EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-18T23:41:10+00:00 (from cache)
Size: 2,146,663 bytes · sha256 5502e4165d07

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
2710 FLOAT32 2 read only energies reactive_energy_received_kvarh 0 Use → row 9
2714 FLOAT32 2 read only energies reactive_energy_delivered_minus_received_kvarh 0 Use → row 9
2716 FLOAT32 2 read only energies apparent_energy_delivered_kvah 0 Use → row 9
2718 FLOAT32 2 read only energies apparent_energy_received_kvah 0 Use → row 9
2722 FLOAT32 2 read only energies apparent_energy_delivered_minus_received_kvah 0 Use → row 9
3002 FLOAT32 2 read only currents current_b_a 0 Use → row 9
3004 FLOAT32 2 read only currents current_c_a 0 Use → row 9
3006 FLOAT32 2 read only currents current_n_a 0 Use → row 9
3010 FLOAT32 2 read only currents current_avg_a 0 Use → row 9
3020 FLOAT32 2 read/write voltages voltage_ab_v 444.720001 Use → row 9
3022 FLOAT32 2 read/write voltages voltage_bc_v 0 Use → row 9
3024 FLOAT32 2 read/write voltages voltage_ca_v 0 Use → row 9
3026 FLOAT32 2 read/write voltages voltage_ll_avg_v 0 Use → row 9
3028 FLOAT32 2 read/write voltages voltage_an_v 0 Use → row 9
3030 FLOAT32 2 read/write voltages voltage_bn_v 0 Use → row 9
3032 FLOAT32 2 read/write voltages voltage_cn_v 0 Use → row 9
3036 FLOAT32 2 read/write voltages voltage_ln_avg_v 0 Use → row 9
3054 FLOAT32 2 read only power active_power_a_kw 0 Use → row 9
3056 FLOAT32 2 read only power active_power_b_kw 0 Use → row 9
3058 FLOAT32 2 read only power active_power_c_kw 0 Use → row 9
3060 FLOAT32 2 read only power active_power_total_kw 0 Use → row 9
3062 FLOAT32 2 read only power reactive_power_a_kvar 0 Use → row 9
3064 FLOAT32 2 read only power reactive_power_b_kvar 0 Use → row 9
3066 FLOAT32 2 read only power reactive_power_c_kvar 0 Use → row 9
3068 FLOAT32 2 read only power reactive_power_total_kvar 0 Use → row 9
3070 FLOAT32 2 read only power apparent_power_a_kva 0 Use → row 9
3072 FLOAT32 2 read only power apparent_power_b_kva 0 Use → row 9
3074 FLOAT32 2 read only power apparent_power_c_kva 0 Use → row 9
3076 FLOAT32 2 read only power apparent_power_total_kva 0 Use → row 9
3110 FLOAT32 2 read only frequency frequency_hz 0 Use → row 9
3144 FLOAT32 2 read only power_factor pf_a 0 Use → row 9
3146 FLOAT32 2 read only power_factor pf_b — Use → row 9
3148 FLOAT32 2 read only power_factor pf_c 0 Use → row 9
3150 FLOAT32 2 read only power_factor pf_total 0 Use → row 9
3152 BITMAP32 2 read only alarms alarm_code 0 Use → row 9
3154 BITMAP32 2 read only ems_health ems_function_fault_bitmap 2 Use → row 9
3156 INT32U 2 read only ems_health ems_health_monitor_age_s 0 Use → row 9
3158 BOOL 1 read only ems_health ems_http_api_down 0 Use → row 9
3159 BOOL 1 read only ems_health ems_sync_lastvalues_down 1 Use → row 9
3160 BOOL 1 read only ems_health ems_folder_cleaner_down 0 Use → row 9
3161 BOOL 1 read only ems_health ems_main_down 0 Use → row 9
3162 BOOL 1 read only ems_health ems_modbus_server_down 0 Use → row 9
3163 BOOL 1 read only ems_health ems_pcs_client_down 0 Use → row 9
3164 INT32U 2 read only ems_health ems_pcs_client_age_s 1 Use → row 9
3166 BOOL 1 read only ems_health ems_grid_meter_client_down 0 Use → row 9
3167 INT32U 2 read only ems_health ems_grid_meter_client_age_s 0 Use → row 9
3169 BOOL 1 read only ems_health ems_solar_meter_client_down 0 Use → row 9
3170 INT32U 2 read only ems_health ems_solar_meter_client_age_s 0 Use → row 9
3172 BOOL 1 read only ems_health ems_frequency_meter_client_down 0 Use → row 9
3173 INT32U 2 read only ems_health ems_frequency_meter_client_age_s 0 Use → row 9
3175 BOOL 1 read only ems_health ems_air_condition_client_down 0 Use → row 9
3176 INT32U 2 read only ems_health ems_air_condition_client_age_s 0 Use → row 9
3178 BOOL 1 read only ems_health ems_fire_safety_client_down 0 Use → row 9
3179 INT32U 2 read only ems_health ems_fire_safety_client_age_s 0 Use → row 9
3181 BOOL 1 read only ems_health ems_cooling_unit_client_down 0 Use → row 9
3182 INT32U 2 read only ems_health ems_cooling_unit_client_age_s 0 Use → row 9
3184 BOOL 1 read only ems_health ems_sensor_block_client_down 0 Use → row 9
3185 INT32U 2 read only ems_health ems_sensor_block_client_age_s 0 Use → row 9
3187 BOOL 1 read only ems_health ems_bmu_client_down 0 Use → row 9
3188 INT32U 2 read only ems_health ems_bmu_client_age_s 0 Use → row 9
3190 BOOL 1 read only ems_health ems_ups_client_down 0 Use → row 9
3191 INT32U 2 read only ems_health ems_ups_client_age_s 0 Use → row 9
3193 BOOL 1 read only ems_health ems_bess_energy_meter_client_down 0 Use → row 9
3194 INT32U 2 read only ems_health ems_bess_energy_meter_client_age_s 0 Use → row 9
3196 BOOL 1 read only ems_health ems_ffr_energy_meter_client_down 0 Use → row 9
3197 INT32U 2 read only ems_health ems_ffr_energy_meter_client_age_s 0 Use → row 9
3199 BOOL 1 read only ems_health ems_door_sensor_client_down 0 Use → row 9
3200 INT32U 2 read only ems_health ems_door_sensor_client_age_s 0 Use → row 9
3202 BOOL 1 read only ems_health ems_temperature_sensor_client_down 0 Use → row 9
3203 INT32U 2 read only ems_health ems_temperature_sensor_client_age_s 0 Use → row 9
3205 BOOL 1 read only ems_health ems_flood_sensor_client_down 0 Use → row 9
3206 INT32U 2 read only ems_health ems_flood_sensor_client_age_s 0 Use → row 9
3208 BOOL 1 read only ems_health ems_smoke_sensor_client_down 0 Use → row 9
3209 INT32U 2 read only ems_health ems_smoke_sensor_client_age_s 0 Use → row 9
3211 BOOL 1 read only ems_health ems_heat_sensor_client_down 0 Use → row 9
3212 INT32U 2 read only ems_health ems_heat_sensor_client_age_s 0 Use → row 9
3214 BOOL 1 read only ems_health ems_ev_charger_client_down 0 Use → row 9
3215 INT32U 2 read only ems_health ems_ev_charger_client_age_s 0 Use → row 9
3217 BOOL 1 read only ems_health ems_contactor_client_down 0 Use → row 9
3218 INT32U 2 read only ems_health ems_contactor_client_age_s 5 Use → row 9
3220 BOOL 1 read only ems_health ems_alarm_action_down 0 Use → row 9
3221 BOOL 1 read only ems_health ems_health_down 0 Use → row 9
13598 INT32U 2 read only alarms current_disturbance 0 Use → row 9
13600 INT32U 2 read only alarms voltage_disturbance 0 Use → row 9
24669 FLOAT32 2 read only currents current_a_a 0 Use → row 9
25000 FLOAT32 2 read only ac1__temperatures room_temp_c — Use → row 9
25002 FLOAT32 2 read only ac1__temperatures supply_air_temp_c — Use → row 9
25004 FLOAT32 2 read only ac1__temperatures return_air_temp_c — Use → row 9
25006 FLOAT32 2 read only ac1__temperatures evap_inlet_temp_c — Use → row 9
25008 FLOAT32 2 read only ac1__temperatures evap_outlet_temp_c — Use → row 9
25010 FLOAT32 2 read only ac1__temperatures cond_inlet_temp_c — Use → row 9
25012 FLOAT32 2 read only ac1__temperatures cond_outlet_temp_c — Use → row 9
25014 FLOAT32 2 read only ac1__temperatures outdoor_temp_c — Use → row 9
25016 FLOAT32 2 read only ac1__temperatures suction_line_temp_c — Use → row 9
25018 FLOAT32 2 read only ac1__temperatures discharge_line_temp_c — Use → row 9
25020 FLOAT32 2 read only ac1__pressures suction_pressure_kpa — Use → row 9
25022 FLOAT32 2 read only ac1__pressures discharge_pressure_kpa — Use → row 9
25024 FLOAT32 2 read only ac1__humidity room_rh_percent — Use → row 9
25026 FLOAT32 2 read only ac1__humidity return_rh_percent — Use → row 9
25028 FLOAT32 2 read/write ac1__control__setpoints cooling_setpoint_c — Use → row 9
← Previous Page 4 of 75 Next →