EMS Registers

Search the EMS register map to find the address and data type of the register you want to write, then send it to the editor.

Source

Re-reads the register map from the EMS.
Endpoint: http://ems-backend:8080/api/v1/ems/register-map
Fetched: 2026-11-19T00:05:06+00:00 (from cache)
Size: 2,146,664 bytes · sha256 27fe28b7d4a4

The EMS writes its merged register map into a file inside its own container, and the archive the simulator syncs deliberately leaves that ems/ directory out. The EMS serves the file itself at GET /api/v1/ems/register-map, so this page reads it over HTTP like every other EMS fact it shows - there is no copy in the stack's shared volume.

7,404 of 7,404 registers

Address Type Regs Access Category Register Value
25331 BOOL16 1 read only ac4__io digital_input_1_status — Use → row 1
25332 BOOL16 1 read only ac4__io digital_input_2_status — Use → row 1
25333 ENUM16 1 read/write ac4__control__commands command_on_off
3 enum values
— Use → row 1
25334 ENUM16 1 read/write ac4__control__commands command_reset_alarms
2 enum values
— Use → row 1
25335 ENUM16 1 read/write ac4__control__commands command_force_defrost
2 enum values
— Use → row 1
25336 INT16U 1 read only ac4__communication protocol_version — Use → row 1
25337 INT16U 1 read only ac4__communication firmware_version_major — Use → row 1
25338 INT16U 1 read only ac4__communication firmware_version_minor — Use → row 1
25339 INT16U 1 read only ac4__communication device_address — Use → row 1
25340 FLOAT32 2 read only ac5__temperatures room_temp_c — Use → row 1
25342 FLOAT32 2 read only ac5__temperatures supply_air_temp_c — Use → row 1
25344 FLOAT32 2 read only ac5__temperatures return_air_temp_c — Use → row 1
25346 FLOAT32 2 read only ac5__temperatures evap_inlet_temp_c — Use → row 1
25348 FLOAT32 2 read only ac5__temperatures evap_outlet_temp_c — Use → row 1
25350 FLOAT32 2 read only ac5__temperatures cond_inlet_temp_c — Use → row 1
25352 FLOAT32 2 read only ac5__temperatures cond_outlet_temp_c — Use → row 1
25354 FLOAT32 2 read only ac5__temperatures outdoor_temp_c — Use → row 1
25356 FLOAT32 2 read only ac5__temperatures suction_line_temp_c — Use → row 1
25358 FLOAT32 2 read only ac5__temperatures discharge_line_temp_c — Use → row 1
25360 FLOAT32 2 read only ac5__pressures suction_pressure_kpa — Use → row 1
25362 FLOAT32 2 read only ac5__pressures discharge_pressure_kpa — Use → row 1
25364 FLOAT32 2 read only ac5__humidity room_rh_percent — Use → row 1
25366 FLOAT32 2 read only ac5__humidity return_rh_percent — Use → row 1
25368 FLOAT32 2 read/write ac5__control__setpoints cooling_setpoint_c — Use → row 1
25370 FLOAT32 2 read/write ac5__control__setpoints heating_setpoint_c — Use → row 1
25372 FLOAT32 2 read/write ac5__control__setpoints supply_air_setpoint_c — Use → row 1
25374 FLOAT32 2 read/write ac5__control__setpoints humidity_setpoint_percent — Use → row 1
25376 FLOAT32 2 read/write ac5__control__setpoints deadband_c — Use → row 1
25378 FLOAT32 2 read/write ac5__control__fan fan_speed_percent — Use → row 1
25380 ENUM16 1 read/write ac5__control__fan fan_mode
4 enum values
— Use → row 1
25381 ENUM16 1 read/write ac5__control__mode system_mode
6 enum values
— Use → row 1
25382 ENUM16 1 read/write ac5__control__mode occupancy_mode
2 enum values
— Use → row 1
25383 INT16U 1 read only ac5__status unit_running — Use → row 1
25384 INT16U 1 read only ac5__status compressor1_running — Use → row 1
25385 INT16U 1 read only ac5__status compressor2_running — Use → row 1
25386 INT16U 1 read only ac5__status economizer_active — Use → row 1
25387 INT16U 1 read only ac5__status defrost_active — Use → row 1
25388 INT16U 1 read only ac5__status fault_active — Use → row 1
25389 INT16U 1 read only ac5__status supply_fan_running — Use → row 1
25390 INT16U 1 read only ac5__status return_fan_running — Use → row 1
25391 BITMAP32 2 read only ac5__alarms alarm_bitmap_1 — Use → row 1
25393 INT16U 1 read only ac5__alarms high_pressure_trip_count — Use → row 1
25394 INT16U 1 read only ac5__alarms low_pressure_trip_count — Use → row 1
25395 INT16U 1 read only ac5__alarms high_temp_alarm_count — Use → row 1
25396 INT16U 1 read only ac5__alarms low_temp_alarm_count — Use → row 1
25397 INT16U 1 read only ac5__alarms sensor_fault_count — Use → row 1
25398 FLOAT32 2 read only ac5__power active_power_kw — Use → row 1
25400 FLOAT32 2 read only ac5__power energy_consumed_kwh — Use → row 1
25402 FLOAT32 2 read only ac5__power demand_kw — Use → row 1
25404 FLOAT32 2 read only ac5__runtime compressor1_hours — Use → row 1
25406 FLOAT32 2 read only ac5__runtime compressor2_hours — Use → row 1
25408 FLOAT32 2 read only ac5__runtime fan_hours — Use → row 1
25410 BOOL16 1 read/write ac5__control__io digital_output_1_command — Use → row 1
25411 BOOL16 1 read/write ac5__control__io digital_output_2_command — Use → row 1
25412 FLOAT32 2 read/write ac5__control__io analog_output_1_percent — Use → row 1
25414 FLOAT32 2 read/write ac5__control__io analog_output_2_percent — Use → row 1
25416 BOOL16 1 read only ac5__io digital_input_1_status — Use → row 1
25417 BOOL16 1 read only ac5__io digital_input_2_status — Use → row 1
25418 ENUM16 1 read/write ac5__control__commands command_on_off
3 enum values
— Use → row 1
25419 ENUM16 1 read/write ac5__control__commands command_reset_alarms
2 enum values
— Use → row 1
25420 ENUM16 1 read/write ac5__control__commands command_force_defrost
2 enum values
— Use → row 1
25421 INT16U 1 read only ac5__communication protocol_version — Use → row 1
25422 INT16U 1 read only ac5__communication firmware_version_major — Use → row 1
25423 INT16U 1 read only ac5__communication firmware_version_minor — Use → row 1
25424 INT16U 1 read only ac5__communication device_address — Use → row 1
25425 FLOAT32 2 read only ac6__temperatures room_temp_c — Use → row 1
25427 FLOAT32 2 read only ac6__temperatures supply_air_temp_c — Use → row 1
25429 FLOAT32 2 read only ac6__temperatures return_air_temp_c — Use → row 1
25431 FLOAT32 2 read only ac6__temperatures evap_inlet_temp_c — Use → row 1
25433 FLOAT32 2 read only ac6__temperatures evap_outlet_temp_c — Use → row 1
25435 FLOAT32 2 read only ac6__temperatures cond_inlet_temp_c — Use → row 1
25437 FLOAT32 2 read only ac6__temperatures cond_outlet_temp_c — Use → row 1
25439 FLOAT32 2 read only ac6__temperatures outdoor_temp_c — Use → row 1
25441 FLOAT32 2 read only ac6__temperatures suction_line_temp_c — Use → row 1
25443 FLOAT32 2 read only ac6__temperatures discharge_line_temp_c — Use → row 1
25445 FLOAT32 2 read only ac6__pressures suction_pressure_kpa — Use → row 1
25447 FLOAT32 2 read only ac6__pressures discharge_pressure_kpa — Use → row 1
25449 FLOAT32 2 read only ac6__humidity room_rh_percent — Use → row 1
25451 FLOAT32 2 read only ac6__humidity return_rh_percent — Use → row 1
25453 FLOAT32 2 read/write ac6__control__setpoints cooling_setpoint_c — Use → row 1
25455 FLOAT32 2 read/write ac6__control__setpoints heating_setpoint_c — Use → row 1
25457 FLOAT32 2 read/write ac6__control__setpoints supply_air_setpoint_c — Use → row 1
25459 FLOAT32 2 read/write ac6__control__setpoints humidity_setpoint_percent — Use → row 1
25461 FLOAT32 2 read/write ac6__control__setpoints deadband_c — Use → row 1
25463 FLOAT32 2 read/write ac6__control__fan fan_speed_percent — Use → row 1
25465 ENUM16 1 read/write ac6__control__fan fan_mode
4 enum values
— Use → row 1
25466 ENUM16 1 read/write ac6__control__mode system_mode
6 enum values
— Use → row 1
25467 ENUM16 1 read/write ac6__control__mode occupancy_mode
2 enum values
— Use → row 1
25468 INT16U 1 read only ac6__status unit_running — Use → row 1
25469 INT16U 1 read only ac6__status compressor1_running — Use → row 1
25470 INT16U 1 read only ac6__status compressor2_running — Use → row 1
25471 INT16U 1 read only ac6__status economizer_active — Use → row 1
25472 INT16U 1 read only ac6__status defrost_active — Use → row 1
25473 INT16U 1 read only ac6__status fault_active — Use → row 1
25474 INT16U 1 read only ac6__status supply_fan_running — Use → row 1
25475 INT16U 1 read only ac6__status return_fan_running — Use → row 1
25476 BITMAP32 2 read only ac6__alarms alarm_bitmap_1 — Use → row 1
25478 INT16U 1 read only ac6__alarms high_pressure_trip_count — Use → row 1
25479 INT16U 1 read only ac6__alarms low_pressure_trip_count — Use → row 1
25480 INT16U 1 read only ac6__alarms high_temp_alarm_count — Use → row 1
← Previous Page 7 of 75 Next →

Use opens the editor with the address and type filled into its first row. The address shown here is the address on the wire: a register declared at 3020 is read and written with 3020.