EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-18T23:32:56+00:00 (from cache)
Size: 2,146,664 bytes · sha256 40fc72a0cec6

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
1 INT16U 1 read/write ems__control ems_operation_mode
ems_operation_mode
23 enum values
2 Use → row 6
2 INT16U 1 read/write ems__control ems_control_mode
ems_control_mode
3 enum values
0 Use → row 6
3 INT16U 1 read only ems__status ems_operation_status
ems_operation_status
23 enum values
0
unset
Use → row 6
4 INT16U 1 read/write ems__control control_settings__ems_refresh_rate_hz
control_settings › ems_refresh_rate_hz
2 Use → row 6
5 INT16U 1 read only ems__status active_function_count 4 Use → row 6
6 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__enabled
functions › Payload_Diagnostic_Test › enabled
1 Use → row 6
7 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__test_duration_sec
functions › Payload_Diagnostic_Test › test_duration_sec
30 Use → row 6
8 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__ffr_fcr_response_test
functions › Payload_Diagnostic_Test › bess › ffr_fcr_response_test
1 Use → row 6
9 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__active_reactive_power_test
functions › Payload_Diagnostic_Test › bess › active_reactive_power_test
1 Use → row 6
10 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__capacity_test
functions › Payload_Diagnostic_Test › bess › capacity_test
1 Use → row 6
11 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__internal_resistance_test
functions › Payload_Diagnostic_Test › bess › internal_resistance_test
1 Use → row 6
12 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__thermal_response_test
functions › Payload_Diagnostic_Test › bess › thermal_response_test
1 Use → row 6
13 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__ocv_test
functions › Payload_Diagnostic_Test › bess › ocv_test
1 Use → row 6
14 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__bess__grid_forming_test
functions › Payload_Diagnostic_Test › bess › grid_forming_test
1 Use → row 6
15 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__charging_power_current_test
functions › Payload_Diagnostic_Test › ev_charger › charging_power_current_test
1 Use → row 6
16 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__charging_efficiency_test
functions › Payload_Diagnostic_Test › ev_charger › charging_efficiency_test
1 Use → row 6
17 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__load_balancing_response_test
functions › Payload_Diagnostic_Test › ev_charger › load_balancing_response_test
1 Use → row 6
18 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__ramp_rate_test
functions › Payload_Diagnostic_Test › ev_charger › ramp_rate_test
1 Use → row 6
19 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__interruption_recovery_test
functions › Payload_Diagnostic_Test › ev_charger › interruption_recovery_test
1 Use → row 6
20 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__energy_measurement_accuracy_test
functions › Payload_Diagnostic_Test › ev_charger › energy_measurement_accuracy_test
1 Use → row 6
21 INT16U 1 read/write ems__control functions__Payload_Diagnostic_Test__ev_charger__session_performance_test
functions › Payload_Diagnostic_Test › ev_charger › session_performance_test
1 Use → row 6
22 INT16U 1 read/write ems__control functions__Self_Test__enabled
functions › Self_Test › enabled
1 Use → row 6
23 INT16U 1 read/write ems__control functions__Self_Test__alarm_diagnostic_test__include_self_test_alarms
functions › Self_Test › alarm_diagnostic_test › include_self_test_alarms
1 Use → row 6
24 INT16U 1 read/write ems__control functions__Self_Test__alarm_diagnostic_test__appear_timeout_s
functions › Self_Test › alarm_diagnostic_test › appear_timeout_s
30 Use → row 6
25 INT16U 1 read/write ems__control functions__Self_Test__alarm_diagnostic_test__clear_timeout_s
functions › Self_Test › alarm_diagnostic_test › clear_timeout_s
45 Use → row 6
26 INT16U 1 read/write ems__control functions__Self_Test__alarm_diagnostic_test__row_settle_s
functions › Self_Test › alarm_diagnostic_test › row_settle_s
8 Use → row 6
27 INT16U 1 read/write ems__control functions__Self_Test__alarm_diagnostic_test__max_alarms_per_device
functions › Self_Test › alarm_diagnostic_test › max_alarms_per_device
0 Use → row 6
28 FLOAT32 2 read/write ems__control functions__Self_Test__alarm_diagnostic_test__simulator_url
functions › Self_Test › alarm_diagnostic_test › simulator_url
0
unset
Use → row 6
30 INT16U 1 read/write ems__control functions__Manual_Operation__enabled
functions › Manual_Operation › enabled
1 Use → row 6
31 INT16U 1 read/write ems__control functions__Manual_Operation__power_setpoint_kw
functions › Manual_Operation › power_setpoint_kw
40 Use → row 6
32 INT16U 1 read/write ems__control functions__Manual_Operation__ramp_rate_kw_s
functions › Manual_Operation › ramp_rate_kw_s
1 Use → row 6
33 INT16U 1 read/write ems__control functions__Manual_Operation__soc_limits__min_soc_pct
functions › Manual_Operation › soc_limits › min_soc_pct
10 Use → row 6
34 INT16U 1 read/write ems__control functions__Manual_Operation__soc_limits__max_soc_pct
functions › Manual_Operation › soc_limits › max_soc_pct
80 Use → row 6
35 INT16U 1 read/write ems__control functions__Manual_Operation__soc_recovery_target_pct
functions › Manual_Operation › soc_recovery_target_pct
12 Use → row 6
36 INT16U 1 read/write ems__control functions__Manual_Operation__power_caps_kw__charge_cap_kw
functions › Manual_Operation › power_caps_kw › charge_cap_kw
100 Use → row 6
37 INT16U 1 read/write ems__control functions__Manual_Operation__power_caps_kw__discharge_cap_kw
functions › Manual_Operation › power_caps_kw › discharge_cap_kw
70 Use → row 6
38 INT16U 1 read/write ems__control functions__Manual_Operation__telemetry_control__command_confirmation
functions › Manual_Operation › telemetry_control › command_confirmation
1 Use → row 6
39 INT16U 1 read/write ems__control functions__Manual_Operation__safety__trip_on_overvoltage
functions › Manual_Operation › safety › trip_on_overvoltage
1 Use → row 6
40 INT16U 1 read/write ems__control functions__Manual_Operation__safety__trip_on_undervoltage
functions › Manual_Operation › safety › trip_on_undervoltage
1 Use → row 6
41 INT16U 1 read/write ems__control functions__Manual_Operation__safety__trip_on_overtemperature
functions › Manual_Operation › safety › trip_on_overtemperature
1 Use → row 6
42 INT16U 1 read/write ems__control functions__Arbitrage__enabled
functions › Arbitrage › enabled
0 Use → row 6
43 INT16U 1 read/write ems__control functions__Arbitrage__tick__interval_seconds
functions › Arbitrage › tick › interval_seconds
300 Use → row 6
44 INT16U 1 read/write ems__control functions__Arbitrage__tick__run_on_start
functions › Arbitrage › tick › run_on_start
1 Use → row 6
45 INT16U 1 read/write ems__control functions__Arbitrage__tick__skip_cycles_log
functions › Arbitrage › tick › skip_cycles_log
1 Use → row 6
46 INT16U 1 read/write ems__control functions__Arbitrage__tick__zero_power_on_skip
functions › Arbitrage › tick › zero_power_on_skip
1 Use → row 6
47 INT16U 1 read/write ems__control functions__Arbitrage__price_source__timeout_ms
functions › Arbitrage › price_source › timeout_ms
4000 Use → row 6
48 FLOAT32 2 read/write ems__control functions__Arbitrage__price_source__http__headers
functions › Arbitrage › price_source › http › headers
0
unset
Use → row 6
50 INT16U 1 read/write ems__control functions__Arbitrage__price_source__resolution_minutes
functions › Arbitrage › price_source › resolution_minutes
15 Use → row 6
51 INT16U 1 read/write ems__control functions__Arbitrage__strategy__prefer_next_slot
functions › Arbitrage › strategy › prefer_next_slot
1 Use → row 6
52 INT16U 1 read/write ems__control functions__Arbitrage__strategy__min_spread
functions › Arbitrage › strategy › min_spread
0 Use → row 6
53 FLOAT32 2 read/write ems__control functions__Arbitrage__strategy__buy_threshold
functions › Arbitrage › strategy › buy_threshold
0.1 Use → row 6
55 FLOAT32 2 read/write ems__control functions__Arbitrage__strategy__sell_threshold
functions › Arbitrage › strategy › sell_threshold
0.12 Use → row 6
57 INT16U 1 read/write ems__control functions__Arbitrage__strategy__buy_power_kw
functions › Arbitrage › strategy › buy_power_kw
20 Use → row 6
58 INT16U 1 read/write ems__control functions__Arbitrage__strategy__sell_power_kw
functions › Arbitrage › strategy › sell_power_kw
20 Use → row 6
59 INT16U 1 read/write ems__control functions__Arbitrage__strategy__tomorrow_plan__enabled
functions › Arbitrage › strategy › tomorrow_plan › enabled
1 Use → row 6
60 INT16U 1 read/write ems__control functions__Arbitrage__strategy__tomorrow_plan__charge_cheapest_slots
functions › Arbitrage › strategy › tomorrow_plan › charge_cheapest_slots
8 Use → row 6
61 INT16U 1 read/write ems__control functions__Arbitrage__strategy__tomorrow_plan__discharge_most_expensive_slots
functions › Arbitrage › strategy › tomorrow_plan › discharge_most_expensive_slots
8 Use → row 6
62 INT16U 1 read/write ems__control functions__Arbitrage__strategy__tomorrow_plan__charge_power_kw
functions › Arbitrage › strategy › tomorrow_plan › charge_power_kw
20 Use → row 6
63 INT16U 1 read/write ems__control functions__Arbitrage__strategy__tomorrow_plan__discharge_power_kw
functions › Arbitrage › strategy › tomorrow_plan › discharge_power_kw
20 Use → row 6
64 INT16U 1 read/write ems__control functions__Arbitrage__optional__hysteresis
functions › Arbitrage › optional › hysteresis
0 Use → row 6
65 FLOAT32 2 read/write ems__control functions__Arbitrage__optional__conflict_rule
functions › Arbitrage › optional › conflict_rule
0
unset
Use → row 6
67 INT16U 1 read/write ems__control functions__Arbitrage__optional__hysteresis_kw
functions › Arbitrage › optional › hysteresis_kw
0 Use → row 6
68 INT16U 1 read/write ems__control functions__Arbitrage__ramp_rate_kw_s
functions › Arbitrage › ramp_rate_kw_s
100 Use → row 6
69 INT16U 1 read/write ems__control functions__Peak_Shaving__enabled
functions › Peak_Shaving › enabled
1 Use → row 6
70 INT16U 1 read/write ems__control functions__Peak_Shaving__peak_threshold_kw
functions › Peak_Shaving › peak_threshold_kw
50 Use → row 6
71 INT16U 1 read/write ems__control functions__Peak_Shaving__discharge_power_limit_kw
functions › Peak_Shaving › discharge_power_limit_kw
50 Use → row 6
72 INT16U 1 read/write ems__control functions__Peak_Shaving__min_soc_pct
functions › Peak_Shaving › min_soc_pct
10 Use → row 6
73 INT16U 1 read/write ems__control functions__Peak_Shaving__recovery_soc_pct
functions › Peak_Shaving › recovery_soc_pct
67 Use → row 6
74 INT16U 1 read/write ems__control functions__Peak_Shaving__response_time_ms
functions › Peak_Shaving › response_time_ms
90 Use → row 6
75 INT16U 1 read/write ems__control functions__Peak_Shaving__optional__hysteresis_kw
functions › Peak_Shaving › optional › hysteresis_kw
2 Use → row 6
76 INT16U 1 read/write ems__control functions__Peak_Shaving__ramp_rate_kw_s
functions › Peak_Shaving › ramp_rate_kw_s
100 Use → row 6
77 INT16U 1 read/write ems__control functions__Valley_Filling__enabled
functions › Valley_Filling › enabled
0 Use → row 6
78 INT16U 1 read/write ems__control functions__Valley_Filling__valley_threshold_kw
functions › Valley_Filling › valley_threshold_kw
75 Use → row 6
79 INT16U 1 read/write ems__control functions__Valley_Filling__charge_power_limit_kw
functions › Valley_Filling › charge_power_limit_kw
120 Use → row 6
80 FLOAT32 2 read/write ems__control functions__Valley_Filling__max_soc_pct
functions › Valley_Filling › max_soc_pct
0
unset
Use → row 6
82 FLOAT32 2 read/write ems__control functions__Valley_Filling__min_soc_pct
functions › Valley_Filling › min_soc_pct
0
unset
Use → row 6
84 FLOAT32 2 read/write ems__control functions__Valley_Filling__response_time_ms
functions › Valley_Filling › response_time_ms
0
unset
Use → row 6
86 INT16U 1 read/write ems__control functions__Valley_Filling__optional__hysteresis_kw
functions › Valley_Filling › optional › hysteresis_kw
2 Use → row 6
87 INT16U 1 read/write ems__control functions__Valley_Filling__ramp_rate_kw_s
functions › Valley_Filling › ramp_rate_kw_s
100 Use → row 6
88 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__enabled
functions › Scheduled_Charge_Discharge › enabled
0 Use → row 6
89 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__soc_limits__min_soc_pct
functions › Scheduled_Charge_Discharge › soc_limits › min_soc_pct
10 Use → row 6
90 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__soc_limits__max_soc_pct
functions › Scheduled_Charge_Discharge › soc_limits › max_soc_pct
80 Use → row 6
91 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__power_limits__charge_power_limit_kw
functions › Scheduled_Charge_Discharge › power_limits › charge_power_limit_kw
30 Use → row 6
92 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__power_limits__discharge_power_limit_kw
functions › Scheduled_Charge_Discharge › power_limits › discharge_power_limit_kw
30 Use → row 6
93 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__response_time_ms
functions › Scheduled_Charge_Discharge › response_time_ms
1 Use → row 6
94 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__validation__prevent_overlaps
functions › Scheduled_Charge_Discharge › validation › prevent_overlaps
1 Use → row 6
95 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__validation__min_duration_minutes
functions › Scheduled_Charge_Discharge › validation › min_duration_minutes
5 Use → row 6
96 INT16U 1 read/write ems__control functions__Scheduled_Charge_Discharge__ramp_rate_kw_s
functions › Scheduled_Charge_Discharge › ramp_rate_kw_s
100 Use → row 6
97 INT16U 1 read/write ems__control functions__Backup__enabled
functions › Backup › enabled
0 Use → row 6
98 FLOAT32 2 read/write ems__control functions__Backup__backup_power_setpoint_kw
functions › Backup › backup_power_setpoint_kw
0
unset
Use → row 6
100 FLOAT32 2 read/write ems__control functions__Backup__min_soc_pct
functions › Backup › min_soc_pct
0
unset
Use → row 6
102 FLOAT32 2 read/write ems__control functions__Backup__recovery_soc_pct
functions › Backup › recovery_soc_pct
0
unset
Use → row 6
104 FLOAT32 2 read/write ems__control functions__Backup__response_time_ms
functions › Backup › response_time_ms
0
unset
Use → row 6
106 INT16U 1 read/write ems__control functions__Backup__black_start_enable
functions › Backup › black_start_enable
1 Use → row 6
107 INT16U 1 read/write ems__control functions__Backup__grid_mode_switch__enabled
functions › Backup › grid_mode_switch › enabled
0 Use → row 6
108 INT16U 1 read/write ems__control functions__Backup__grid_mode_switch__grid_loss_voltage_v
functions › Backup › grid_mode_switch › grid_loss_voltage_v
100 Use → row 6
109 INT16U 1 read/write ems__control functions__Backup__grid_mode_switch__grid_loss_frequency_hz_low
functions › Backup › grid_mode_switch › grid_loss_frequency_hz_low
47 Use → row 6
110 INT16U 1 read/write ems__control functions__Backup__grid_mode_switch__grid_loss_frequency_hz_high
functions › Backup › grid_mode_switch › grid_loss_frequency_hz_high
53 Use → row 6
111 INT16U 1 read/write ems__control functions__Backup__grid_mode_switch__switch_delay_s
functions › Backup › grid_mode_switch › switch_delay_s
3 Use → row 6
112 INT16U 1 read/write ems__control functions__Backup__power_dispatch__enabled
functions › Backup › power_dispatch › enabled
0 Use → row 6
Page 1 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.