EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-19T01:41:27+00:00 (from cache)
Size: 2,146,664 bytes · sha256 3099c5e150cf

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
26339 BOOL16 1 read only door_sensor9__doors door_sensor_2_status — Use → row 4
26340 BOOL16 1 read only door_sensor9__doors door_sensor_3_status — Use → row 4
26341 BOOL16 1 read only door_sensor9__doors door_sensor_4_status — Use → row 4
26342 BOOL16 1 read only door_sensor9__doors door_sensor_5_status — Use → row 4
26343 BOOL16 1 read only door_sensor9__doors door_sensor_6_status — Use → row 4
26344 BOOL16 1 read only door_sensor9__doors door_sensor_7_status — Use → row 4
26345 BOOL16 1 read only door_sensor9__doors door_sensor_8_status — Use → row 4
26346 BOOL16 1 read only door_sensor9__doors door_sensor_9_status — Use → row 4
26347 BOOL16 1 read only door_sensor9__doors door_sensor_10_status — Use → row 4
26348 BOOL16 1 read only door_sensor9__doors door_sensor_11_status — Use → row 4
26349 BOOL16 1 read only door_sensor9__doors door_sensor_12_status — Use → row 4
26350 FLOAT32 2 read only ffrEnergyMeter1__currents current_l1_a 0 Use → row 4
26352 FLOAT32 2 read only ffrEnergyMeter1__currents current_l2_a 0 Use → row 4
26354 FLOAT32 2 read only ffrEnergyMeter1__currents current_l3_a 0 Use → row 4
26356 FLOAT32 2 read only ffrEnergyMeter1__currents current_avg_a 0 Use → row 4
26358 FLOAT32 2 read only ffrEnergyMeter1__currents current_neutral_a 0 Use → row 4
26360 FLOAT32 2 read only ffrEnergyMeter1__voltages voltage_l1_n_v 0 Use → row 4
26362 FLOAT32 2 read only ffrEnergyMeter1__voltages voltage_l2_n_v 0 Use → row 4
26364 FLOAT32 2 read only ffrEnergyMeter1__voltages voltage_l3_n_v 0 Use → row 4
26366 FLOAT32 2 read only ffrEnergyMeter1__voltages voltage_l1_l2_v 0 Use → row 4
26368 FLOAT32 2 read only ffrEnergyMeter1__voltages voltage_l2_l3_v 0 Use → row 4
26370 FLOAT32 2 read only ffrEnergyMeter1__voltages voltage_l3_l1_v 0 Use → row 4
26372 FLOAT32 2 read only ffrEnergyMeter1__power active_power_total_kw 150 Use → row 4
26374 FLOAT32 2 read only ffrEnergyMeter1__power reactive_power_total_kvar 0 Use → row 4
26376 FLOAT32 2 read only ffrEnergyMeter1__power apparent_power_total_kva 0 Use → row 4
26378 FLOAT32 2 read only ffrEnergyMeter1__power_factor pf_total 1 Use → row 4
26380 FLOAT32 2 read only ffrEnergyMeter1__frequency frequency_hz 50 Use → row 4
26382 UINT32 2 read only ffrEnergyMeter1__energies active_energy_import_kwh 0 Use → row 4
26384 UINT32 2 read only ffrEnergyMeter1__energies active_energy_export_kwh 0 Use → row 4
26386 UINT32 2 read only ffrEnergyMeter1__energies reactive_energy_import_kvarh 0 Use → row 4
26388 UINT32 2 read only ffrEnergyMeter1__energies apparent_energy_total_kvah 0 Use → row 4
26390 FLOAT32 2 read only fss1__sensors gas_detector_ppm — Use → row 4
26392 FLOAT32 2 read only fss1__sensors smoke_obscuration_percent — Use → row 4
26394 FLOAT32 2 read only fss1__sensors heat_detector_temp_c — Use → row 4
26396 FLOAT32 2 read only fss1__sensors ambient_temp_c — Use → row 4
26398 FLOAT32 2 read only fss1__sensors aerosol_canister_pressure_kpa — Use → row 4
26400 FLOAT32 2 read only fss1__sensors aerosol_canister_remaining_percent — Use → row 4
26402 FLOAT32 2 read/write fss1__control__setpoints gas_pre_alarm_ppm — Use → row 4
26404 FLOAT32 2 read/write fss1__control__setpoints gas_alarm_ppm — Use → row 4
26406 FLOAT32 2 read/write fss1__control__setpoints smoke_pre_alarm_obscuration_percent — Use → row 4
26408 FLOAT32 2 read/write fss1__control__setpoints smoke_alarm_obscuration_percent — Use → row 4
26410 FLOAT32 2 read/write fss1__control__setpoints heat_pre_alarm_temp_c — Use → row 4
26412 FLOAT32 2 read/write fss1__control__setpoints heat_alarm_temp_c — Use → row 4
26414 INT16U 1 read/write fss1__control__setpoints release_delay_s — Use → row 4
26415 INT16U 1 read/write fss1__control__setpoints discharge_duration_s — Use → row 4
26416 ENUM16 1 read/write fss1__control__setpoints cross_zone_logic
6 enum values
— Use → row 4
26417 BOOL16 1 read/write fss1__control__setpoints manual_release_enable — Use → row 4
26418 BOOL16 1 read/write fss1__control__setpoints inhibit_release — Use → row 4
26419 BOOL16 1 read/write fss1__control__setpoints abort_enabled — Use → row 4
26420 INT16U 1 read/write fss1__control__setpoints hush_duration_s — Use → row 4
26421 BOOL16 1 read/write fss1__control__setpoints auto_reset_enabled — Use → row 4
26422 ENUM16 1 read only fss1__status system_state
8 enum values
— Use → row 4
26423 BOOL16 1 read only fss1__status gas_alarm_active — Use → row 4
26424 BOOL16 1 read only fss1__status smoke_alarm_active — Use → row 4
26425 BOOL16 1 read only fss1__status heat_alarm_active — Use → row 4
26426 BOOL16 1 read only fss1__status cross_zone_met — Use → row 4
26427 BOOL16 1 read only fss1__status actuator_ready — Use → row 4
26428 BOOL16 1 read only fss1__status actuator_fired — Use → row 4
26429 BOOL16 1 read only fss1__status abort_active — Use → row 4
26430 BOOL16 1 read only fss1__status manual_release_active — Use → row 4
26431 BITMAP32 2 read only fss1__status fault_bitmap — Use → row 4
26433 BITMAP32 2 read only fss1__alarms_counters alarm_bitmap — Use → row 4
26435 INT16U 1 read only fss1__alarms_counters fault_counts_total — Use → row 4
26436 INT16U 1 read only fss1__alarms_counters gas_alarm_count — Use → row 4
26437 INT16U 1 read only fss1__alarms_counters smoke_alarm_count — Use → row 4
26438 INT16U 1 read only fss1__alarms_counters heat_alarm_count — Use → row 4
26439 INT16U 1 read only fss1__alarms_counters release_count — Use → row 4
26440 ENUM16 1 read only fss1__alarms_counters last_event_code — Use → row 4
26441 INT32U 2 read only fss1__alarms_counters last_event_epoch_s — Use → row 4
26443 INT16U 1 read only fss1__alarms_counters maintenance_due_days — Use → row 4
26444 BOOL16 1 read only fss1__io input_abort_button — Use → row 4
26445 BOOL16 1 read only fss1__io input_manual_release — Use → row 4
26446 BOOL16 1 read only fss1__io input_door_interlock — Use → row 4
26447 BOOL16 1 read only fss1__io input_service_key — Use → row 4
26448 ENUM16 1 read/write fss1__control__io sounder_command
4 enum values
— Use → row 4
26449 BOOL16 1 read/write fss1__control__io strobe_enable — Use → row 4
26450 ENUM16 1 read/write fss1__control__commands command_system_reset
2 enum values
— Use → row 4
26451 ENUM16 1 read/write fss1__control__commands command_acknowledge
2 enum values
— Use → row 4
26452 ENUM16 1 read/write fss1__control__commands command_silence_sounder
2 enum values
— Use → row 4
26453 ENUM16 1 read/write fss1__control__commands command_manual_release
2 enum values
— Use → row 4
26454 ENUM16 1 read/write fss1__control__commands command_inhibit_toggle
3 enum values
— Use → row 4
26455 ENUM16 1 read/write fss1__control__commands command_test_mode
2 enum values
— Use → row 4
26456 INT16U 1 read only fss1__communication protocol_version — Use → row 4
26457 INT16U 1 read only fss1__communication firmware_version_major — Use → row 4
26458 INT16U 1 read only fss1__communication firmware_version_minor — Use → row 4
26459 INT16U 1 read only fss1__communication device_address — Use → row 4
26460 BOOL16 1 read only flood_sensor1__flood flood_sensor_1_status — Use → row 4
26461 BOOL16 1 read only flood_sensor1__flood flood_sensor_2_status — Use → row 4
26462 BITMAP32 2 read only frequency_meter1__alarms digital_input_status_validity_base 0 Use → row 4
26464 FLOAT32 2 read only frequency_meter1__energies active_energy_delivered_minus_received_kwh 0 Use → row 4
26466 FLOAT32 2 read only frequency_meter1__currents current_a_a 0 Use → row 4
26468 FLOAT32 2 read only frequency_meter1__voltages voltage_ab_v 0 Use → row 4
26470 BITMAP32 2 read only frequency_meter1__alarms alarms 0 Use → row 4
26472 FLOAT32 2 read only frequency_meter1__power active_power_total_kw 150 Use → row 4
26474 FLOAT32 2 read only frequency_meter1__power reactive_power_total_kvar 0 Use → row 4
26476 FLOAT32 2 read only frequency_meter1__frequency frequency_hz 50 Use → row 4
26478 FLOAT32 2 read only frequency_meter1__power_factor pf_total 1 Use → row 4
26480 FLOAT32 2 read only frequency_meter1__energies active_energy_delivered_plus_received_kwh 0 Use → row 4
26482 FLOAT32 2 read only frequency_meter1__energies active_energy_received_kwh 0 Use → row 4
26484 FLOAT32 2 read only frequency_meter1__energies active_energy_delivered_kwh 0 Use → row 4