EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-18T23:52:59+00:00 (from cache)
Size: 2,146,663 bytes · sha256 7088bd1c4a6f

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
25176 FLOAT32 2 read only ac3__temperatures evap_inlet_temp_c — Use → row 5
25178 FLOAT32 2 read only ac3__temperatures evap_outlet_temp_c — Use → row 5
25180 FLOAT32 2 read only ac3__temperatures cond_inlet_temp_c — Use → row 5
25182 FLOAT32 2 read only ac3__temperatures cond_outlet_temp_c — Use → row 5
25184 FLOAT32 2 read only ac3__temperatures outdoor_temp_c — Use → row 5
25186 FLOAT32 2 read only ac3__temperatures suction_line_temp_c — Use → row 5
25188 FLOAT32 2 read only ac3__temperatures discharge_line_temp_c — Use → row 5
25190 FLOAT32 2 read only ac3__pressures suction_pressure_kpa — Use → row 5
25192 FLOAT32 2 read only ac3__pressures discharge_pressure_kpa — Use → row 5
25194 FLOAT32 2 read only ac3__humidity room_rh_percent — Use → row 5
25196 FLOAT32 2 read only ac3__humidity return_rh_percent — Use → row 5
25198 FLOAT32 2 read/write ac3__control__setpoints cooling_setpoint_c — Use → row 5
25200 FLOAT32 2 read/write ac3__control__setpoints heating_setpoint_c — Use → row 5
25202 FLOAT32 2 read/write ac3__control__setpoints supply_air_setpoint_c — Use → row 5
25204 FLOAT32 2 read/write ac3__control__setpoints humidity_setpoint_percent — Use → row 5
25206 FLOAT32 2 read/write ac3__control__setpoints deadband_c — Use → row 5
25208 FLOAT32 2 read/write ac3__control__fan fan_speed_percent — Use → row 5
25210 ENUM16 1 read/write ac3__control__fan fan_mode
4 enum values
— Use → row 5
25211 ENUM16 1 read/write ac3__control__mode system_mode
6 enum values
— Use → row 5
25212 ENUM16 1 read/write ac3__control__mode occupancy_mode
2 enum values
— Use → row 5
25213 INT16U 1 read only ac3__status unit_running — Use → row 5
25214 INT16U 1 read only ac3__status compressor1_running — Use → row 5
25215 INT16U 1 read only ac3__status compressor2_running — Use → row 5
25216 INT16U 1 read only ac3__status economizer_active — Use → row 5
25217 INT16U 1 read only ac3__status defrost_active — Use → row 5
25218 INT16U 1 read only ac3__status fault_active — Use → row 5
25219 INT16U 1 read only ac3__status supply_fan_running — Use → row 5
25220 INT16U 1 read only ac3__status return_fan_running — Use → row 5
25221 BITMAP32 2 read only ac3__alarms alarm_bitmap_1 — Use → row 5
25223 INT16U 1 read only ac3__alarms high_pressure_trip_count — Use → row 5
25224 INT16U 1 read only ac3__alarms low_pressure_trip_count — Use → row 5
25225 INT16U 1 read only ac3__alarms high_temp_alarm_count — Use → row 5
25226 INT16U 1 read only ac3__alarms low_temp_alarm_count — Use → row 5
25227 INT16U 1 read only ac3__alarms sensor_fault_count — Use → row 5
25228 FLOAT32 2 read only ac3__power active_power_kw — Use → row 5
25230 FLOAT32 2 read only ac3__power energy_consumed_kwh — Use → row 5
25232 FLOAT32 2 read only ac3__power demand_kw — Use → row 5
25234 FLOAT32 2 read only ac3__runtime compressor1_hours — Use → row 5
25236 FLOAT32 2 read only ac3__runtime compressor2_hours — Use → row 5
25238 FLOAT32 2 read only ac3__runtime fan_hours — Use → row 5
25240 BOOL16 1 read/write ac3__control__io digital_output_1_command — Use → row 5
25241 BOOL16 1 read/write ac3__control__io digital_output_2_command — Use → row 5
25242 FLOAT32 2 read/write ac3__control__io analog_output_1_percent — Use → row 5
25244 FLOAT32 2 read/write ac3__control__io analog_output_2_percent — Use → row 5
25246 BOOL16 1 read only ac3__io digital_input_1_status — Use → row 5
25247 BOOL16 1 read only ac3__io digital_input_2_status — Use → row 5
25248 ENUM16 1 read/write ac3__control__commands command_on_off
3 enum values
— Use → row 5
25249 ENUM16 1 read/write ac3__control__commands command_reset_alarms
2 enum values
— Use → row 5
25250 ENUM16 1 read/write ac3__control__commands command_force_defrost
2 enum values
— Use → row 5
25251 INT16U 1 read only ac3__communication protocol_version — Use → row 5
25252 INT16U 1 read only ac3__communication firmware_version_major — Use → row 5
25253 INT16U 1 read only ac3__communication firmware_version_minor — Use → row 5
25254 INT16U 1 read only ac3__communication device_address — Use → row 5
25255 FLOAT32 2 read only ac4__temperatures room_temp_c — Use → row 5
25257 FLOAT32 2 read only ac4__temperatures supply_air_temp_c — Use → row 5
25259 FLOAT32 2 read only ac4__temperatures return_air_temp_c — Use → row 5
25261 FLOAT32 2 read only ac4__temperatures evap_inlet_temp_c — Use → row 5
25263 FLOAT32 2 read only ac4__temperatures evap_outlet_temp_c — Use → row 5
25265 FLOAT32 2 read only ac4__temperatures cond_inlet_temp_c — Use → row 5
25267 FLOAT32 2 read only ac4__temperatures cond_outlet_temp_c — Use → row 5
25269 FLOAT32 2 read only ac4__temperatures outdoor_temp_c — Use → row 5
25271 FLOAT32 2 read only ac4__temperatures suction_line_temp_c — Use → row 5
25273 FLOAT32 2 read only ac4__temperatures discharge_line_temp_c — Use → row 5
25275 FLOAT32 2 read only ac4__pressures suction_pressure_kpa — Use → row 5
25277 FLOAT32 2 read only ac4__pressures discharge_pressure_kpa — Use → row 5
25279 FLOAT32 2 read only ac4__humidity room_rh_percent — Use → row 5
25281 FLOAT32 2 read only ac4__humidity return_rh_percent — Use → row 5
25283 FLOAT32 2 read/write ac4__control__setpoints cooling_setpoint_c — Use → row 5
25285 FLOAT32 2 read/write ac4__control__setpoints heating_setpoint_c — Use → row 5
25287 FLOAT32 2 read/write ac4__control__setpoints supply_air_setpoint_c — Use → row 5
25289 FLOAT32 2 read/write ac4__control__setpoints humidity_setpoint_percent — Use → row 5
25291 FLOAT32 2 read/write ac4__control__setpoints deadband_c — Use → row 5
25293 FLOAT32 2 read/write ac4__control__fan fan_speed_percent — Use → row 5
25295 ENUM16 1 read/write ac4__control__fan fan_mode
4 enum values
— Use → row 5
25296 ENUM16 1 read/write ac4__control__mode system_mode
6 enum values
— Use → row 5
25297 ENUM16 1 read/write ac4__control__mode occupancy_mode
2 enum values
— Use → row 5
25298 INT16U 1 read only ac4__status unit_running — Use → row 5
25299 INT16U 1 read only ac4__status compressor1_running — Use → row 5
25300 INT16U 1 read only ac4__status compressor2_running — Use → row 5
25301 INT16U 1 read only ac4__status economizer_active — Use → row 5
25302 INT16U 1 read only ac4__status defrost_active — Use → row 5
25303 INT16U 1 read only ac4__status fault_active — Use → row 5
25304 INT16U 1 read only ac4__status supply_fan_running — Use → row 5
25305 INT16U 1 read only ac4__status return_fan_running — Use → row 5
25306 BITMAP32 2 read only ac4__alarms alarm_bitmap_1 — Use → row 5
25308 INT16U 1 read only ac4__alarms high_pressure_trip_count — Use → row 5
25309 INT16U 1 read only ac4__alarms low_pressure_trip_count — Use → row 5
25310 INT16U 1 read only ac4__alarms high_temp_alarm_count — Use → row 5
25311 INT16U 1 read only ac4__alarms low_temp_alarm_count — Use → row 5
25312 INT16U 1 read only ac4__alarms sensor_fault_count — Use → row 5
25313 FLOAT32 2 read only ac4__power active_power_kw — Use → row 5
25315 FLOAT32 2 read only ac4__power energy_consumed_kwh — Use → row 5
25317 FLOAT32 2 read only ac4__power demand_kw — Use → row 5
25319 FLOAT32 2 read only ac4__runtime compressor1_hours — Use → row 5
25321 FLOAT32 2 read only ac4__runtime compressor2_hours — Use → row 5
25323 FLOAT32 2 read only ac4__runtime fan_hours — Use → row 5
25325 BOOL16 1 read/write ac4__control__io digital_output_1_command — Use → row 5
25326 BOOL16 1 read/write ac4__control__io digital_output_2_command — Use → row 5
25327 FLOAT32 2 read/write ac4__control__io analog_output_1_percent — Use → row 5
25329 FLOAT32 2 read/write ac4__control__io analog_output_2_percent — Use → row 5
← Previous Page 6 of 75 Next →