EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-19T02:17:27+00:00
Size: 2,146,664 bytes · sha256 3beb700a1c99

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
26886 FLOAT32 2 read only grid_meter8__currents current_l1_a 0 Use → row 10
26888 FLOAT32 2 read only grid_meter8__currents current_l2_a 0 Use → row 10
26890 FLOAT32 2 read only grid_meter8__currents current_l3_a 0 Use → row 10
26892 FLOAT32 2 read only grid_meter8__currents current_avg_a 0 Use → row 10
26894 FLOAT32 2 read only grid_meter8__currents current_neutral_a 0 Use → row 10
26896 FLOAT32 2 read only grid_meter8__voltages voltage_l1_n_v 0 Use → row 10
26898 FLOAT32 2 read only grid_meter8__voltages voltage_l2_n_v 0 Use → row 10
26900 FLOAT32 2 read only grid_meter8__voltages voltage_l3_n_v 0 Use → row 10
26902 FLOAT32 2 read only grid_meter8__voltages voltage_l1_l2_v 0 Use → row 10
26904 FLOAT32 2 read only grid_meter8__voltages voltage_l2_l3_v 0 Use → row 10
26906 FLOAT32 2 read only grid_meter8__voltages voltage_l3_l1_v 0 Use → row 10
26908 FLOAT32 2 read only grid_meter8__power active_power_total_kw 150 Use → row 10
26910 FLOAT32 2 read only grid_meter8__power reactive_power_total_kvar 0 Use → row 10
26912 FLOAT32 2 read only grid_meter8__power apparent_power_total_kva 0 Use → row 10
26914 FLOAT32 2 read only grid_meter8__power_factor pf_total 1 Use → row 10
26916 FLOAT32 2 read only grid_meter8__frequency frequency_hz 50 Use → row 10
26918 UINT32 2 read only grid_meter8__energies active_energy_import_kwh 0 Use → row 10
26920 UINT32 2 read only grid_meter8__energies active_energy_export_kwh 0 Use → row 10
26922 UINT32 2 read only grid_meter8__energies reactive_energy_import_kvarh 0 Use → row 10
26924 UINT32 2 read only grid_meter8__energies apparent_energy_total_kvah 0 Use → row 10
26926 FLOAT32 2 read only grid_meter9__currents current_l1_a 0 Use → row 10
26928 FLOAT32 2 read only grid_meter9__currents current_l2_a 0 Use → row 10
26930 FLOAT32 2 read only grid_meter9__currents current_l3_a 0 Use → row 10
26932 FLOAT32 2 read only grid_meter9__currents current_avg_a 0 Use → row 10
26934 FLOAT32 2 read only grid_meter9__currents current_neutral_a 0 Use → row 10
26936 FLOAT32 2 read only grid_meter9__voltages voltage_l1_n_v 0 Use → row 10
26938 FLOAT32 2 read only grid_meter9__voltages voltage_l2_n_v 0 Use → row 10
26940 FLOAT32 2 read only grid_meter9__voltages voltage_l3_n_v 0 Use → row 10
26942 FLOAT32 2 read only grid_meter9__voltages voltage_l1_l2_v 0 Use → row 10
26944 FLOAT32 2 read only grid_meter9__voltages voltage_l2_l3_v 0 Use → row 10
26946 FLOAT32 2 read only grid_meter9__voltages voltage_l3_l1_v 0 Use → row 10
26948 FLOAT32 2 read only grid_meter9__power active_power_total_kw 150 Use → row 10
26950 FLOAT32 2 read only grid_meter9__power reactive_power_total_kvar 0 Use → row 10
26952 FLOAT32 2 read only grid_meter9__power apparent_power_total_kva 0 Use → row 10
26954 FLOAT32 2 read only grid_meter9__power_factor pf_total 1 Use → row 10
26956 FLOAT32 2 read only grid_meter9__frequency frequency_hz 50 Use → row 10
26958 UINT32 2 read only grid_meter9__energies active_energy_import_kwh 0 Use → row 10
26960 UINT32 2 read only grid_meter9__energies active_energy_export_kwh 0 Use → row 10
26962 UINT32 2 read only grid_meter9__energies reactive_energy_import_kvarh 0 Use → row 10
26964 UINT32 2 read only grid_meter9__energies apparent_energy_total_kvah 0 Use → row 10
26966 BITMAP32 2 read only heat_sensor1__alarms alarm_bitmap — Use → row 10
26968 FLOAT32 2 read only cooling1__temperatures supply_temp_c — Use → row 10
26970 FLOAT32 2 read only cooling1__temperatures return_temp_c — Use → row 10
26972 FLOAT32 2 read only cooling1__temperatures ambient_temp_c — Use → row 10
26974 FLOAT32 2 read only cooling1__temperatures coolant_inlet_temp_c — Use → row 10
26976 FLOAT32 2 read only cooling1__temperatures coolant_outlet_temp_c — Use → row 10
26978 FLOAT32 2 read only cooling1__temperatures compressor_temp_c — Use → row 10
26980 FLOAT32 2 read only cooling1__temperatures condenser_temp_c — Use → row 10
26982 FLOAT32 2 read only cooling1__temperatures evaporator_temp_c — Use → row 10
26984 FLOAT32 2 read/write cooling1__control__setpoints setpoint_temp_c — Use → row 10
26986 FLOAT32 2 read/write cooling1__control__setpoints min_temp_limit_c — Use → row 10
26988 FLOAT32 2 read/write cooling1__control__setpoints max_temp_limit_c — Use → row 10
26990 UINT16 1 read/write cooling1__control__mode operating_mode — Use → row 10
26991 FLOAT32 2 read/write cooling1__control__mode setpoint_temp_apply — Use → row 10
26993 FLOAT32 2 read only cooling1__flow_pressure water_flow_rate_lpm — Use → row 10
26995 FLOAT32 2 read only cooling1__flow_pressure system_pressure_bar — Use → row 10
26997 FLOAT32 2 read only cooling1__flow_pressure refrigerant_pressure_bar — Use → row 10
26999 BOOL 1 read only cooling1__status running — Use → row 10
27000 BOOL 1 read only cooling1__status compressor_on — Use → row 10
27001 BOOL 1 read only cooling1__status fan_on — Use → row 10
27002 BOOL 1 read only cooling1__status pump_on — Use → row 10
27003 BOOL 1 read only cooling1__status maintenance_required — Use → row 10
27004 BOOL 1 read only cooling1__status leak_detected — Use → row 10
27005 UINT16 1 read only cooling1__alarms alarm_code — Use → row 10
27006 BITMAP32 2 read only cooling1__alarms alarm_bitmap — Use → row 10
27008 BOOL 1 read only cooling1__alarms high_pressure_alarm — Use → row 10
27009 BOOL 1 read only cooling1__alarms low_flow_alarm — Use → row 10
27010 BOOL 1 read only cooling1__alarms over_temperature_alarm — Use → row 10
27011 FLOAT32 2 read only cooling1__power cooling_power_kw — Use → row 10
27013 FLOAT32 2 read only cooling1__power energy_consumed_kwh — Use → row 10
27015 FLOAT32 2 read only cooling1__power compressor_speed_rpm — Use → row 10
27017 FLOAT32 2 read only cooling1__power fan_speed_rpm — Use → row 10
27019 FLOAT32 2 read only cooling1__runtime runtime_hours — Use → row 10
27021 FLOAT32 2 read only cooling1__runtime compressor_runtime_hours — Use → row 10
27023 UINT16 1 read only cooling1__communication comm_status — Use → row 10
27024 UINT16 1 read only cooling1__communication heartbeat — Use → row 10
27025 INT16 1 read/write pcs1__control__remote_control start_stop_command 0 Use → row 10
27026 BOOL 1 read only pcs1__bc 1_cell_voltage_too_high 0 Use → row 10
27027 BOOL 1 read only pcs1__bc_switch_quantities l1_cell_voltage_high 0 Use → row 10
27028 BOOL 1 read only pcs1__bc l1_cell_voltage_too_low 0 Use → row 10
27029 BOOL 1 read only pcs1__bc_switch_quantities l1_cell_voltage_low 0 Use → row 10
27030 BOOL 1 read only pcs1__bc l1_cell_voltage_difference_too_large 0 Use → row 10
27031 BOOL 1 read only pcs1__bc_switch_quantities l1_cell_voltage_difference_excessive 0 Use → row 10
27032 BOOL 1 read only pcs1__bc l1_total_voltage_too_high 0 Use → row 10
27033 BOOL 1 read only pcs1__bc_switch_quantities l1_total_voltage_high 0 Use → row 10
27034 BOOL 1 read only pcs1__bc l1_total_voltage_too_low 0 Use → row 10
27035 BOOL 1 read only pcs1__bc_switch_quantities l1_total_voltage_low 0 Use → row 10
27036 BOOL 1 read only pcs1__bc l1_battery_discharge_temperature_too_high 0 Use → row 10
27037 BOOL 1 read only pcs1__bc_switch_quantities l1_battery_discharging_temperature_high 0 Use → row 10
27038 BOOL 1 read only pcs1__bc l1_battery_discharge_temperature_too_low 0 Use → row 10
27039 BOOL 1 read only pcs1__bc_switch_quantities l1_battery_discharging_temperature_low 0 Use → row 10
27040 BOOL 1 read only pcs1__bc l1_battery_charge_temperature_too_high 0 Use → row 10
27041 BOOL 1 read only pcs1__bc_switch_quantities l1_battery_charging_temperature_high 0 Use → row 10
27042 BOOL 1 read only pcs1__bc l1_battery_charge_temperature_too_low 0 Use → row 10
27043 BOOL 1 read only pcs1__bc_switch_quantities l1_battery_charging_temperature_low 0 Use → row 10
27044 BOOL 1 read only pcs1__bc l1_cell_temperature_difference_too_large 0 Use → row 10
27045 BOOL 1 read only pcs1__bc_switch_quantities l1_cell_temperature_difference_excessive 0 Use → row 10
27046 BOOL 1 read only pcs1__bc l1_charging_current_too_high 0 Use → row 10
27047 BOOL 1 read only pcs1__bc_switch_quantities l1_charging_current_high 0 Use → row 10
27048 BOOL 1 read only pcs1__bc l1_discharging_current_too_high 0 Use → row 10
← Previous Page 19 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.