EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-19T02:00:42+00:00 (from cache)
Size: 2,146,665 bytes · sha256 4e25b86867b3

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
26486 FLOAT32 2 read only grid_meter1__currents current_l1_a 0 Use → row 5
26488 FLOAT32 2 read only grid_meter1__currents current_l2_a 0 Use → row 5
26490 FLOAT32 2 read only grid_meter1__currents current_l3_a 0 Use → row 5
26492 FLOAT32 2 read only grid_meter1__currents current_avg_a 0 Use → row 5
26494 FLOAT32 2 read only grid_meter1__currents current_neutral_a 0 Use → row 5
26496 FLOAT32 2 read only grid_meter1__voltages voltage_l1_n_v 0 Use → row 5
26498 FLOAT32 2 read only grid_meter1__voltages voltage_l2_n_v 0 Use → row 5
26500 FLOAT32 2 read only grid_meter1__voltages voltage_l3_n_v 0 Use → row 5
26502 FLOAT32 2 read only grid_meter1__voltages voltage_l1_l2_v 0 Use → row 5
26504 FLOAT32 2 read only grid_meter1__voltages voltage_l2_l3_v 0 Use → row 5
26506 FLOAT32 2 read only grid_meter1__voltages voltage_l3_l1_v 0 Use → row 5
26508 FLOAT32 2 read only grid_meter1__power active_power_total_kw 150 Use → row 5
26510 FLOAT32 2 read only grid_meter1__power reactive_power_total_kvar 0 Use → row 5
26512 FLOAT32 2 read only grid_meter1__power apparent_power_total_kva 0 Use → row 5
26514 FLOAT32 2 read only grid_meter1__power_factor pf_total 1 Use → row 5
26516 FLOAT32 2 read only grid_meter1__frequency frequency_hz 50 Use → row 5
26518 UINT32 2 read only grid_meter1__energies active_energy_import_kwh 0 Use → row 5
26520 UINT32 2 read only grid_meter1__energies active_energy_export_kwh 0 Use → row 5
26522 UINT32 2 read only grid_meter1__energies reactive_energy_import_kvarh 0 Use → row 5
26524 UINT32 2 read only grid_meter1__energies apparent_energy_total_kvah 0 Use → row 5
26526 FLOAT32 2 read only grid_meter10__currents current_l1_a 0 Use → row 5
26528 FLOAT32 2 read only grid_meter10__currents current_l2_a 0 Use → row 5
26530 FLOAT32 2 read only grid_meter10__currents current_l3_a 0 Use → row 5
26532 FLOAT32 2 read only grid_meter10__currents current_avg_a 0 Use → row 5
26534 FLOAT32 2 read only grid_meter10__currents current_neutral_a 0 Use → row 5
26536 FLOAT32 2 read only grid_meter10__voltages voltage_l1_n_v 0 Use → row 5
26538 FLOAT32 2 read only grid_meter10__voltages voltage_l2_n_v 0 Use → row 5
26540 FLOAT32 2 read only grid_meter10__voltages voltage_l3_n_v 0 Use → row 5
26542 FLOAT32 2 read only grid_meter10__voltages voltage_l1_l2_v 0 Use → row 5
26544 FLOAT32 2 read only grid_meter10__voltages voltage_l2_l3_v 0 Use → row 5
26546 FLOAT32 2 read only grid_meter10__voltages voltage_l3_l1_v 0 Use → row 5
26548 FLOAT32 2 read only grid_meter10__power active_power_total_kw 150 Use → row 5
26550 FLOAT32 2 read only grid_meter10__power reactive_power_total_kvar 0 Use → row 5
26552 FLOAT32 2 read only grid_meter10__power apparent_power_total_kva 0 Use → row 5
26554 FLOAT32 2 read only grid_meter10__power_factor pf_total 1 Use → row 5
26556 FLOAT32 2 read only grid_meter10__frequency frequency_hz 50 Use → row 5
26558 UINT32 2 read only grid_meter10__energies active_energy_import_kwh 0 Use → row 5
26560 UINT32 2 read only grid_meter10__energies active_energy_export_kwh 0 Use → row 5
26562 UINT32 2 read only grid_meter10__energies reactive_energy_import_kvarh 0 Use → row 5
26564 UINT32 2 read only grid_meter10__energies apparent_energy_total_kvah 0 Use → row 5
26566 FLOAT32 2 read only grid_meter11__currents current_l1_a 0 Use → row 5
26568 FLOAT32 2 read only grid_meter11__currents current_l2_a 0 Use → row 5
26570 FLOAT32 2 read only grid_meter11__currents current_l3_a 0 Use → row 5
26572 FLOAT32 2 read only grid_meter11__currents current_avg_a 0 Use → row 5
26574 FLOAT32 2 read only grid_meter11__currents current_neutral_a 0 Use → row 5
26576 FLOAT32 2 read only grid_meter11__voltages voltage_l1_n_v 0 Use → row 5
26578 FLOAT32 2 read only grid_meter11__voltages voltage_l2_n_v 0 Use → row 5
26580 FLOAT32 2 read only grid_meter11__voltages voltage_l3_n_v 0 Use → row 5
26582 FLOAT32 2 read only grid_meter11__voltages voltage_l1_l2_v 0 Use → row 5
26584 FLOAT32 2 read only grid_meter11__voltages voltage_l2_l3_v 0 Use → row 5
26586 FLOAT32 2 read only grid_meter11__voltages voltage_l3_l1_v 0 Use → row 5
26588 FLOAT32 2 read only grid_meter11__power active_power_total_kw 150 Use → row 5
26590 FLOAT32 2 read only grid_meter11__power reactive_power_total_kvar 0 Use → row 5
26592 FLOAT32 2 read only grid_meter11__power apparent_power_total_kva 0 Use → row 5
26594 FLOAT32 2 read only grid_meter11__power_factor pf_total 1 Use → row 5
26596 FLOAT32 2 read only grid_meter11__frequency frequency_hz 50 Use → row 5
26598 UINT32 2 read only grid_meter11__energies active_energy_import_kwh 0 Use → row 5
26600 UINT32 2 read only grid_meter11__energies active_energy_export_kwh 0 Use → row 5
26602 UINT32 2 read only grid_meter11__energies reactive_energy_import_kvarh 0 Use → row 5
26604 UINT32 2 read only grid_meter11__energies apparent_energy_total_kvah 0 Use → row 5
26606 FLOAT32 2 read only grid_meter12__currents current_l1_a 0 Use → row 5
26608 FLOAT32 2 read only grid_meter12__currents current_l2_a 0 Use → row 5
26610 FLOAT32 2 read only grid_meter12__currents current_l3_a 0 Use → row 5
26612 FLOAT32 2 read only grid_meter12__currents current_avg_a 0 Use → row 5
26614 FLOAT32 2 read only grid_meter12__currents current_neutral_a 0 Use → row 5
26616 FLOAT32 2 read only grid_meter12__voltages voltage_l1_n_v 0 Use → row 5
26618 FLOAT32 2 read only grid_meter12__voltages voltage_l2_n_v 0 Use → row 5
26620 FLOAT32 2 read only grid_meter12__voltages voltage_l3_n_v 0 Use → row 5
26622 FLOAT32 2 read only grid_meter12__voltages voltage_l1_l2_v 0 Use → row 5
26624 FLOAT32 2 read only grid_meter12__voltages voltage_l2_l3_v 0 Use → row 5
26626 FLOAT32 2 read only grid_meter12__voltages voltage_l3_l1_v 0 Use → row 5
26628 FLOAT32 2 read only grid_meter12__power active_power_total_kw 150 Use → row 5
26630 FLOAT32 2 read only grid_meter12__power reactive_power_total_kvar 0 Use → row 5
26632 FLOAT32 2 read only grid_meter12__power apparent_power_total_kva 0 Use → row 5
26634 FLOAT32 2 read only grid_meter12__power_factor pf_total 1 Use → row 5
26636 FLOAT32 2 read only grid_meter12__frequency frequency_hz 50 Use → row 5
26638 UINT32 2 read only grid_meter12__energies active_energy_import_kwh 0 Use → row 5
26640 UINT32 2 read only grid_meter12__energies active_energy_export_kwh 0 Use → row 5
26642 UINT32 2 read only grid_meter12__energies reactive_energy_import_kvarh 0 Use → row 5
26644 UINT32 2 read only grid_meter12__energies apparent_energy_total_kvah 0 Use → row 5
26646 FLOAT32 2 read only grid_meter2__currents current_l1_a 0 Use → row 5
26648 FLOAT32 2 read only grid_meter2__currents current_l2_a 0 Use → row 5
26650 FLOAT32 2 read only grid_meter2__currents current_l3_a 0 Use → row 5
26652 FLOAT32 2 read only grid_meter2__currents current_avg_a 0 Use → row 5
26654 FLOAT32 2 read only grid_meter2__currents current_neutral_a 0 Use → row 5
26656 FLOAT32 2 read only grid_meter2__voltages voltage_l1_n_v 0 Use → row 5
26658 FLOAT32 2 read only grid_meter2__voltages voltage_l2_n_v 0 Use → row 5
26660 FLOAT32 2 read only grid_meter2__voltages voltage_l3_n_v 0 Use → row 5
26662 FLOAT32 2 read only grid_meter2__voltages voltage_l1_l2_v 0 Use → row 5
26664 FLOAT32 2 read only grid_meter2__voltages voltage_l2_l3_v 0 Use → row 5
26666 FLOAT32 2 read only grid_meter2__voltages voltage_l3_l1_v 0 Use → row 5
26668 FLOAT32 2 read only grid_meter2__power active_power_total_kw 150 Use → row 5
26670 FLOAT32 2 read only grid_meter2__power reactive_power_total_kvar 0 Use → row 5
26672 FLOAT32 2 read only grid_meter2__power apparent_power_total_kva 0 Use → row 5
26674 FLOAT32 2 read only grid_meter2__power_factor pf_total 1 Use → row 5
26676 FLOAT32 2 read only grid_meter2__frequency frequency_hz 50 Use → row 5
26678 UINT32 2 read only grid_meter2__energies active_energy_import_kwh 0 Use → row 5
26680 UINT32 2 read only grid_meter2__energies active_energy_export_kwh 0 Use → row 5
26682 UINT32 2 read only grid_meter2__energies reactive_energy_import_kvarh 0 Use → row 5
26684 UINT32 2 read only grid_meter2__energies apparent_energy_total_kvah 0 Use → row 5
← Previous Page 17 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.