EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-18T23:32:56+00:00
Size: 2,146,664 bytes · sha256 40fc72a0cec6

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
267 FLOAT32 2 read/write ems__control protections__protection_rules__current__protection_current_overcurrent_recovery_a
protections › protection_rules › current › protection_current_overcurrent_recovery_a
230 Use → row 5
269 INT16U 1 read/write ems__control protections__protection_rules__current__protection_current_phase_imbalance_enabled
protections › protection_rules › current › protection_current_phase_imbalance_enabled
1 Use → row 5
270 FLOAT32 2 read/write ems__control protections__protection_rules__current__protection_current_phase_imbalance_percent
protections › protection_rules › current › protection_current_phase_imbalance_percent
10 Use → row 5
272 INT16U 1 read/write ems__control protections__protection_rules__current__protection_current_phase_imbalance_delay_ms
protections › protection_rules › current › protection_current_phase_imbalance_delay_ms
2000 Use → row 5
274 FLOAT32 2 read/write ems__control protections__protection_rules__current__protection_current_phase_imbalance_recovery_percent
protections › protection_rules › current › protection_current_phase_imbalance_recovery_percent
5 Use → row 5
278 INT16U 1 read/write ems__control protections__protection_rules__current__protection_current_poll_ms
protections › protection_rules › current › protection_current_poll_ms
200 Use → row 5
280 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_grid_import_limit_enabled
protections › protection_rules › power › protection_power_grid_import_limit_enabled
1 Use → row 5
281 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_grid_import_limit_kw
protections › protection_rules › power › protection_power_grid_import_limit_kw
250 Use → row 5
283 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_grid_import_limit_delay_ms
protections › protection_rules › power › protection_power_grid_import_limit_delay_ms
2000 Use → row 5
285 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_grid_import_limit_recovery_kw
protections › protection_rules › power › protection_power_grid_import_limit_recovery_kw
230 Use → row 5
287 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_grid_export_limit_enabled
protections › protection_rules › power › protection_power_grid_export_limit_enabled
1 Use → row 5
288 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_grid_export_limit_kw
protections › protection_rules › power › protection_power_grid_export_limit_kw
200 Use → row 5
290 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_grid_export_limit_delay_ms
protections › protection_rules › power › protection_power_grid_export_limit_delay_ms
2000 Use → row 5
292 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_grid_export_limit_recovery_kw
protections › protection_rules › power › protection_power_grid_export_limit_recovery_kw
180 Use → row 5
294 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_reverse_power_enabled
protections › protection_rules › power › protection_power_reverse_power_enabled
1 Use → row 5
295 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_reverse_power_threshold_kw
protections › protection_rules › power › protection_power_reverse_power_threshold_kw
300 Use → row 5
297 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_reverse_power_delay_ms
protections › protection_rules › power › protection_power_reverse_power_delay_ms
1000 Use → row 5
299 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_pcs_overload_enabled
protections › protection_rules › power › protection_power_pcs_overload_enabled
1 Use → row 5
300 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_pcs_overload_threshold_kw
protections › protection_rules › power › protection_power_pcs_overload_threshold_kw
250 Use → row 5
302 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_pcs_overload_delay_ms
protections › protection_rules › power › protection_power_pcs_overload_delay_ms
3000 Use → row 5
304 FLOAT32 2 read/write ems__control protections__protection_rules__power__protection_power_pcs_overload_recovery_kw
protections › protection_rules › power › protection_power_pcs_overload_recovery_kw
230 Use → row 5
308 INT16U 1 read/write ems__control protections__protection_rules__power__protection_power_poll_ms
protections › protection_rules › power › protection_power_poll_ms
200 Use → row 5
310 INT16U 1 read/write ems__control protections__protection_rules__bess__protection_bess_soc_high_enabled
protections › protection_rules › bess › protection_bess_soc_high_enabled
0 Use → row 5
311 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_soc_high_percent
protections › protection_rules › bess › protection_bess_soc_high_percent
0
unset
Use → row 5
313 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_soc_high_delay_ms
protections › protection_rules › bess › protection_bess_soc_high_delay_ms
0
unset
Use → row 5
315 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_soc_high_recovery_percent
protections › protection_rules › bess › protection_bess_soc_high_recovery_percent
0
unset
Use → row 5
317 INT16U 1 read/write ems__control protections__protection_rules__bess__protection_bess_soc_low_enabled
protections › protection_rules › bess › protection_bess_soc_low_enabled
0 Use → row 5
318 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_soc_low_percent
protections › protection_rules › bess › protection_bess_soc_low_percent
0
unset
Use → row 5
320 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_soc_low_delay_ms
protections › protection_rules › bess › protection_bess_soc_low_delay_ms
0
unset
Use → row 5
322 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_soc_low_recovery_percent
protections › protection_rules › bess › protection_bess_soc_low_recovery_percent
0
unset
Use → row 5
324 INT16U 1 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_high_enabled
protections › protection_rules › bess › protection_bess_voltage_high_enabled
0 Use → row 5
325 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_high_v
protections › protection_rules › bess › protection_bess_voltage_high_v
0
unset
Use → row 5
327 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_high_delay_ms
protections › protection_rules › bess › protection_bess_voltage_high_delay_ms
0
unset
Use → row 5
329 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_high_recovery_v
protections › protection_rules › bess › protection_bess_voltage_high_recovery_v
0
unset
Use → row 5
331 INT16U 1 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_low_enabled
protections › protection_rules › bess › protection_bess_voltage_low_enabled
0 Use → row 5
332 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_low_v
protections › protection_rules › bess › protection_bess_voltage_low_v
0
unset
Use → row 5
334 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_low_delay_ms
protections › protection_rules › bess › protection_bess_voltage_low_delay_ms
0
unset
Use → row 5
336 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_voltage_low_recovery_v
protections › protection_rules › bess › protection_bess_voltage_low_recovery_v
0
unset
Use → row 5
338 INT16U 1 read/write ems__control protections__protection_rules__bess__protection_bess_overtemperature_enabled
protections › protection_rules › bess › protection_bess_overtemperature_enabled
0 Use → row 5
339 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_overtemperature_c
protections › protection_rules › bess › protection_bess_overtemperature_c
0
unset
Use → row 5
341 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_overtemperature_delay_ms
protections › protection_rules › bess › protection_bess_overtemperature_delay_ms
0
unset
Use → row 5
343 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_overtemperature_recovery_c
protections › protection_rules › bess › protection_bess_overtemperature_recovery_c
0
unset
Use → row 5
345 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_max_charge_current_a
protections › protection_rules › bess › protection_bess_max_charge_current_a
0
unset
Use → row 5
347 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_max_discharge_current_a
protections › protection_rules › bess › protection_bess_max_discharge_current_a
0
unset
Use → row 5
349 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_max_charge_power_kw
protections › protection_rules › bess › protection_bess_max_charge_power_kw
0
unset
Use → row 5
351 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_max_discharge_power_kw
protections › protection_rules › bess › protection_bess_max_discharge_power_kw
0
unset
Use → row 5
353 FLOAT32 2 read/write ems__control protections__protection_rules__bess__protection_bess_measurement_source
protections › protection_rules › bess › protection_bess_measurement_source
0
unset
Use → row 5
355 INT16U 1 read/write ems__control protections__protection_rules__bess__protection_bess_poll_ms
protections › protection_rules › bess › protection_bess_poll_ms
200 Use → row 5
357 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_overcurrent_enabled
protections › protection_rules › ev_charging › protection_ev_overcurrent_enabled
0 Use → row 5
358 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_overcurrent_threshold_a
protections › protection_rules › ev_charging › protection_ev_overcurrent_threshold_a
0
unset
Use → row 5
360 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_overcurrent_delay_ms
protections › protection_rules › ev_charging › protection_ev_overcurrent_delay_ms
0
unset
Use → row 5
362 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_overtemperature_enabled
protections › protection_rules › ev_charging › protection_ev_overtemperature_enabled
0 Use → row 5
363 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_overtemperature_c
protections › protection_rules › ev_charging › protection_ev_overtemperature_c
0
unset
Use → row 5
365 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_overtemperature_delay_ms
protections › protection_rules › ev_charging › protection_ev_overtemperature_delay_ms
0
unset
Use → row 5
367 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_max_power_enabled
protections › protection_rules › ev_charging › protection_ev_max_power_enabled
0 Use → row 5
368 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_max_power_kw
protections › protection_rules › ev_charging › protection_ev_max_power_kw
0
unset
Use → row 5
370 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_max_power_delay_ms
protections › protection_rules › ev_charging › protection_ev_max_power_delay_ms
0
unset
Use → row 5
372 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_comm_failure_enabled
protections › protection_rules › ev_charging › protection_ev_comm_failure_enabled
0 Use → row 5
373 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_comm_failure_timeout_ms
protections › protection_rules › ev_charging › protection_ev_comm_failure_timeout_ms
0
unset
Use → row 5
375 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_allocation_violation_enabled
protections › protection_rules › ev_charging › protection_ev_allocation_violation_enabled
0 Use → row 5
376 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_allocation_violation_delay_ms
protections › protection_rules › ev_charging › protection_ev_allocation_violation_delay_ms
0
unset
Use → row 5
378 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_grid_capacity_enabled
protections › protection_rules › ev_charging › protection_ev_grid_capacity_enabled
0 Use → row 5
379 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_grid_capacity_kw
protections › protection_rules › ev_charging › protection_ev_grid_capacity_kw
0
unset
Use → row 5
381 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_grid_capacity_delay_ms
protections › protection_rules › ev_charging › protection_ev_grid_capacity_delay_ms
0
unset
Use → row 5
383 FLOAT32 2 read/write ems__control protections__protection_rules__ev_charging__protection_ev_measurement_source
protections › protection_rules › ev_charging › protection_ev_measurement_source
0
unset
Use → row 5
385 INT16U 1 read/write ems__control protections__protection_rules__ev_charging__protection_ev_poll_ms
protections › protection_rules › ev_charging › protection_ev_poll_ms
200 Use → row 5
387 INT16U 1 read/write ems__control protections__protection_rules__communication__protection_comm_device_timeout_enabled
protections › protection_rules › communication › protection_comm_device_timeout_enabled
0 Use → row 5
388 FLOAT32 2 read/write ems__control protections__protection_rules__communication__protection_comm_device_timeout_ms
protections › protection_rules › communication › protection_comm_device_timeout_ms
0
unset
Use → row 5
390 INT16U 1 read/write ems__control protections__protection_rules__communication__protection_comm_stale_reading_enabled
protections › protection_rules › communication › protection_comm_stale_reading_enabled
0 Use → row 5
391 FLOAT32 2 read/write ems__control protections__protection_rules__communication__protection_comm_stale_reading_timeout_ms
protections › protection_rules › communication › protection_comm_stale_reading_timeout_ms
0
unset
Use → row 5
393 INT16U 1 read/write ems__control protections__protection_rules__communication__protection_comm_bms_timeout_enabled
protections › protection_rules › communication › protection_comm_bms_timeout_enabled
0 Use → row 5
394 FLOAT32 2 read/write ems__control protections__protection_rules__communication__protection_comm_bms_timeout_ms
protections › protection_rules › communication › protection_comm_bms_timeout_ms
0
unset
Use → row 5
396 INT16U 1 read/write ems__control protections__protection_rules__communication__protection_comm_poll_ms
protections › protection_rules › communication › protection_comm_poll_ms
200 Use → row 5
398 INT16U 1 read/write ems__control protections__protection_rules__actions_reset__protection_actions_enabled
protections › protection_rules › actions_reset › protection_actions_enabled
1 Use → row 5
399 INT16U 1 read/write ems__control protections__protection_rules__actions_reset__protection_actions_interval_sec
protections › protection_rules › actions_reset › protection_actions_interval_sec
30 Use → row 5
400 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_enabled
protections › protection_rules › guard › protection_guard_enabled
1 Use → row 5
401 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_evaluate_interval_ms
protections › protection_rules › guard › protection_guard_evaluate_interval_ms
500 Use → row 5
402 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_stop_pcs
protections › protection_rules › guard › protection_guard_stop_pcs
1 Use → row 5
403 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_open_contactor
protections › protection_rules › guard › protection_guard_open_contactor
1 Use → row 5
404 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_auto_reset_max_attempts
protections › protection_rules › guard › protection_guard_auto_reset_max_attempts
3 Use → row 5
405 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_auto_reset_stabilization_ms
protections › protection_rules › guard › protection_guard_auto_reset_stabilization_ms
2000 Use → row 5
406 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_measurement_max_age_ms
protections › protection_rules › guard › protection_guard_measurement_max_age_ms
10000 Use → row 5
407 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_verify_timeout_ms
protections › protection_rules › guard › protection_guard_verify_timeout_ms
5000 Use → row 5
408 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_poll_ms
protections › protection_rules › guard › protection_guard_poll_ms
200 Use → row 5
410 INT16U 1 read/write ems__control protections__protection_rules__guard__protection_guard_event_driven
protections › protection_rules › guard › protection_guard_event_driven
1 Use → row 5
411 INT16U 1 read/write ems__control monitoring_logging__data_push_interval_ms
monitoring_logging › data_push_interval_ms
1000 Use → row 5
412 INT16U 1 read/write ems__control monitoring_logging__default_soc_percent
monitoring_logging › default_soc_percent
50 Use → row 5
413 INT16U 1 read/write ems__control monitoring_logging__default_soh_percent
monitoring_logging › default_soh_percent
50 Use → row 5
2400 BITMAP32 2 read only alarms digital_input_status_validity_base 0 Use → row 5
2420 BITMAP32 2 read only alarms setpoint_status_validity 0 Use → row 5
2550 BITMAP32 2 read only alarms digital_input_status_validity_slot_a 0 Use → row 5
2552 BITMAP32 2 read only alarms digital_input_status_validity_slot_b 0 Use → row 5
2554 BITMAP32 2 read only alarms digital_input_status_validity_slot_c 0 Use → row 5
2556 BITMAP32 2 read only alarms digital_input_status_validity_slot_d 0 Use → row 5
2566 BITMAP32 2 read only alarms digital_output_status_validity_slot_a 0 Use → row 5
2568 BITMAP32 2 read only alarms digital_output_status_validity_slot_b 0 Use → row 5
2570 BITMAP32 2 read only alarms digital_output_status_validity_slot_c 0 Use → row 5
2572 BITMAP32 2 read only alarms digital_output_status_validity_slot_d 0 Use → row 5
2706 FLOAT32 2 read only energies active_energy_delivered_minus_received_kwh 0 Use → row 5
2708 FLOAT32 2 read only energies reactive_energy_delivered_kvarh 0 Use → row 5
← Previous Page 3 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.