FREQ-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
FREQ-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
FREQ-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter1 GRID-METER-001
grid_meters grid_energy_meter/grid_meter1/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter10 GRID-METER-010
grid_meters grid_energy_meter/grid_meter10/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter11 GRID-METER-011
grid_meters grid_energy_meter/grid_meter11/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter12 GRID-METER-012
grid_meters grid_energy_meter/grid_meter12/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter2 GRID-METER-002
grid_meters grid_energy_meter/grid_meter2/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter3 GRID-METER-003
grid_meters grid_energy_meter/grid_meter3/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter4 GRID-METER-004
grid_meters grid_energy_meter/grid_meter4/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter5 GRID-METER-005
grid_meters grid_energy_meter/grid_meter5/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter6 GRID-METER-006
grid_meters grid_energy_meter/grid_meter6/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter7 GRID-METER-007
grid_meters grid_energy_meter/grid_meter7/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter8 GRID-METER-008
grid_meters grid_energy_meter/grid_meter8/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
grid_meter9 GRID-METER-009
grid_meters grid_energy_meter/grid_meter9/gridmeter_register_full gridMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
5 alarms defined by gridMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
GRID-OV-L1 critical Grid Over Voltage L1
Grid phase L1 voltage above 245 V.
voltage_l1_n_v > 245.0
reset writes 245
GRID-OF major Grid Over Frequency
Grid frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
GRID-UF major Grid Under Frequency
Grid frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
GRID-UV-L1 major Grid Under Voltage L1
Grid phase L1 voltage below 180 V.
voltage_l1_n_v < 180.0
reset writes 180
GRID-PF-LOW warning Grid Power Factor Low
Grid power factor below 0.8.
pf_total < 0.8
reset writes 0.8
heat_sensor1 HEAT-SENSOR-001
heat_sensors heat_sensor/heat_sensor1/heat_sensor_register_full heat_sensor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
3 alarms defined by heat_sensor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
HEAT-ALARM-1 critical Heat Alarm
Heat detector alarm bit is set (bit 0).
alarm_bitmap bit 0
reset writes bit 0 off
HEAT-FAULT-1 major Heat Detector Fault
Heat detector fault bit is set (bit 1).
alarm_bitmap bit 1
reset writes bit 1 off
HEAT-TEST-1 minor Heat Detector Test
Heat detector test bit is set (bit 2).
alarm_bitmap bit 2
reset writes bit 2 off
cooling1 LIQUID-COOLING-001
cooling_unit liquid_cooling_unit/cooling1/cooling_register_full cooling_alarm_code___cool_std.json EMS model COOL_STD switched off in the control setting disabled in the simulator
8 alarms defined by cooling_alarm_code___cool_std.json
Code Severity Alarm Watched register Rule Writes
COOL-1003 critical Leak Detected
Leak detected: coolant is escaping the loop.
leak_detected truthy
reset writes 0
COOL-1002 major High Pressure Alarm
High pressure alarm: pressure has exceeded the safe limit.
high_pressure_alarm truthy
reset writes 0
COOL-1004 major Low Flow Alarm
Low flow alarm: flow has fallen below the minimum.
low_flow_alarm truthy
reset writes 0
COOL-1006 major Over Temperature Alarm
Over temperature alarm: temperature has exceeded the safe operating limit.
over_temperature_alarm truthy
reset writes 0
COOL-FLOW-LOW major Coolant Flow Low
Coolant flow rate below 5 L/min.
water_flow_rate_lpm < 5.0
reset writes 5
COOL-INLET-TEMP major Coolant Inlet Temperature High
Coolant inlet temperature above 45 degC.
coolant_inlet_temp_c > 45.0
reset writes 45
COOL-1001 warning Alarm Code
Alarm code: the meter has raised an alarm code.
alarm_code truthy
reset writes 0
COOL-1005 warning Maintenance Required
Maintenance required: a scheduled service interval has elapsed.
maintenance_required truthy
reset writes 0
pcs1 PCS-001
pcs pcs/pcs1/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs10 PCS-010
pcs pcs/pcs10/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs11 PCS-011
pcs pcs/pcs11/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs12 PCS-012
pcs pcs/pcs12/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs2 PCS-002
pcs pcs/pcs2/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs3 PCS-003
pcs pcs/pcs3/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs4 PCS-004
pcs pcs/pcs4/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs5 PCS-005
pcs pcs/pcs5/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs6 PCS-006
pcs pcs/pcs6/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs7 PCS-007
pcs pcs/pcs7/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs8 PCS-008
pcs pcs/pcs8/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
pcs9 PCS-009
pcs pcs/pcs9/pcs_register_full pcs_alarm_code___epcs105.json EMS model EPCS105 switched off in the control setting disabled in the simulator
187 alarms defined by pcs_alarm_code___epcs105.json
Code Severity Alarm Watched register Rule Writes
PCS-1004 critical A Phase Overvoltage Fault Flag
A-phase overvoltage fault: voltage has exceeded the safe operating limit.
a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1005 critical A Phase Software Overcurrent
A-phase software overcurrent: current has exceeded the safe operating limit.
a_phase_software_overcurrent truthy
reset writes 0
PCS-1006 critical A Phase Undervoltage Fault Flag
A-phase undervoltage fault: voltage has fallen below the safe operating limit.
a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1007 critical AC Main Relay Adhesion Fault
AC main relay adhesion fault: the contactor did not operate as commanded.
ac_main_relay_adhesion_fault truthy
reset writes 0
PCS-1008 critical AC Main Relay Welding Fault
AC main relay welding fault: the contactor did not operate as commanded.
ac_main_relay_welding_fault truthy
reset writes 0
PCS-1012 critical B Phase Overvoltage Fault Flag
B-phase overvoltage fault: voltage has exceeded the safe operating limit.
b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1013 critical B Phase Software Overcurrent
B-phase software overcurrent: current has exceeded the safe operating limit.
b_phase_software_overcurrent truthy
reset writes 0
PCS-1014 critical B Phase Undervoltage Fault Flag
B-phase undervoltage fault: voltage has fallen below the safe operating limit.
b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1015 critical Balancing Module Software Overcurrent
Balancing module software overcurrent: current has exceeded the safe operating limit.
balancing_module_software_overcurrent truthy
reset writes 0
PCS-1017 critical Battery Overvoltage
Battery overvoltage: voltage has exceeded the safe operating limit.
battery_overvoltage truthy
reset writes 0
PCS-1018 critical Battery Undervoltage
Battery undervoltage: voltage has fallen below the safe operating limit.
battery_undervoltage truthy
reset writes 0
PCS-1024 critical C Phase Overvoltage Fault Flag
C-phase overvoltage fault: voltage has exceeded the safe operating limit.
c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1025 critical C Phase Software Overcurrent
C-phase software overcurrent: current has exceeded the safe operating limit.
c_phase_software_overcurrent truthy
reset writes 0
PCS-1026 critical C Phase Undervoltage Fault Flag
C-phase undervoltage fault: voltage has fallen below the safe operating limit.
c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1028 critical Current Mode Bus Undervoltage
Current mode bus undervoltage: voltage has fallen below the safe operating limit.
current_mode_bus_undervoltage truthy
reset writes 0
PCS-1029 critical Current Mode Busbar Undervoltage
Current mode busbar undervoltage: voltage has fallen below the safe operating limit.
current_mode_busbar_undervoltage truthy
reset writes 0
PCS-1030 critical DC Overcurrent
DC overcurrent: current has exceeded the safe operating limit.
dc_overcurrent truthy
reset writes 0
PCS-1031 critical DC Pre Charge Overcurrent
DC pre charge overcurrent: current has exceeded the safe operating limit.
dc_pre_charge_overcurrent truthy
reset writes 0
PCS-1034 critical EPO Fault Flag
EPO fault: the emergency stop circuit has tripped.
epo_fault_flag truthy
reset writes 0
PCS-1039 critical Grid Islanding Fault Flag
Grid islanding fault: the grid connection was lost while the unit was exporting.
grid_islanding_fault_flag truthy
reset writes 0
PCS-1045 critical Inverter Voltage A Phase Overvoltage Fault Flag
Inverter voltage A-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_a_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1046 critical Inverter Voltage A Phase Undervoltage Fault Flag
Inverter voltage A-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_a_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1047 critical Inverter Voltage B Phase Overvoltage Fault Flag
Inverter voltage B-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_b_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1048 critical Inverter Voltage B Phase Undervoltage Fault Flag
Inverter voltage B-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_b_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1049 critical Inverter Voltage C Phase Overvoltage Fault Flag
Inverter voltage C-phase overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_c_phase_overvoltage_fault_flag truthy
reset writes 0
PCS-1050 critical Inverter Voltage C Phase Undervoltage Fault Flag
Inverter voltage C-phase undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_c_phase_undervoltage_fault_flag truthy
reset writes 0
PCS-1051 critical Inverter Voltage Phase A Overvoltage Fault Flag
Inverter voltage phase A overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1052 critical Inverter Voltage Phase A Undervoltage Fault Flag
Inverter voltage phase A undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1053 critical Inverter Voltage Phase B Overvoltage Fault Flag
Inverter voltage phase B overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1054 critical Inverter Voltage Phase B Undervoltage Fault Flag
Inverter voltage phase B undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1055 critical Inverter Voltage Phase C Overvoltage Fault Flag
Inverter voltage phase C overvoltage fault: voltage has exceeded the safe operating limit.
inverter_voltage_phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1056 critical Inverter Voltage Phase C Undervoltage Fault Flag
Inverter voltage phase C undervoltage fault: voltage has fallen below the safe operating limit.
inverter_voltage_phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1076 critical L1 Insulation Fault
L1 insulation fault: insulation resistance has fallen below the safe limit.
l1_insulation_fault truthy
reset writes 0
PCS-1103 critical L2 Insulation Fault
L2 insulation fault: insulation resistance has fallen below the safe limit.
l2_insulation_fault truthy
reset writes 0
PCS-1130 critical L3 Insulation Fault
L3 insulation fault: insulation resistance has fallen below the safe limit.
l3_insulation_fault truthy
reset writes 0
PCS-1141 critical N Line Overcurrent
N line overcurrent: current has exceeded the safe operating limit.
n_line_overcurrent truthy
reset writes 0
PCS-1142 critical Neutral Line Overcurrent
Neutral line overcurrent: current has exceeded the safe operating limit.
neutral_line_overcurrent truthy
reset writes 0
PCS-1144 critical Off Grid Short Circuit Fault Flag
Off grid short circuit fault: the circuit is shorted.
off_grid_short_circuit_fault_flag truthy
reset writes 0
PCS-1145 critical Operating Bus Overvoltage
Operating bus overvoltage: voltage has exceeded the safe operating limit.
operating_bus_overvoltage truthy
reset writes 0
PCS-1146 critical Operating Bus Undervoltage
Operating bus undervoltage: voltage has fallen below the safe operating limit.
operating_bus_undervoltage truthy
reset writes 0
PCS-1147 critical Overload Fault Flag Specific Customer
Overload fault flag specific customer: load has exceeded the rated capacity.
overload_fault_flag_specific_customer truthy
reset writes 0
PCS-1150 critical Phase A Overvoltage Fault Flag
Phase A overvoltage fault: voltage has exceeded the safe operating limit.
phase_a_overvoltage_fault_flag truthy
reset writes 0
PCS-1151 critical Phase A Software Overcurrent
Phase A software overcurrent: current has exceeded the safe operating limit.
phase_a_software_overcurrent truthy
reset writes 0
PCS-1152 critical Phase A Undervoltage Fault Flag
Phase A undervoltage fault: voltage has fallen below the safe operating limit.
phase_a_undervoltage_fault_flag truthy
reset writes 0
PCS-1153 critical Phase B Overvoltage Fault Flag
Phase B overvoltage fault: voltage has exceeded the safe operating limit.
phase_b_overvoltage_fault_flag truthy
reset writes 0
PCS-1154 critical Phase B Software Overcurrent
Phase B software overcurrent: current has exceeded the safe operating limit.
phase_b_software_overcurrent truthy
reset writes 0
PCS-1155 critical Phase B Undervoltage Fault Flag
Phase B undervoltage fault: voltage has fallen below the safe operating limit.
phase_b_undervoltage_fault_flag truthy
reset writes 0
PCS-1156 critical Phase C Overvoltage Fault Flag
Phase C overvoltage fault: voltage has exceeded the safe operating limit.
phase_c_overvoltage_fault_flag truthy
reset writes 0
PCS-1157 critical Phase C Software Overcurrent
Phase C software overcurrent: current has exceeded the safe operating limit.
phase_c_software_overcurrent truthy
reset writes 0
PCS-1158 critical Phase C Undervoltage Fault Flag
Phase C undervoltage fault: voltage has fallen below the safe operating limit.
phase_c_undervoltage_fault_flag truthy
reset writes 0
PCS-1160 critical Positive Negative Busbar Imbalance
Positive negative busbar imbalance: the spread between the measured values is above the allowed limit.
positive_negative_busbar_imbalance truthy
reset writes 0
PCS-1161 critical Pre Charge A Phase Overcurrent
Pre charge A-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_a_phase_overcurrent truthy
reset writes 0
PCS-1162 critical Pre Charge B Phase Overcurrent
Pre charge B-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_b_phase_overcurrent truthy
reset writes 0
PCS-1163 critical Pre Charge Bus Overvoltage
Pre charge bus overvoltage: voltage has exceeded the safe operating limit.
pre_charge_bus_overvoltage truthy
reset writes 0
PCS-1164 critical Pre Charge Bus Undervoltage
Pre charge bus undervoltage: voltage has fallen below the safe operating limit.
pre_charge_bus_undervoltage truthy
reset writes 0
PCS-1165 critical Pre Charge Busbar Overvoltage
Pre charge busbar overvoltage: voltage has exceeded the safe operating limit.
pre_charge_busbar_overvoltage truthy
reset writes 0
PCS-1166 critical Pre Charge Busbar Undervoltage
Pre charge busbar undervoltage: voltage has fallen below the safe operating limit.
pre_charge_busbar_undervoltage truthy
reset writes 0
PCS-1167 critical Pre Charge C Phase Overcurrent
Pre charge C-phase overcurrent: current has exceeded the safe operating limit.
pre_charge_c_phase_overcurrent truthy
reset writes 0
PCS-1168 critical Pre Charge Phase A Overcurrent
Pre charge phase A overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_a_overcurrent truthy
reset writes 0
PCS-1169 critical Pre Charge Phase B Overcurrent
Pre charge phase B overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_b_overcurrent truthy
reset writes 0
PCS-1170 critical Pre Charge Phase C Overcurrent
Pre charge phase C overcurrent: current has exceeded the safe operating limit.
pre_charge_phase_c_overcurrent truthy
reset writes 0
PCS-1174 critical Running Busbar Overvoltage
Running busbar overvoltage: voltage has exceeded the safe operating limit.
running_busbar_overvoltage truthy
reset writes 0
PCS-1175 critical Running Busbar Undervoltage
Running busbar undervoltage: voltage has fallen below the safe operating limit.
running_busbar_undervoltage truthy
reset writes 0
PCS-1178 critical Surge Protector Fault
Surge protector fault: the surge protection device has failed.
surge_protector_fault truthy
reset writes 0
PCS-1179 critical System Fire Alarm Fault Flag
System fire alarm fault: the fire-safety input is active.
system_fire_alarm_fault_flag truthy
reset writes 0
PCS-1180 critical System Resonance Fault Flag
System resonance fault: resonance detected in the output filter.
system_resonance_fault_flag truthy
reset writes 0
PCS-1182 critical Uncontrolled Rectification Busbar Overvoltage
Uncontrolled rectification busbar overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectification_busbar_overvoltage truthy
reset writes 0
PCS-1183 critical Uncontrolled Rectification Busbar Undervoltage
Uncontrolled rectification busbar undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectification_busbar_undervoltage truthy
reset writes 0
PCS-1184 critical Uncontrolled Rectifier Bus Overvoltage
Uncontrolled rectifier bus overvoltage: voltage has exceeded the safe operating limit.
uncontrolled_rectifier_bus_overvoltage truthy
reset writes 0
PCS-1185 critical Uncontrolled Rectifier Bus Undervoltage
Uncontrolled rectifier bus undervoltage: voltage has fallen below the safe operating limit.
uncontrolled_rectifier_bus_undervoltage truthy
reset writes 0
PCS-SOC-LOW critical Battery SOC Critically Low
Battery state of charge below 3%, discharge must stop.
soc_state_of_charge_item < 3.0
reset writes 3
PCS-1001 major 15v Power Supply Fault Flag
15 V power supply fault: the internal supply voltage is out of range.
15v_power_supply_fault_flag truthy
reset writes 0
PCS-1002 major 1 Cell Voltage Too High
1 cell voltage too high: the measured value is above the safe operating limit.
1_cell_voltage_too_high truthy
reset writes 0
PCS-1003 major 24v Power Supply Fault Flag
24 V power supply fault: the internal supply voltage is out of range.
24v_power_supply_fault_flag truthy
reset writes 0
PCS-1009 major AD Sampling Zero Drift Fault
AD sampling zero drift fault: the measurement has drifted from its reference.
ad_sampling_zero_drift_fault truthy
reset writes 0
PCS-1011 major Air Conditioner Fault
Air conditioner fault: the device reports this fault as active.
air_conditioner_fault truthy
reset writes 0
PCS-1016 major Battery Dry Contact Fault Flag
Battery dry contact fault: the device reports this fault as active.
battery_dry_contact_fault_flag truthy
reset writes 0
PCS-1019 major BMS Battery System Fault
BMS battery system fault: the device reports this fault as active.
bms_battery_system_fault truthy
reset writes 0
PCS-1020 major BMS Communication Fault
BMS communication fault: the device has stopped responding.
bms_communication_fault truthy
reset writes 0
PCS-1021 major BMS Level 1 Alarm
BMS level 1 alarm: protection level 1 has tripped.
bms_level_1_alarm truthy
reset writes 0
PCS-1022 major BMS Level 2 Alarm
BMS level 2 alarm: protection level 2 has tripped.
bms_level_2_alarm truthy
reset writes 0
PCS-1023 major BMS Level 3 Alarm
BMS level 3 alarm: protection level 3 has tripped.
bms_level_3_alarm truthy
reset writes 0
PCS-1027 major Connection Fault Flag
Connection fault: the device reports this fault as active.
connection_fault_flag truthy
reset writes 0
PCS-1032 major DC Relay Open Circuit Fault
DC relay open circuit fault: the circuit is open where it should be closed.
dc_relay_open_circuit_fault truthy
reset writes 0
PCS-1033 major Ems Communication Fault
EMS communication fault: the device has stopped responding.
ems_communication_fault truthy
reset writes 0
PCS-1035 major Fan Fault Flag
Fan fault: the device reports this fault as active.
fan_fault_flag truthy
reset writes 0
PCS-1036 major Gas Alarm
Gas alarm: the fire-safety input is active.
gas_alarm truthy
reset writes 0
PCS-1037 major Grid Current Imbalance
Grid current imbalance: the spread between the measured values is above the allowed limit.
grid_current_imbalance truthy
reset writes 0
PCS-1038 major Grid Current Unbalance
Grid current unbalance: the spread between the measured values is above the allowed limit.
grid_current_unbalance truthy
reset writes 0
PCS-1042 major Grid Voltage Imbalance
Grid voltage imbalance: the spread between the measured values is above the allowed limit.
grid_voltage_imbalance truthy
reset writes 0
PCS-1043 major Grid Voltage Unbalance
Grid voltage unbalance: the spread between the measured values is above the allowed limit.
grid_voltage_unbalance truthy
reset writes 0
PCS-1044 major High Voltage Ride Through Timeout Fault Flag
High voltage ride through timeout fault: the ride-through window expired before the grid recovered.
high_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1057 major L1 AFE Chip Fault
L1 AFE chip fault: the device reports this fault as active.
l1_afe_chip_fault truthy
reset writes 0
PCS-1058 major L1 Balancing Circuit Fault
L1 balancing circuit fault: the device reports this fault as active.
l1_balancing_circuit_fault truthy
reset writes 0
PCS-1059 major L1 Battery Charge Temperature Too High
L1 battery charge temperature too high: the measured value is above the safe operating limit.
l1_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1060 major L1 Battery Charge Temperature Too Low
L1 battery charge temperature too low: the measured value is below the safe operating limit.
l1_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1061 major L1 Battery Discharge Temperature Too High
L1 battery discharge temperature too high: the measured value is above the safe operating limit.
l1_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1062 major L1 Battery Discharge Temperature Too Low
L1 battery discharge temperature too low: the measured value is below the safe operating limit.
l1_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1063 major L1 BMS Fault
L1 BMS fault: the device reports this fault as active.
l1_bms_fault truthy
reset writes 0
PCS-1064 major L1 Cell Temperature Difference Excessive
L1 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1065 major L1 Cell Temperature Difference Too Large
L1 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l1_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1066 major L1 Cell Temperature Fault
L1 cell temperature fault: the device reports this fault as active.
l1_cell_temperature_fault truthy
reset writes 0
PCS-1067 major L1 Cell Voltage Difference Excessive
L1 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1069 major L1 Cell Voltage Fault
L1 cell voltage fault: the device reports this fault as active.
l1_cell_voltage_fault truthy
reset writes 0
PCS-1070 major L1 Cell Voltage Too Low
L1 cell voltage too low: the measured value is below the safe operating limit.
l1_cell_voltage_too_low truthy
reset writes 0
PCS-1071 major L1 Charging Current Too High
L1 charging current too high: the measured value is above the safe operating limit.
l1_charging_current_too_high truthy
reset writes 0
PCS-1072 major L1 Communication Fault
L1 communication fault: the device has stopped responding.
l1_communication_fault truthy
reset writes 0
PCS-1073 major L1 Current Sensor Fault
L1 current sensor fault: the sensor reading is not reliable.
l1_current_sensor_fault truthy
reset writes 0
PCS-1074 major L1 Discharging Current Too High
L1 discharging current too high: the measured value is above the safe operating limit.
l1_discharging_current_too_high truthy
reset writes 0
PCS-1075 major L1 Equalization Circuit Fault
L1 equalization circuit fault: the device reports this fault as active.
l1_equalization_circuit_fault truthy
reset writes 0
PCS-1077 major L1 Main Negative Relay Fault
L1 main negative relay fault: the device reports this fault as active.
l1_main_negative_relay_fault truthy
reset writes 0
PCS-1078 major L1 Main Positive Relay Fault
L1 main positive relay fault: the device reports this fault as active.
l1_main_positive_relay_fault truthy
reset writes 0
PCS-1079 major L1 Pre Charge Failure
L1 pre charge failure: the contactor did not reach the commanded state.
l1_pre_charge_failure truthy
reset writes 0
PCS-1080 major L1 Pre Charging Failure
L1 pre charging failure: the contactor did not reach the commanded state.
l1_pre_charging_failure truthy
reset writes 0
PCS-1081 major L1 Total Voltage Too High
L1 total voltage too high: the measured value is above the safe operating limit.
l1_total_voltage_too_high truthy
reset writes 0
PCS-1082 major L1 Total Voltage Too Low
L1 total voltage too low: the measured value is below the safe operating limit.
l1_total_voltage_too_low truthy
reset writes 0
PCS-1083 major L2 AFE Chip Fault
L2 AFE chip fault: the device reports this fault as active.
l2_afe_chip_fault truthy
reset writes 0
PCS-1084 major L2 Balancing Circuit Fault
L2 balancing circuit fault: the device reports this fault as active.
l2_balancing_circuit_fault truthy
reset writes 0
PCS-1085 major L2 Battery Charge Temperature Too High
L2 battery charge temperature too high: the measured value is above the safe operating limit.
l2_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1086 major L2 Battery Charge Temperature Too Low
L2 battery charge temperature too low: the measured value is below the safe operating limit.
l2_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1087 major L2 Battery Discharge Temperature Too High
L2 battery discharge temperature too high: the measured value is above the safe operating limit.
l2_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1088 major L2 Battery Discharge Temperature Too Low
L2 battery discharge temperature too low: the measured value is below the safe operating limit.
l2_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1089 major L2 BMS Fault
L2 BMS fault: the device reports this fault as active.
l2_bms_fault truthy
reset writes 0
PCS-1090 major L2 Cell Temperature Difference Excessive
L2 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1091 major L2 Cell Temperature Difference Too Large
L2 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l2_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1092 major L2 Cell Temperature Fault
L2 cell temperature fault: the device reports this fault as active.
l2_cell_temperature_fault truthy
reset writes 0
PCS-1093 major L2 Cell Voltage Difference Excessive
L2 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1095 major L2 Cell Voltage Fault
L2 cell voltage fault: the device reports this fault as active.
l2_cell_voltage_fault truthy
reset writes 0
PCS-1096 major L2 Cell Voltage Too High
L2 cell voltage too high: the measured value is above the safe operating limit.
l2_cell_voltage_too_high truthy
reset writes 0
PCS-1097 major L2 Cell Voltage Too Low
L2 cell voltage too low: the measured value is below the safe operating limit.
l2_cell_voltage_too_low truthy
reset writes 0
PCS-1098 major L2 Charging Current Too High
L2 charging current too high: the measured value is above the safe operating limit.
l2_charging_current_too_high truthy
reset writes 0
PCS-1099 major L2 Communication Fault
L2 communication fault: the device has stopped responding.
l2_communication_fault truthy
reset writes 0
PCS-1100 major L2 Current Sensor Fault
L2 current sensor fault: the sensor reading is not reliable.
l2_current_sensor_fault truthy
reset writes 0
PCS-1101 major L2 Discharging Current Too High
L2 discharging current too high: the measured value is above the safe operating limit.
l2_discharging_current_too_high truthy
reset writes 0
PCS-1102 major L2 Equalization Circuit Fault
L2 equalization circuit fault: the device reports this fault as active.
l2_equalization_circuit_fault truthy
reset writes 0
PCS-1104 major L2 Main Negative Relay Fault
L2 main negative relay fault: the device reports this fault as active.
l2_main_negative_relay_fault truthy
reset writes 0
PCS-1105 major L2 Main Positive Relay Fault
L2 main positive relay fault: the device reports this fault as active.
l2_main_positive_relay_fault truthy
reset writes 0
PCS-1106 major L2 Pre Charge Failure
L2 pre charge failure: the contactor did not reach the commanded state.
l2_pre_charge_failure truthy
reset writes 0
PCS-1107 major L2 Pre Charging Failure
L2 pre charging failure: the contactor did not reach the commanded state.
l2_pre_charging_failure truthy
reset writes 0
PCS-1108 major L2 Total Voltage Too High
L2 total voltage too high: the measured value is above the safe operating limit.
l2_total_voltage_too_high truthy
reset writes 0
PCS-1109 major L2 Total Voltage Too Low
L2 total voltage too low: the measured value is below the safe operating limit.
l2_total_voltage_too_low truthy
reset writes 0
PCS-1110 major L3 AFE Chip Fault
L3 AFE chip fault: the device reports this fault as active.
l3_afe_chip_fault truthy
reset writes 0
PCS-1111 major L3 Balancing Circuit Fault
L3 balancing circuit fault: the device reports this fault as active.
l3_balancing_circuit_fault truthy
reset writes 0
PCS-1112 major L3 Battery Charge Temperature Too High
L3 battery charge temperature too high: the measured value is above the safe operating limit.
l3_battery_charge_temperature_too_high truthy
reset writes 0
PCS-1113 major L3 Battery Charge Temperature Too Low
L3 battery charge temperature too low: the measured value is below the safe operating limit.
l3_battery_charge_temperature_too_low truthy
reset writes 0
PCS-1114 major L3 Battery Discharge Temperature Too High
L3 battery discharge temperature too high: the measured value is above the safe operating limit.
l3_battery_discharge_temperature_too_high truthy
reset writes 0
PCS-1115 major L3 Battery Discharge Temperature Too Low
L3 battery discharge temperature too low: the measured value is below the safe operating limit.
l3_battery_discharge_temperature_too_low truthy
reset writes 0
PCS-1116 major L3 BMS Fault
L3 BMS fault: the device reports this fault as active.
l3_bms_fault truthy
reset writes 0
PCS-1117 major L3 Cell Temperature Difference Excessive
L3 cell temperature difference excessive: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_excessive truthy
reset writes 0
PCS-1118 major L3 Cell Temperature Difference Too Large
L3 cell temperature difference too large: the temperature spread between cells is above the allowed limit.
l3_cell_temperature_difference_too_large truthy
reset writes 0
PCS-1119 major L3 Cell Temperature Fault
L3 cell temperature fault: the device reports this fault as active.
l3_cell_temperature_fault truthy
reset writes 0
PCS-1120 major L3 Cell Voltage Difference Excessive
L3 cell voltage difference excessive: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_excessive truthy
reset writes 0
PCS-1122 major L3 Cell Voltage Fault
L3 cell voltage fault: the device reports this fault as active.
l3_cell_voltage_fault truthy
reset writes 0
PCS-1123 major L3 Cell Voltage Too High
L3 cell voltage too high: the measured value is above the safe operating limit.
l3_cell_voltage_too_high truthy
reset writes 0
PCS-1124 major L3 Cell Voltage Too Low
L3 cell voltage too low: the measured value is below the safe operating limit.
l3_cell_voltage_too_low truthy
reset writes 0
PCS-1125 major L3 Charging Current Too High
L3 charging current too high: the measured value is above the safe operating limit.
l3_charging_current_too_high truthy
reset writes 0
PCS-1126 major L3 Communication Fault
L3 communication fault: the device has stopped responding.
l3_communication_fault truthy
reset writes 0
PCS-1127 major L3 Current Sensor Fault
L3 current sensor fault: the sensor reading is not reliable.
l3_current_sensor_fault truthy
reset writes 0
PCS-1128 major L3 Discharging Current Too High
L3 discharging current too high: the measured value is above the safe operating limit.
l3_discharging_current_too_high truthy
reset writes 0
PCS-1129 major L3 Equalization Circuit Fault
L3 equalization circuit fault: the device reports this fault as active.
l3_equalization_circuit_fault truthy
reset writes 0
PCS-1131 major L3 Main Negative Relay Fault
L3 main negative relay fault: the device reports this fault as active.
l3_main_negative_relay_fault truthy
reset writes 0
PCS-1132 major L3 Main Positive Relay Fault
L3 main positive relay fault: the device reports this fault as active.
l3_main_positive_relay_fault truthy
reset writes 0
PCS-1133 major L3 Pre Charge Failure
L3 pre charge failure: the contactor did not reach the commanded state.
l3_pre_charge_failure truthy
reset writes 0
PCS-1134 major L3 Pre Charging Failure
L3 pre charging failure: the contactor did not reach the commanded state.
l3_pre_charging_failure truthy
reset writes 0
PCS-1135 major L3 Total Voltage Too High
L3 total voltage too high: the measured value is above the safe operating limit.
l3_total_voltage_too_high truthy
reset writes 0
PCS-1136 major L3 Total Voltage Too Low
L3 total voltage too low: the measured value is below the safe operating limit.
l3_total_voltage_too_low truthy
reset writes 0
PCS-1137 major Low Voltage Ride Through Timeout Fault Flag
Low voltage ride through timeout fault: the ride-through window expired before the grid recovered.
low_voltage_ride_through_timeout_fault_flag truthy
reset writes 0
PCS-1138 major Main Relay Closing Failure
Main relay closing failure: the contactor did not reach the commanded state.
main_relay_closing_failure truthy
reset writes 0
PCS-1139 major Main Relay Closure Failure
Main relay closure failure: the contactor did not reach the commanded state.
main_relay_closure_failure truthy
reset writes 0
PCS-1140 major Main Relay Opening Failure
Main relay opening failure: the contactor did not reach the commanded state.
main_relay_opening_failure truthy
reset writes 0
PCS-1143 major Off Grid No Synchronization Signal Fault Flag
Off grid no synchronization signal fault: the grid reference signal is absent.
off_grid_no_synchronization_signal_fault_flag truthy
reset writes 0
PCS-1149 major PCS Fault Present
PCS fault present: the device reports this fault as active.
pcs_fault_present truthy
reset writes 0
PCS-1159 major Positive And Negative Bus Unbalance
Positive and negative bus unbalance: the spread between the measured values is above the allowed limit.
positive_and_negative_bus_unbalance truthy
reset writes 0
PCS-1171 major Pre Charge Relay Closing Failure
Pre charge relay closing failure: the contactor did not reach the commanded state.
pre_charge_relay_closing_failure truthy
reset writes 0
PCS-1172 major Pre Charge Relay Closure Failure
Pre charge relay closure failure: the contactor did not reach the commanded state.
pre_charge_relay_closure_failure truthy
reset writes 0
PCS-1173 major Pre Charge Relay Opening Failure
Pre charge relay opening failure: the contactor did not reach the commanded state.
pre_charge_relay_opening_failure truthy
reset writes 0
PCS-1176 major Slave Module CAN Communication Fault
Slave module CAN communication fault: the device has stopped responding.
slave_module_can_communication_fault truthy
reset writes 0
PCS-1177 major STS Communication Fault
STS communication fault: the device has stopped responding.
sts_communication_fault truthy
reset writes 0
PCS-1181 major Temperature Alarm
Temperature alarm: the device reports this alarm as active.
temperature_alarm truthy
reset writes 0
PCS-1010 warning Air Conditioner Alarm
Air conditioner alarm: the device reports this alarm as active.
air_conditioner_alarm truthy
reset writes 0
PCS-1040 warning Grid Overfrequency
Grid overfrequency: grid frequency has exceeded the trip limit.
grid_overfrequency truthy
reset writes 0
PCS-1041 warning Grid Underfrequency
Grid underfrequency: grid frequency has fallen below the trip limit.
grid_underfrequency truthy
reset writes 0
PCS-1068 warning L1 Cell Voltage Difference Too Large
L1 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l1_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1094 warning L2 Cell Voltage Difference Too Large
L2 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l2_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1121 warning L3 Cell Voltage Difference Too Large
L3 cell voltage difference too large: the voltage spread between cells is above the allowed limit.
l3_cell_voltage_difference_too_large truthy
reset writes 0
PCS-1148 warning PCS Alarm Present
PCS alarm present: the device reports this alarm as active.
pcs_alarm_present truthy
reset writes 0
PCS-SOH-LOW warning Battery SOH Low
Battery state of health below 80%.
soh_state_of_health_item < 80.0
reset writes 80
plc1 PLC-001
plcs plc/plc1/plc_register_full plc_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
2 alarms defined by plc_alarm_code.json
Code Severity Alarm Watched register Rule Writes
PLC-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
PLC-1003 minor PLC Not Running
The PLC is not in run mode.
plc_running falsy
zero may be ignored
reset writes 1
relay_box1 RELAY-BOX-001
relay_boxes relay_box/relay_box1/relay_box_register_full relay_box_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
3 alarms defined by relay_box_alarm_code.json
Code Severity Alarm Watched register Rule Writes
RLB-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
RLB-1002 minor Relay Command Timeout
A relay did not report the commanded position within the timeout.
relay_command_timeout truthy
reset writes 0
RLB-1003 minor Relay Feedback Mismatch
A relay's reported position disagrees with the commanded position.
relay_feedback_mismatch truthy
reset writes 0
relay_box2 RELAY-BOX-002
relay_boxes relay_box/relay_box2/relay_box_register_full relay_box_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
3 alarms defined by relay_box_alarm_code.json
Code Severity Alarm Watched register Rule Writes
RLB-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
RLB-1002 minor Relay Command Timeout
A relay did not report the commanded position within the timeout.
relay_command_timeout truthy
reset writes 0
RLB-1003 minor Relay Feedback Mismatch
A relay's reported position disagrees with the commanded position.
relay_feedback_mismatch truthy
reset writes 0
sensor_block1 SENSOR-BLOCK-001
sensor_blocks sensor_block/sensorb1/sensorb_register_full sensorB_alarm_code___sens_std.json EMS model SENS_STD switched off in the control setting disabled in the simulator
3 alarms defined by sensorB_alarm_code___sens_std.json
Code Severity Alarm Watched register Rule Writes
SENSB-RH1-HIGH major Humidity 1 High
Humidity channel 1 reads above 85 %RH.
humidity_sensor_1_percent > 85.0
reset writes 85
SENSB-RH2-HIGH major Humidity 2 High
Humidity channel 2 reads above 85 %RH.
humidity_sensor_2_percent > 85.0
reset writes 85
SENSB-ALARM-RELAY warning Alarm Relay Energised
The sensor block alarm activation relay is energised.
alarm_activation_relay truthy
reset writes 0
smoke_detector1 SMOKE-DETECTOR-001
smoke_detectors smoke_sensor/smoke_sensor1/smoke_sensor_register_full smoke_sensor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
3 alarms defined by smoke_sensor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
SMOKE-ALARM-1 critical Smoke Alarm
Smoke detector alarm bit is set (bit 0).
alarm_bitmap bit 0
reset writes bit 0 off
SMOKE-FAULT-1 major Smoke Detector Fault
Smoke detector fault bit is set (bit 1).
alarm_bitmap bit 1
reset writes bit 1 off
SMOKE-TEST-1 minor Smoke Detector Test
Smoke detector test bit is set (bit 2).
alarm_bitmap bit 2
reset writes bit 2 off
solar_meter1 SOLAR-METER-001
solar_meters solar_energy_meter/solar_meter1/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter10 SOLAR-METER-010
solar_meters solar_energy_meter/solar_meter10/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter11 SOLAR-METER-011
solar_meters solar_energy_meter/solar_meter11/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter12 SOLAR-METER-012
solar_meters solar_energy_meter/solar_meter12/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter2 SOLAR-METER-002
solar_meters solar_energy_meter/solar_meter2/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter3 SOLAR-METER-003
solar_meters solar_energy_meter/solar_meter3/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter4 SOLAR-METER-004
solar_meters solar_energy_meter/solar_meter4/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter5 SOLAR-METER-005
solar_meters solar_energy_meter/solar_meter5/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter6 SOLAR-METER-006
solar_meters solar_energy_meter/solar_meter6/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter7 SOLAR-METER-007
solar_meters solar_energy_meter/solar_meter7/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter8 SOLAR-METER-008
solar_meters solar_energy_meter/solar_meter8/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
solar_meter9 SOLAR-METER-009
solar_meters solar_energy_meter/solar_meter9/solarmeter_register_full solarMeter_alarm_code___me231.json EMS model ME231 switched off in the control setting disabled in the simulator
4 alarms defined by solarMeter_alarm_code___me231.json
Code Severity Alarm Watched register Rule Writes
SOLAR-OF major Solar Over Frequency
Frequency above 50.5 Hz.
frequency_hz > 50.5
reset writes 50.5
SOLAR-UF major Solar Under Frequency
Frequency below 49.5 Hz.
frequency_hz < 49.5
reset writes 49.5
SOLAR-1001 warning Alarms
Alarms: the meter has raised an alarm code.
alarms truthy
reset writes 0
SOLAR-PF-LOW warning Solar Power Factor Low
Power factor below 0.8.
pf_total < 0.8
reset writes 0.8
sts1 STS-001
sts_units sts/sts1/sts_register_full sts_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting no reading yet
4 alarms defined by sts_alarm_code.json
Code Severity Alarm Watched register Rule Writes
STS-1001 major Communication Fault
The device stopped answering: no valid response within the poll timeout.
communication_fault truthy
reset writes 0
STS-1002 major Source 1 Unavailable
Source 1 is not presenting a usable supply.
source_1_available falsy
zero may be ignored
reset writes 1
STS-1003 major Source 2 Unavailable
Source 2 is not presenting a usable supply.
source_2_available falsy
zero may be ignored
reset writes 1
STS-1005 major Switching Fault
The STS reports a switching fault.
switching_fault truthy
reset writes 0
temperature_sensor1 TEMP-SENSOR-001
temperature_sensors temperature_sensor/temperature_sensor1/temperature_sensor_register_full temperature_sensor_alarm_code.json EMS model ME231 no model-specific map switched off in the control setting
4 alarms defined by temperature_sensor_alarm_code.json
Code Severity Alarm Watched register Rule Writes
TEMP-1-HIGH major Temperature 1 High
Temperature channel 1 reads above 60 degC.
temp_sensor_1_c > 60.0
reset writes 60
TEMP-2-HIGH major Temperature 2 High
Temperature channel 2 reads above 60 degC.
temp_sensor_2_c > 60.0
reset writes 60
TEMP-3-HIGH major Temperature 3 High
Temperature channel 3 reads above 60 degC.
temp_sensor_3_c > 60.0
reset writes 60
TEMP-4-HIGH major Temperature 4 High
Temperature channel 4 reads above 60 degC.
temp_sensor_4_c > 60.0
reset writes 60
ups1 ups_unit
ups_units ups/ups1/ups_register_full ups_alarm_code___ups_10k.json EMS model UPS_10K switched off in the control setting
13 alarms defined by ups_alarm_code___ups_10k.json
Code Severity Alarm Watched register Rule Writes
UPS-1007 critical Output Short Circuit
Output short circuit: the circuit is shorted.
output_short_circuit truthy
reset writes 0
UPS-1008 critical Overload
Overload: load has exceeded the rated capacity.
overload truthy
reset writes 0
UPS-1001 major Alarm Count
Alarm count: number of events recorded since the last reset.
alarm_count > 0.0
reset writes 0
UPS-1002 major Battery Low
Battery low: charge is below the operating limit.
battery_low truthy
reset writes 0
UPS-1004 major Fan Fault
Fan fault: the device reports this fault as active.
fan_fault truthy
reset writes 0
UPS-1009 major Overtemperature
Overtemperature: temperature has exceeded the safe operating limit.
overtemperature truthy
reset writes 0
UPS-1010 major UPS Fault
UPS fault: the device reports this fault as active.
ups_fault truthy
reset writes 0
UPS-BATT-CAP major Battery Capacity Low
Battery capacity below 20% of rated.
battery_capacity_percent < 20.0
reset writes 20
UPS-BATT-RUNTIME major Battery Runtime Low
Remaining battery runtime below 5 minutes.
battery_runtime_min < 5.0
reset writes 5
UPS-BATT-TEMP major Battery Temperature High
Battery temperature above 50 degC.
battery_temperature_c > 50.0
reset writes 50
UPS-1003 warning Bypass Active
Bypass active: the load is being supplied through the bypass path.
bypass_active truthy
reset writes 0
UPS-1005 warning Input Line Fail
Input line fail: the supply input is not present.
input_line_fail truthy
reset writes 0
UPS-1006 warning On Battery
On battery: the mains supply has failed.
on_battery truthy
reset writes 0