Run a device command sequence three ways: as an alarm action, from Python, or over the REST API. Each has a different safety posture, and the difference is enforced in code rather than by convention.


Purpose

Configure or trigger execution of a sequence that already exists. For creating sequences, see How to Add a Device Command Sequence; for validating them, How to Test Device Command Sequences.


Prerequisites

Method Requires
Alarm action An alarm whose target's model defines the sequence
Python pyModbusTCP, and reachability of the device, the simulator, or a protocol adapter
REST A running EMS backend and its API token
Physical execution authorize_physical, plus the safeguards in the last section

Relevant Files

Path Role
device_command_sequences.py The engine: run_action, run_task, describe
pcs_power_sequence.py The underlying execute_sequence
alarm_actions.py The alarm-triggered executor and its gate_reason
command_sequence_test.py start_test, stop_test, run_test
ems_settings_api.py The REST surface
protocol_adapters.py Modbus / OCPP adapters
resources/views/alarmActionsEditor.blade.php Configuring the alarm-triggered route

Method A — Alarm-Triggered Execution

The sequence is attached to an alarm; the engine runs it when the alarm fires. Configure it in the alarm action editor (see How to Add an Alarm Action).

  1. Open the alarm whose action you want, in /alarm-actions-editor?device_type=…&device_id=….
  2. Select the target device. It need not be the alarmed device.
  3. The editor detects the target's model and lists available_actions for it — the sequences you may choose from are exactly those the model defines.
  4. Assign the sequence.
  5. Enter parameters — the values for the sequence's ${…} placeholders.
  6. Set the condition, mode, order, delay_ms, timeout_ms and failure_action.
  7. Choose the trigger: active to act when the alarm fires, cleared to act when it clears. A cleared action additionally requires allow_on_clear: true.
  8. Save. The engine validates the whole action and refuses a map it could not execute.
  9. Raise the alarm — with the simulator, or by driving the watched register.
  10. Monitor execution and confirm the outcome.

What happens on a clearance

A cleared action passes through gate_reason first, and runs only when all three conditions hold. The refusals are:

allow_on_clear is not set on the action
still active on this device: ALARM-1, ALARM-2
operation mode 'x' does not permit a clearance action

Any one of them leaves the equipment as it is — the deliberate, recoverable outcome.


Method B — Executing from Python

The execution call

run_action(
    client,
    *,
    device_type: str,
    action: str,
    model: str | None = None,
    device_key: str | None = None,
    parameters: dict | None = None,
    config_path: str | None = None,
    control_path: str | None = None,
    protocol: str | None = None,
    debug: bool = False,
    event_logger=None,
    allow_during_backup: bool = False,
) -> list[dict]

Returns the per-step results as a list of dicts.

  • action is the sequence name — an actions key in the model's sequence file.
  • model defaults to the model configured for the device in ems_control_setting.json, so callers normally pass only device_type and action.
  • device_key selects a specific device, which matters for the layer resolution: with a device key the device's own sequence copy is consulted first.
  • allow_during_backup applies only to PCS grid-mode actions; any other device type raises allow_during_backup only applies to the PCS grid-mode actions.

run_task(client, device_type=…, task=…, **kwargs) is a thin alias — "a task is simply an action made of several ordered steps. Kept separate so call sites read as intent."

Discovering what you may run

from device_command_sequences import describe
import json
print(json.dumps(describe("<device_type>"), indent=2))

describe returns, per device type: label, models (each with its file and actions), protocol, configured_model and configured_devices. It is deliberately fault-tolerant — "An inventory call must not fail because one device's protocol is unusable" — and reports protocol_error instead.

Example 1 — Start a BESS

from pyModbusTCP.client import ModbusClient
from device_command_sequences import run_action

client = ModbusClient(host="127.0.0.1", port=502, unit_id=1, timeout=5.0, auto_open=True)
if not client.open():
    raise SystemExit("cannot open Modbus connection")

results = run_action(
    client,
    device_type="pcs",          # the engine key, not the config directory name
    device_key="PCS1",
    action="start",             # writes 0x0291 = 1, then waits 10 s
)
for step in results:
    print(step)

Example 2 — Set PCS active power to 50 kW

results = run_action(
    client,
    device_type="pcs",
    device_key="PCS1",
    action="change_power",
    parameters={"power_kw": 50},    # fills ${power_kw} in the step's value
)

model is omitted on purpose: it resolves from the device's own configuration, and passing a wrong model is the fastest way to address another model's registers. On EPCS105 the step is write_single 0x0D57, encoding: signed_i16, scale: 10 — pass whole kW and let the step's own scale do the conversion.

Example 3 — Resolve the model explicitly, then cap an EV charger at 11 kW

from device_command_sequences import model_for, available_actions, run_action

model = model_for("ev_charger", "EV-1")
print("model:", model)                          # EVC1
print("sequences:", available_actions("ev_charger", model))

results = run_action(
    client,
    device_type="ev_charger",
    device_key="EV-1",
    model=model,
    action="set_power_limit",                   # register 4122, reads ${power_kw}
    parameters={"power_kw": 11},
)

available_actions() is the authoritative list for a model — the names it returns are the only ones run_action will accept.

run_action itself validates the model early with a device-worded message plus the model catalogue, "rather than letting the engine report 'No power sequence file matches PCS model'". It also proves that the copy the device actually runs can serve the model, so a stale copy fails before the sequence starts rather than midway through it.

Example 4 — Multi-device alarm response

The alarm-action path is the supported way to run several sequences off one trigger. From Python, the equivalent is to run them explicitly, and to treat the first failure as fatal when the sequence is safety-relevant:

plan = [
    ("pcs",        "PCS1", "change_power",      {"power_kw": 0}),
    ("ev_charger", "EV-1", "set_current_limit", {"current_a": 16}),
    ("ev_charger", "EV-2", "set_current_limit", {"current_a": 16}),
]

for device_type, device_key, action, params in plan:
    try:
        results = run_action(client, device_type=device_type,
                             device_key=device_key, action=action,
                             parameters=params)
    except DeviceSequenceError as exc:
        print(f"{device_type}/{device_key} {action} failed: {exc}")
        break        # abort: do not continue shedding after a failure
    print(f"{device_type}/{device_key} {action}: {len(results)} steps")

Example 5 — A read-only sequence, safe to run anywhere

Prefer a sequence made only of read_holding steps when you want to prove the wiring without moving anything. read_status is exactly that on the live system.

results = run_action(client, device_type="<category>",
                     device_key="<key>", action="read_status")

Method C — Execution over the REST API

Base path: /api/v1/ems/command-sequences.

Method Path Purpose
GET /command-sequences List devices and read their sequences
GET /command-sequences/backups List backups
PUT /command-sequences/sequences Save sequences
POST /command-sequences/validate Validate without writing
POST /command-sequences/restore Restore a backup
POST /command-sequences/test Run a test
POST /command-sequences/test/stop Stop a running test

The safety property

This is the most important thing in this guide, quoted from the handler:

HTTP callers are always simulator-only: authorize_physical is deliberately not read from the body, so a request can never write to live equipment. Physical runs stay a deliberate Python-side act.

So over REST, execution is simulator-only, and that is not configurable through the API. A request cannot opt itself into writing to live equipment. Physical execution is only possible from Python, deliberately.

Running a test over REST

curl -s -X POST "http://<ems-host>/api/v1/ems/command-sequences/test" \
  -H "Authorization: Bearer <token>" \
  -H "Content-Type: application/json" \
  -d '{
        "device_type": "ev_charger",
        "device_key": "EV-1",
        "action": "set_current_limit",
        "parameters": { "current_a": 16 }
      }'

Both device_type and action are required — a request missing either gets device_type and action are required. This endpoint is the asynchronous one: it calls start_test and returns the background job record, whose test_id polls GET /api/v1/ems/command-sequences/test?id=<test_id> and stops the run via POST /api/v1/ems/command-sequences/test/stop. Note the asymmetry: the job record's key is test_id, but the stop body's key is id.

Stopping a running test

curl -s -X POST "http://<ems-host>/api/v1/ems/command-sequences/test/stop" \
  -H "Authorization: Bearer <token>" \
  -H "Content-Type: application/json" \
  -d '{"id": "<the id from the start response>"}'

Validating without writing

curl -s -X POST "http://<ems-host>/api/v1/ems/command-sequences/validate" \
  -H "Authorization: Bearer <token>" \
  -H "Content-Type: application/json" \
  -d '{"device_type": "ev_charger", "model": "AC_PRO", "data": {...}}'
stop_test(id)        # command_sequence_test
start_test(device_type, action, model=..., device_key=..., parameters=...)

Monitoring and Results

Both paths return per-step outcomes. The test harness maps engine statuses to operator words:

_STEP_RESULT = {"ok": "PASS", "command": "PASS", "skipped": "SKIPPED",
                "failed": "FAIL", "timeout": "ERROR", "error": "ERROR"}

The overall report is PASS or FAIL, with FAIL when any row is FAIL or ERROR, and the report is stamped with elapsed time.


Error Handling

Exception Raised when
DeviceSequenceError Device-level failure: unknown device, unresolvable model, sequence path missing
PowerSequenceError The underlying engine failed
ProtocolError The protocol adapter is unusable
SequenceTestError Test-level failure
TestNotFound No such test
TestConflict A conflicting test is already running
SequenceStopped The test was cancelled

run_action wraps the engine's error, so a caller sees a device-worded message naming the device label, the model and the action:

<label> [<model>] action '<action>' failed: <detail>

Timeouts and cancellation

  • Timeouts come from the Modbus client (--timeout, default 5.0 s) and from a step's own handling. A timed-out step reports ERROR, not FAIL.
  • Cancellation is supported on the test path: stop_test(id) over REST, or a stop flag in Python. There is no cancellation parameter on run_action itself — a direct run_action call runs to completion or raises. If you need to abort a long physical sequence, drive it through the test path, which is built for that.

Live Device Execution

Physical execution is possible only from Python, and only by opting in explicitly:

  1. Authorization. The authorize_physical flag gates it and is never read from an HTTP body, so a remote caller cannot reach live equipment.
  2. Operation mode. The EMS's operation mode gates clearance actions through gate_reason's allowed_modes.
  3. Communication. client.open() must succeed, and adapter_client must resolve a protocol; otherwise you get cannot open Modbus connection to host:port.
  4. Model validation. run_action proves the device's own layer can serve the model before the first step, so a stale copy fails up front.
  5. Register validation. None. An address in a sequence is not cross-checked against the register map — a wrong address is accepted and written. This is the sharpest edge in the whole system, and it is an implementation gap.
  6. Protection status. For clearance actions, gate_reason refuses while anything else is still active on the device.
  7. Confirmation. verify: true on a step gives read-back confirmation of the write.
  8. Failure handling. failure_action decides whether a failure aborts, skips, retries, or runs a recovery sequence.

Simulator first, always. Not because it is polite, but because the REST path enforces it and the physical path has no register validation to catch a wrong address.


Troubleshooting

Symptom Cause
device_type and action are required Missing field in the REST body
401 unauthorized Missing or bad API token
cannot open Modbus connection to host:port Device or simulator unreachable
<label> [<model>] action '<x>' failed: … The engine failed at a step — read the inner detail
No power sequence file matches … model The model is not defined for that device type
allow_during_backup only applies to the PCS grid-mode actions The flag was used on a non-PCS device
A cleared action does nothing allow_on_clear absent, another alarm still active, or the mode forbids it
A REST request never writes to real equipment By design; the API is simulator-only
Cancelling a direct run_action has no effect No cancellation on that path; use the test path