EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-19T05:18:12+00:00
Size: 2,146,664 bytes · sha256 6e79ed08a71d

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
28809 BOOL 1 read only pcs2__bc_switch_quantities inverter_voltage_a_phase_overvoltage_fault_flag 0 Use → row 10
28810 BOOL 1 read only pcs2__pcs inverter_voltage_phase_a_overvoltage_fault_flag 0 Use → row 10
28811 BOOL 1 read only pcs2__bc_switch_quantities inverter_voltage_b_phase_overvoltage_fault_flag 0 Use → row 10
28812 BOOL 1 read only pcs2__pcs inverter_voltage_phase_b_overvoltage_fault_flag 0 Use → row 10
28813 BOOL 1 read only pcs2__bc_switch_quantities inverter_voltage_c_phase_overvoltage_fault_flag 0 Use → row 10
28814 BOOL 1 read only pcs2__pcs inverter_voltage_phase_c_overvoltage_fault_flag 0 Use → row 10
28815 BOOL 1 read only pcs2__pcs grid_islanding_fault_flag 0 Use → row 10
28816 BOOL 1 read only pcs2__pcs system_resonance_fault_flag 0 Use → row 10
28817 BOOL 1 read only pcs2__bc_switch_quantities software_overvoltage_overcurrent_flag 0 Use → row 10
28818 BOOL 1 read only pcs2__pcs software_overvoltage_and_overcurrent_flag 0 Use → row 10
28819 BOOL 1 read only pcs2__bc_switch_quantities high_voltage_ride_through_timeout_fault_flag 0 Use → row 10
28820 BOOL 1 read only pcs2__pcs high_voltage_ride_through_timeout_fault_flag 0 Use → row 10
28821 BOOL 1 read only pcs2__bc_switch_quantities inverter_voltage_a_phase_undervoltage_fault_flag 0 Use → row 10
28822 BOOL 1 read only pcs2__pcs inverter_voltage_phase_a_undervoltage_fault_flag 0 Use → row 10
28823 BOOL 1 read only pcs2__bc_switch_quantities inverter_voltage_b_phase_undervoltage_fault_flag 0 Use → row 10
28824 BOOL 1 read only pcs2__pcs inverter_voltage_phase_b_undervoltage_fault_flag 0 Use → row 10
28825 BOOL 1 read only pcs2__bc_switch_quantities inverter_voltage_c_phase_undervoltage_fault_flag 0 Use → row 10
28826 BOOL 1 read only pcs2__pcs inverter_voltage_phase_c_undervoltage_fault_flag 0 Use → row 10
28827 BOOL 1 read only pcs2__pcs off_grid_no_synchronization_signal_fault_flag 0 Use → row 10
28828 BOOL 1 read only pcs2__pcs off_grid_short_circuit_fault_flag 0 Use → row 10
28829 BOOL 1 read only pcs2__bc_switch_quantities low_voltage_ride_through_timeout_fault_flag 0 Use → row 10
28830 BOOL 1 read only pcs2__pcs low_voltage_ride_through_timeout_fault_flag 0 Use → row 10
28831 FLOAT32 2 read only pcs2__bc_battery_cluster battery_temperature_c 25 Use → row 10
28833 INT16 1 read only pcs2__bc_battery_cluster dc_current_a 0 Use → row 10
28834 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_1_mv 3300 Use → row 10
28835 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_2_mv 3301 Use → row 10
28836 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_3_mv 3302 Use → row 10
28837 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_4_mv 3303 Use → row 10
28838 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_5_mv 3304 Use → row 10
28839 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_6_mv 3305 Use → row 10
28840 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_7_mv 3306 Use → row 10
28841 UINT16 1 read only pcs2__bc_battery_cluster cell_voltage_8_mv 3307 Use → row 10
28842 UINT16 1 read only pcs2__bc_battery_cluster operating_status 0 Use → row 10
28843 UINT16 1 read only pcs2__bc_battery_cluster cluster_voltage_v 0 Use → row 10
28844 INT16 1 read only pcs2__bc_battery_cluster cluster_current_a 0 Use → row 10
28845 UINT16 1 read only pcs2__bc_battery_cluster maximum_allowable_charging_power_kw 0 Use → row 10
28846 UINT16 1 read only pcs2__bc_battery_cluster maximum_allowable_discharging_power_kw 0 Use → row 10
28847 UINT16 1 read only pcs2__bc_battery_cluster soc_state_of_charge_item 0 Use → row 10
28848 UINT16 1 read only pcs2__bc_battery_cluster soh_state_of_health_item 0 Use → row 10
28849 UINT16 1 read only pcs2__bc_battery_cluster maximum_cell_voltage_mv 0 Use → row 10
28850 UINT16 1 read only pcs2__bc_battery_cluster maximum_cell_voltage_module_number 0 Use → row 10
28851 UINT16 1 read only pcs2__bc_battery_cluster maximum_cell_voltage_cell_number 0 Use → row 10
28852 UINT16 1 read only pcs2__bc_battery_cluster minimum_cell_voltage_mv 0 Use → row 10
28853 UINT16 1 read only pcs2__bc_battery_cluster minimum_cell_voltage_module_number 0 Use → row 10
28854 UINT16 1 read only pcs2__bc_battery_cluster minimum_cell_voltage_cell_number 0 Use → row 10
28855 INT16 1 read only pcs2__bc_battery_cluster maximum_cell_temperature_c 0 Use → row 10
28856 UINT16 1 read only pcs2__bc_battery_cluster maximum_cell_temperature_module_number 0 Use → row 10
28857 UINT16 1 read only pcs2__bc_battery_cluster maximum_cell_temperature_cell_number 0 Use → row 10
28858 INT16 1 read only pcs2__bc_battery_cluster minimum_cell_temperature_c 0 Use → row 10
28859 UINT16 1 read only pcs2__bc_battery_cluster minimum_cell_temperature_module_number 0 Use → row 10
28860 UINT16 1 read only pcs2__bc_battery_cluster minimum_cell_temperature_cell_number 0 Use → row 10
28861 UINT32 2 read only pcs2__bc_battery_cluster cumulative_charging_energy_kwh 0 Use → row 10
28863 UINT32 2 read only pcs2__bc_battery_cluster cumulative_discharging_energy_kwh 0 Use → row 10
28865 UINT16 1 read only pcs2__bc_battery_cluster main_positive_relay_status 1 Use → row 10
28866 UINT16 1 read only pcs2__bc_battery_cluster main_negative_relay_status 1 Use → row 10
28867 UINT16 1 read only pcs2__bc_battery_cluster pre_charge_relay_status 1 Use → row 10
28868 UINT16 1 read only pcs2__bc_battery_cluster communication_status 1 Use → row 10
28869 UINT16 1 read only pcs2__bc_battery_cluster bms_level_1_alarm 0 Use → row 10
28870 UINT16 1 read only pcs2__bc_battery_cluster bms_level_2_alarm 0 Use → row 10
28871 UINT16 1 read only pcs2__bc_battery_cluster bms_level_3_alarm 0 Use → row 10
28872 INT16 1 read/write pcs2__control__remote_control active_power_set_kw 0 Use → row 10
28873 UINT16 1 read only pcs2__air_condition unit_operating_status 1 Use → row 10
28874 UINT16 1 read only pcs2__air_condition air_conditioner_alarm 0 Use → row 10
28875 UINT16 1 read only pcs2__air_condition air_conditioner_fault 0 Use → row 10
28876 UINT16 1 read only pcs2__air_condition communication_status 1 Use → row 10
28877 UINT16 1 read only pcs2__fire_detector temperature_c 25 Use → row 10
28878 UINT16 1 read only pcs2__fire_detector temperature_alarm 0 Use → row 10
28879 UINT16 1 read only pcs2__fire_detector gas_alarm 0 Use → row 10
28880 UINT16 1 read only pcs2__fire_detector communication_status 1 Use → row 10
28881 INT16 1 read only pcs2__pcs a_phase_output_current_a 0 Use → row 10
28882 INT16 1 read only pcs2__pcs b_phase_output_current_a 0 Use → row 10
28883 INT16 1 read only pcs2__pcs c_phase_output_current_a 0 Use → row 10
28884 INT16 1 read only pcs2__pcs a_phase_voltage_v 0 Use → row 10
28885 INT16 1 read only pcs2__pcs b_phase_voltage_v 0 Use → row 10
28886 INT16 1 read only pcs2__pcs c_phase_voltage_v 0 Use → row 10
28887 INT16 1 read only pcs2__pcs three_phase_total_active_power_kwh 0 Use → row 10
28888 INT16 1 read only pcs2__pcs three_phase_total_reactive_power_kvar 0 Use → row 10
28889 INT16 1 read only pcs2__pcs three_phase_total_apparent_power_kvar 0 Use → row 10
28890 UINT32 2 read only pcs2__pcs cumulative_discharging_energy_kwh 0 Use → row 10
28892 UINT32 2 read only pcs2__pcs cumulative_charging_energy_kwh 0 Use → row 10
28894 INT16 1 read only pcs2__pcs module_current_maximum_temperature_c 0 Use → row 10
28895 INT16 1 read only pcs2__pcs dc_power_kw 0 Use → row 10
28896 INT16 1 read only pcs2__pcs dc_voltage_v 0 Use → row 10
28897 INT16 1 read only pcs2__pcs dc_current_a 0 Use → row 10
28898 UINT16 1 read only pcs2__pcs pcs_start_stop_status 0 Use → row 10
28899 UINT16 1 read only pcs2__pcs pcs_grid_connected_status 0 Use → row 10
28900 UINT16 1 read only pcs2__pcs pcs_off_grid_status 0 Use → row 10
28901 UINT16 1 read only pcs2__pcs pcs_alarm_present 0 Use → row 10
28902 UINT16 1 read only pcs2__pcs pcs_fault_present 0 Use → row 10
28903 UINT16 1 read only pcs2__pcs communication_status 0 Use → row 10
28904 FLOAT32 2 read only pcs2__auxiliary insulation_resistance_mohm 5 Use → row 10
28906 FLOAT32 2 read only pcs2__auxiliary fuse_continuity_ohm 0.1 Use → row 10
28908 FLOAT32 2 read only pcs2__auxiliary coolant_flow_rate_lpm 28 Use → row 10
28910 FLOAT32 2 read only pcs2__auxiliary coolant_pump_rpm 2950 Use → row 10
28912 UINT16 1 read only pcs2__auxiliary heater_status 1 Use → row 10
28913 INT16 1 read only pcs2__auxiliary heater_power_kw 6 Use → row 10
28914 FLOAT32 2 read only pcs2__auxiliary exchanger_inlet_temp_c 40 Use → row 10
28916 FLOAT32 2 read only pcs2__auxiliary exchanger_outlet_temp_c 30 Use → row 10
28918 UINT16 1 read only pcs2__auxiliary power_response_time_ms 120 Use → row 10
28919 UINT16 1 read only pcs2__auxiliary activation_time_t90_ms 800 Use → row 10
← Previous Page 37 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.