EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-19T08:52:51+00:00
Size: 2,146,663 bytes · sha256 db5933e76160

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
31202 UINT16 1 read only pcs8__fire_detector communication_status 1 Use → row 5
31203 INT16 1 read only pcs8__pcs a_phase_output_current_a 0 Use → row 5
31204 INT16 1 read only pcs8__pcs b_phase_output_current_a 0 Use → row 5
31205 INT16 1 read only pcs8__pcs c_phase_output_current_a 0 Use → row 5
31206 INT16 1 read only pcs8__pcs a_phase_voltage_v 0 Use → row 5
31207 INT16 1 read only pcs8__pcs b_phase_voltage_v 0 Use → row 5
31208 INT16 1 read only pcs8__pcs c_phase_voltage_v 0 Use → row 5
31209 INT16 1 read only pcs8__pcs three_phase_total_active_power_kwh 0 Use → row 5
31210 INT16 1 read only pcs8__pcs three_phase_total_reactive_power_kvar 0 Use → row 5
31211 INT16 1 read only pcs8__pcs three_phase_total_apparent_power_kvar 0 Use → row 5
31212 UINT32 2 read only pcs8__pcs cumulative_discharging_energy_kwh 0 Use → row 5
31214 UINT32 2 read only pcs8__pcs cumulative_charging_energy_kwh 0 Use → row 5
31216 INT16 1 read only pcs8__pcs module_current_maximum_temperature_c 0 Use → row 5
31217 INT16 1 read only pcs8__pcs dc_power_kw 0 Use → row 5
31218 INT16 1 read only pcs8__pcs dc_voltage_v 0 Use → row 5
31219 INT16 1 read only pcs8__pcs dc_current_a 0 Use → row 5
31220 UINT16 1 read only pcs8__pcs pcs_start_stop_status 0 Use → row 5
31221 UINT16 1 read only pcs8__pcs pcs_grid_connected_status 0 Use → row 5
31222 UINT16 1 read only pcs8__pcs pcs_off_grid_status 0 Use → row 5
31223 UINT16 1 read only pcs8__pcs pcs_alarm_present 0 Use → row 5
31224 UINT16 1 read only pcs8__pcs pcs_fault_present 0 Use → row 5
31225 UINT16 1 read only pcs8__pcs communication_status 0 Use → row 5
31226 FLOAT32 2 read only pcs8__auxiliary insulation_resistance_mohm 5 Use → row 5
31228 FLOAT32 2 read only pcs8__auxiliary fuse_continuity_ohm 0.1 Use → row 5
31230 FLOAT32 2 read only pcs8__auxiliary coolant_flow_rate_lpm 28 Use → row 5
31232 FLOAT32 2 read only pcs8__auxiliary coolant_pump_rpm 2950 Use → row 5
31234 UINT16 1 read only pcs8__auxiliary heater_status 1 Use → row 5
31235 INT16 1 read only pcs8__auxiliary heater_power_kw 6 Use → row 5
31236 FLOAT32 2 read only pcs8__auxiliary exchanger_inlet_temp_c 40 Use → row 5
31238 FLOAT32 2 read only pcs8__auxiliary exchanger_outlet_temp_c 30 Use → row 5
31240 UINT16 1 read only pcs8__auxiliary power_response_time_ms 120 Use → row 5
31241 UINT16 1 read only pcs8__auxiliary activation_time_t90_ms 800 Use → row 5
31242 UINT16 1 read only pcs8__auxiliary activation_time_t100_ms 1000 Use → row 5
31243 UINT16 1 read only pcs8__auxiliary filter_latency_ms 30 Use → row 5
31244 INT16 1 read only pcs8__auxiliary time_sync_offset_ms 0 Use → row 5
31245 INT16 1 read only pcs8__auxiliary comms_loss_failsafe_power_kw 0 Use → row 5
31246 UINT16 1 read only pcs8__auxiliary telemetry_sample_rate_hz 10 Use → row 5
31247 UINT16 1 read only pcs8__auxiliary ride_through_ms 500 Use → row 5
31248 UINT16 1 read only pcs8__auxiliary ramp_rate_kw_s 60 Use → row 5
31249 UINT16 1 read only pcs8__auxiliary response_delay_ms 100 Use → row 5
31250 FLOAT32 2 read only pcs8__auxiliary measured_droop_pct 5 Use → row 5
31252 FLOAT32 2 read only pcs8__auxiliary delivered_power_pct 100 Use → row 5
31254 UINT16 1 read only pcs8__auxiliary measured_hold_duration_sec 900 Use → row 5
31255 UINT16 1 read only pcs8__auxiliary recovery_time_sec 5 Use → row 5
31256 FLOAT32 2 read only pcs8__auxiliary grid_frequency_hz 50 Use → row 5
31258 BOOL 1 read only pcs8__ems ems_state1_bit_field_item 0 Use → row 5
31259 BOOL 1 read only pcs8__ems ems_state1_item 0 Use → row 5
31260 BOOL 1 read only pcs8__ems ems_state2_bit_field_item 0 Use → row 5
31261 BOOL 1 read only pcs8__ems ems_state2_item 0 Use → row 5
31262 UINT16 1 read only pcs8__ems ems_main_state 0 Use → row 5
31263 UINT16 1 read only pcs8__ems ems_control_status 1 Use → row 5
31264 UINT16 1 read only pcs8__ems system_current_highest_alarm_level 0 Use → row 5
31265 UINT16 1 read only pcs8__ems ems_reset_pcs_status_item 0 Use → row 5
31266 UINT16 1 read only pcs8__ems ems_reset_bms_status_item 0 Use → row 5
31267 UINT16 1 read only pcs8__ems system_maximum_allowable_charging_power_kw 0 Use → row 5
31268 UINT16 1 read only pcs8__ems system_maximum_allowable_discharging_power_kw 0 Use → row 5
31269 INT16 1 read/write pcs8__control__remote_control start_stop_control_item 0 Use → row 5
31270 INT16 1 read/write pcs8__control__remote_control operation_mode_setting_item 0 Use → row 5
31271 INT16 1 read/write pcs8__control__remote_control scheduling_mode_item 0 Use → row 5
31272 INT16 1 read/write pcs8__control__remote_control pcs_switch_control_valid_when_8002_register_value_is_2_item 0 Use → row 5
31273 INT16 1 read/write pcs8__control__remote_control pcs_power_control_valid_when_8002_register_value_is_2_kw 0 Use → row 5
31274 INT16 1 read/write pcs8__control__remote_control pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item 0 Use → row 5
31275 UINT32 2 read/write pcs8__control__remote_control ems_time_setting_item 0 Use → row 5
31277 UINT16 1 read/write pcs8__control__remote_control ems_reset_pcs_item 0 Use → row 5
31278 UINT16 1 read/write pcs8__control__remote_control ems_reset_bms_item 0 Use → row 5
31279 UINT16 1 read only pcs8__ems electricity_meter_communication_status_item 1 Use → row 5
31280 UINT16 1 read only pcs8__remote_control meter_communiction_status_item 1 Use → row 5
31281 INT16 1 read/write pcs8__control__remote_control mode_pq_vf_command_item 0 Use → row 5
31282 INT16 1 read/write pcs9__control__remote_control start_stop_command 0 Use → row 5
31283 BOOL 1 read only pcs9__bc 1_cell_voltage_too_high 0 Use → row 5
31284 BOOL 1 read only pcs9__bc_switch_quantities l1_cell_voltage_high 0 Use → row 5
31285 BOOL 1 read only pcs9__bc l1_cell_voltage_too_low 0 Use → row 5
31286 BOOL 1 read only pcs9__bc_switch_quantities l1_cell_voltage_low 0 Use → row 5
31287 BOOL 1 read only pcs9__bc l1_cell_voltage_difference_too_large 0 Use → row 5
31288 BOOL 1 read only pcs9__bc_switch_quantities l1_cell_voltage_difference_excessive 0 Use → row 5
31289 BOOL 1 read only pcs9__bc l1_total_voltage_too_high 0 Use → row 5
31290 BOOL 1 read only pcs9__bc_switch_quantities l1_total_voltage_high 0 Use → row 5
31291 BOOL 1 read only pcs9__bc l1_total_voltage_too_low 0 Use → row 5
31292 BOOL 1 read only pcs9__bc_switch_quantities l1_total_voltage_low 0 Use → row 5
31293 BOOL 1 read only pcs9__bc l1_battery_discharge_temperature_too_high 0 Use → row 5
31294 BOOL 1 read only pcs9__bc_switch_quantities l1_battery_discharging_temperature_high 0 Use → row 5
31295 BOOL 1 read only pcs9__bc l1_battery_discharge_temperature_too_low 0 Use → row 5
31296 BOOL 1 read only pcs9__bc_switch_quantities l1_battery_discharging_temperature_low 0 Use → row 5
31297 BOOL 1 read only pcs9__bc l1_battery_charge_temperature_too_high 0 Use → row 5
31298 BOOL 1 read only pcs9__bc_switch_quantities l1_battery_charging_temperature_high 0 Use → row 5
31299 BOOL 1 read only pcs9__bc l1_battery_charge_temperature_too_low 0 Use → row 5
31300 BOOL 1 read only pcs9__bc_switch_quantities l1_battery_charging_temperature_low 0 Use → row 5
31301 BOOL 1 read only pcs9__bc l1_cell_temperature_difference_too_large 0 Use → row 5
31302 BOOL 1 read only pcs9__bc_switch_quantities l1_cell_temperature_difference_excessive 0 Use → row 5
31303 BOOL 1 read only pcs9__bc l1_charging_current_too_high 0 Use → row 5
31304 BOOL 1 read only pcs9__bc_switch_quantities l1_charging_current_high 0 Use → row 5
31305 BOOL 1 read only pcs9__bc l1_discharging_current_too_high 0 Use → row 5
31306 BOOL 1 read only pcs9__bc_switch_quantities l1_discharging_current_high 0 Use → row 5
31307 BOOL 1 read only pcs9__bc l1_insulation_fault 0 Use → row 5
31308 BOOL 1 read only pcs9__bc_switch_quantities l1_insulation_fault 0 Use → row 5
31309 BOOL 1 read only pcs9__bc l1_communication_fault 0 Use → row 5
31310 BOOL 1 read only pcs9__bc_switch_quantities l1_communication_fault 0 Use → row 5
31311 BOOL 1 read only pcs9__bc l1_main_positive_relay_fault 0 Use → row 5
31312 BOOL 1 read only pcs9__bc_switch_quantities l1_main_positive_relay_fault 0 Use → row 5
31313 BOOL 1 read only pcs9__bc l1_main_negative_relay_fault 0 Use → row 5
← Previous Page 60 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.