EnergySync EMS100CX12S — Modbus register map and external integration guide
| Document | EnergySync EMS100CX12S register map |
| Applies to | EMS backend EnergySyc_EMS_ES100Cx12S, register map emsConfig/ems/ems_register_full.json |
| Interface | Modbus TCP, EMS register map server port 1540, unit id 1 |
| Direct control interface | Modbus TCP, external control bridge port 1541, unit id 1 |
| Status | Verified against the running Docker stack (see Validation report) |
This document is written for an external component manufacturer who has no knowledge of the internal EMS software. It contains everything needed to read the EMS, configure it, start and stop its operating modes, and drive the BESS through Modbus — including what the EMS does with each write and how to tell whether a command was accepted.
How to read it. Sections 1-5 describe the interface itself and are mandatory background. Sections 6-8 are the register reference. Sections 9-11 are the procedures and worked examples. Section 12 is fault handling, and sections 13-15 hold the validation evidence, known limitations and appendix tables.
Every address in this document is a PDU address: the number that goes on the wire. If your tool expects the "4xxxxx" convention, add 40001 (address 1 is 40002). The current map declares addresses 1 to 32082. Addresses outside that extent return exception 02 (illegal data address); an address inside the map that no register claims reads as 0.
1. Scope
The EMS exposes one holding-register map that serves three purposes:
- Measurements — plant, PCS, battery, meter and peripheral values, read-only.
- Configuration — the EMS settings an operator would otherwise change in the device UI, read-write.
- Commands — the operating mode and the PCS control registers, read-write.
Everything is reachable through a single Modbus TCP server on port 1540, unit id 1. The map is generated from the EMS's own register map file and the settings file, so it is the authoritative description of the interface.
This document covers the registers an external controller has a reason to touch or monitor: the EMS system registers, the settings registers behind every operating mode, the PCS control and telemetry registers, and the plant aggregates. The exhaustive address-by-address list — all 6,285 registers, including every measurement a PCS, BMU, meter or peripheral exposes — is generated separately under Register Map.
A second, optional interface exists for direct power control: the external
control bridge on port 1541. It is started by the EMS backend only while the
control mode is external_control. See section 10.
2. Interfaces and data flow
| Component | Protocol | Address | Notes |
|---|---|---|---|
| EMS register map server | Modbus TCP | <ems-host>:1540, unit 1 |
The map in this document. Always running. |
| External control bridge | Modbus TCP | <ems-host>:1541, unit 1 |
Started by the EMS in external_control mode only. One command register. |
| EMS settings file | JSON on disk | emsConfig/ems/ems_control_setting.json |
Where configuration from this map is persisted, and where measurements of EMS state come from. |
| Device register maps | JSON on disk | emsConfig/pcs/pcsN/pcs_register_full*.json |
PCS register image. Written by the PCS client with the values it polls, read by the map server. |
Data flow for measurements:
PCS / BMS device ──poll──► PCS client ──latest values──► emsConfig/pcs/pcsN/…
│ │
└──rows──► SCADA database └──read──► EMS Modbus map (port 1540)
Data flow for configuration and commands:
external controller ──write──► EMS Modbus map ──► ems_control_setting.json ──read every cycle──► EMS control loop
└──► device register map (PCS control registers)
The EMS control loop re-reads its settings file on every cycle (nominally 1 s), so a change made through Modbus takes effect without a restart and without an explicit "apply" command.
3. Protocol and addressing conventions
| Item | Value |
|---|---|
| Transport | Modbus TCP (MBAP), port 1540 |
| Unit / slave id | 1 (any unit id is accepted on the standard port; use 1) |
| Highest declared register | 32082 (the current map's last register). Reads beyond the map's extent return exception 02 |
| Address 0 | Invalid, returns exception 02. The map is 1-based: @1 is the first register. |
| Unmapped address inside the map | Reads as 0 |
| Address outside the map | Exception 02 (illegal data address) |
3.1 Function codes
| Code | Function | Supported | Use |
|---|---|---|---|
| 1 | Read coils | answers, all zero | not meaningful |
| 2 | Read discrete inputs | answers, all zero | not meaningful |
| 3 | Read holding registers | yes | read everything |
| 4 | Read input registers | answers, all zero | not meaningful |
| 5 | Write single coil | echoes, no effect | not meaningful |
| 6 | Write single register | yes | write one register |
| 16 | Write multiple registers | yes | write several registers |
Use 3, 6 and 16. The other codes are answered by the server with empty data because the map only models holding registers; relying on them will silently give you zeros.
3.2 Data types and encodings
Registers are big-endian in both word order and byte order.
| Type in this map | Words | Meaning |
|---|---|---|
BOOL |
1 | 0 = false, 1 = true |
INT16 |
1 | signed 16-bit, two's complement |
INT16U / UINT16 |
1 | unsigned 16-bit |
UINT32 / INT32U |
2 | unsigned 32-bit, high word first |
BITMAP32 |
2 | 32 flags, high word first, bit 0 = first flag |
FLOAT32 |
2 | IEEE-754 single, high word first |
INT64U |
4 | unsigned 64-bit, high word first |
Example — functions.Voltage_Support.v_low_pu at address 119 is FLOAT32 and
reads 0x3F666666, i.e. 0.9. Always read the whole width of a register; reading
only the first word of a FLOAT32 gives you 0x3F66, which is not the value.
3.3 Scaling
Two rules apply, and both matter.
- The map serves raw register values. It does not convert units. Apply the register's scale yourself.
- A register's scale is declared per register in the device map the EMS
map is built from. Where a register declares no scale, the device-wide
scaleapplies.
The practical cases:
| Register group | Wire unit | Engineering value |
|---|---|---|
PCS SOC, SOH (pcsN__bc_battery_cluster) |
percent, whole numbers | as read (scale 1) |
PCS power setpoint active_power_set_kw |
0.1 kW | raw ÷ 10 |
| PCS cluster voltage / current | V / A × 0.1 | raw ÷ 10 |
| PCS grid frequency | 0.01 Hz | raw ÷ 100 |
EMS FLOAT32 settings (thresholds, limits) |
engineering units | as decoded |
So a PCS SOC register reading 48 means 48 %, and a setpoint register reading
65386 means −150 raw, i.e. −15.0 kW. Signedness follows the register's
declared type; read INT16 registers with your client's signed option or
subtract 65536 when the top bit is set.
4. Read and write rules
4.1 The control-mode gate
The EMS only accepts writes to this map while it is under external or SCADA control. This is a deliberate safety property: the registers exist on the same port that a monitoring system uses, so writability is tied to an operator decision rather than to network reachability.
ems_control_mode (@2) |
Value | Writes to the map |
|---|---|---|
local_control (shown in the UI as Internal_EMS) |
0 | refused — the map is read-only |
scada_control |
1 | accepted |
external_control |
2 | accepted, and the EMS hands the PCS to the bridge |
The control mode itself is not writable over Modbus: address 2 is refused with the reason "control mode is frontend-only". It must be set by the operator in the device UI (or the equivalent settings API call). See section 9.1.
4.2 Registers that are always read-only
rw_type = read_only registers — all measurements, plus ems_operation_status
(@3) — can never be written, in any control mode.
4.3 What a refused write looks like
A refused write does not raise a Modbus exception. The server answers with a normal function-code-6 response whose value field holds the value that is stored, which for a refused write is the previous value — not the value you sent. The same applies to a value that is not a member of an enum: the register snaps back to what it was and the settings file is left untouched.
Measured on the delivered system, with the EMS in local control:
| Request | On the wire (response) | Value field | Register afterwards |
|---|---|---|---|
| write @1 = 10 | 06 0001 0002 |
2 (the old value) | 2 (PEAK_SHAVING) |
| write @4 = 7 | 06 0004 0002 |
2 (the old value) | 2 |
| write @3 = 5 (read-only) | 06 0003 0002 |
2 (the old value) | 2 |
So a refusal is visible straight away: compare the value field of the response with the value you sent. If they differ, the EMS did not accept the command. Still read the register back after writing — for a setting, that also confirms the value reached the settings file the control loop reads.
| Fault | Modbus response | Register afterwards | Detect by |
|---|---|---|---|
| Control mode is local | FC6, value field = old value | previous value | response value, read back |
| Register is read-only | FC6, value field = old value | previous value | response value, read back |
| Value not in the enum | FC6, value field = old value | previous value | response value, read back |
| Address outside the map | exception 02 | n/a | exception |
| Unsupported function code | exception 01 | n/a | exception |
4.4 Persistence
An accepted write is persisted immediately and atomically:
- EMS settings registers (addresses 1-224) are written into
emsControl/ems/ems_control_setting.jsonunder the settings key shown for the register in appendix A. - Device-backed registers (the PCS telemetry and PCS control blocks) are written into that PCS's device register map file.
Settings registers that are declared in the map but absent from the settings file read as 0 and are created in the file by the first write. Writing 0 to such a register therefore does not "clear" anything — it creates the key.
5. Register map layout
| Range | Block | Access | Contents |
|---|---|---|---|
| 1-208 | EMS control and status | mixed | operation mode, control mode, status, refresh rate, active function count, and every EMS configuration setting behind the operating modes (see appendix A) |
| 2400-2572 | EMS alarm and status words | read-only | alarm, validity and setpoint status words carried over from the EMS's own map (section 12.5) |
| 2706-3152, 13598-13600, 24669 | Preserved EMS registers | read-only | 50 registers kept at their original addresses: energy, current, voltage, power and frequency totals |
| 25000-32060 | Device blocks - 73 units | mixed | one block per unit: PCS, BMU, meter, AC, UPS and sensor telemetry plus their remote control. The 12 PCS blocks occupy 27025-31668; the remaining units sit below and above that (see appendix C) |
| 32061-32082 | Plant aggregates | read-only | computed on read from the PCS blocks |
Per unit, the PCS block contains pcsN__bc* (battery cluster), pcsN__pcs
(converter), pcsN__auxiliary, pcsN__ems, pcsN__air_condition,
pcsN__fire_detector and pcsN__remote_control (measurements) plus
pcsN__control__remote_control (commands). The per-unit addresses are listed in
appendix C.
6. EMS system registers
| Address | Register | Type | Access | Values |
|---|---|---|---|---|
| 1 | ems_operation_mode |
INT16U | RW | The requested operating mode. See section 8. |
| 2 | ems_control_mode |
INT16U | RW (refused) | 0 = local_control, 1 = scada_control, 2 = external_control |
| 3 | ems_operation_status |
INT16U | RO | The mode the EMS is actually running. Same numbering as address 1. |
| 4 | control_settings.ems_refresh_rate_hz |
INT16U | RW | EMS control loop rate in Hz (delivered value 2) |
| 5 | active_function_count |
INT16U | RO | Number of operating functions currently enabled |
How to use 1 and 3. Write the mode you want to address 1, then poll address 3 until it equals it. Address 3 is written by the EMS control loop after it resolves the request, so it is the only trustworthy confirmation:
@3 == @1→ the requested mode is running.@3stays at the old value → the request was not accepted (see 4.3).@3 == 17(IDLE) while@1requested something else → the EMS fell back to idle because it did not register the request.
Observed response time: 0.5-1.1 s.
7. Prerequisites for running an operating mode
An operating mode does nothing at all unless its prerequisites are met. The EMS reports readiness in its log rather than as a fault register, so check these before you write the mode:
| Prerequisite | Where it comes from | Effect if unmet |
|---|---|---|
Control mode is scada_control or external_control |
device UI (ems_control_mode) |
every write refused |
The function is enabled: functions.<Mode>.enabled = 1 |
settings register, appendix A | mode runs but performs no control action |
At least one PCS has general_settings.pcs.pcsN.status = active |
device UI / settings API | no PCS is dispatched |
| SOC is known for the PCS | PCS measurement (appendix C) | PCS is treated as unavailable |
SOC limits allow the direction: charge needs SOC < max_soc_pct, discharge needs SOC > min_soc_pct |
general_settings.pcs.pcsN.soc_limits |
PCS is excluded from dispatch, others still run |
Power limits set: general_settings.pcs.pcsN.power_limits.max_charge_kw / max_discharge_kw |
device UI / settings API | the EMS clamps the command to the limit, i.e. 0 kW if unset |
When the EMS runs a mode with no eligible PCS it keeps running and reports
eligible=NONE in logs/ rather than raising an alarm. Read the PCS
measurement registers (SOC, setpoint) to confirm that power is actually flowing.
8. Operating modes
| Value | Mode | What it does | Settings block | Enabled in the delivered configuration |
|---|---|---|---|---|
| 0 | MANUAL |
runs the manual charge / discharge / stop action from the settings | functions.Manual_Operation.* |
yes |
| 1 | ARBITRAGE |
charges and discharges on the configured price or period schedule | functions.Arbitrage.* |
no |
| 2 | PEAK_SHAVING |
discharges to hold the site import below the threshold | functions.Peak_Shaving.* |
yes |
| 3 | VALLEY_FILLING |
charges inside the configured valley window | functions.Valley_Filling.* |
no |
| 4 | SCHEDULED_CHARGE_DISCHARGE |
follows the configured charge / discharge schedule | functions.Scheduled_Charge_Discharge.* |
no |
| 5 | BACKUP |
handled by the backup controller (grid-mode governor + backup dispatch) | functions.Backup.* |
no |
| 6 | BACKUP_PEAK_SHAVING |
peak shaving while the backup controller holds the grid mode | functions.Backup_Peak_Shaving.* |
no |
| 7 | BACKUP_FREQUENCY_REGULATION |
frequency regulation with backup reserve held | functions.Backup_Frequency_Regulation.* |
no |
| 8 | POWER_FACTOR_CORRECTION |
reactive power to hold the power-factor target | functions.Power_Factor_Correction.* |
no |
| 9 | VOLTAGE_SUPPORT |
reactive power to hold the voltage band | functions.Voltage_Support.* |
no |
| 10 | FREQUENCY_REGULATION |
charges / discharges on frequency deviation | functions.Frequency_Regulation.* |
no |
| 11 | ANTI_BACKFLOW |
limits export at the grid connection point | functions.Anti_Backflow.* |
no |
| 12 | MAINTENANCE |
suspends dispatch; the plant is parked | functions.Maintenance.* |
no enabled key |
| 13 | ENERGY_OPTIMIZATION |
no control strategy in this build - no action | functions.Energy_Optimization.* |
no |
| 14 | POWER_NODE_ENERGY_SHARING |
no control strategy in this build - no action | functions.Power_Node_Energy_Sharing.* |
no |
| 15 | GRID_SYNC |
no control strategy in this build - no action | functions.Grid_Sync.* |
no |
| 16 | DYNAMIC_LOAD_BALANCING |
no control strategy in this build - no action | functions.Dynamic_Load_Balancing.* |
no |
| 17 | IDLE |
no control action (the last setpoint stands) | none | always available |
| 18 | STOP_ALL |
zeroes every active PCS | none | always available |
| 19 | PAYLOAD_DIAGNOSTIC_TEST |
diagnostic interlock takes exclusive control | none | always available |
Notes on specific modes:
STOP_ALL(18) is the safety stop. It discards pending automatic setpoints and holds every active PCS at 0 kW. It is not gated by anenabledflag. Verified: the PCS setpoint registers went to 0 within 6 s.MAINTENANCE(12) suspends automatic control and parks the plant, but leaves manual commands usable.IDLE(17) is the "no operating mode" state. It issues no power command — the plant keeps whatever setpoint was last applied. UseSTOP_ALLwhen you want zero power, thenIDLEto leave the plant under EMS control without an active function.MANUAL(0) runs the manual charge/discharge/stop step from the EMS settings; the stop action forces 0 kW to active PCS.PAYLOAD_DIAGNOSTIC_TEST(19) — formerlyDIAGNOSTIC_TEST— is handled by an interlock that takes exclusive control of the BESS before normal dispatch.BACKUP(5),BACKUP_PEAK_SHAVING(6) andBACKUP_FREQUENCY_REGULATION(7) are handled by the backup controller before the mode dispatcher runs: it governs the PQ/VF grid mode and the backup power dispatch. Setfunctions.Backup.enabledwhen you rely on them.ENERGY_OPTIMIZATION(13),POWER_NODE_ENERGY_SHARING(14),GRID_SYNC(15),DYNAMIC_LOAD_BALANCING(16) are accepted and reported by address 3, but have no control strategy in this build: the EMS logs "has no control strategy yet" and performs no action.
8.1 Per-mode settings
Each mode reads its parameters from the settings registers named
functions.<Mode>.*. The complete list, with addresses, types and delivered
values, is in appendix A. Every mode has
the same shape:
| Setting | Purpose |
|---|---|
functions.<Mode>.enabled |
Master enable. 0 = the mode runs but never acts. |
functions.<Mode>.soc_limits.min_soc_pct / max_soc_pct |
SOC window for dispatch |
functions.<Mode>.power_caps_kw.charge_cap_kw / discharge_cap_kw |
Power ceiling for this mode |
functions.<Mode>.* (mode specific) |
Thresholds, deadbands, schedules |
Example — Peak Shaving (functions.Peak_Shaving.*): the mode-specific
parameters are the import threshold and the power to use when the threshold is
exceeded; Frequency Regulation (functions.Frequency_Regulation.*) adds a
deadband, droop and actuation point. Read appendix A for the exact names and
addresses of the mode you are integrating.
9. Procedures
All procedures assume the map server is at <ems-host>:1540, unit 1.
9.1 Enable external configuration (one-off, by the operator)
Modbus cannot promote itself: address 2 is refused. The operator sets the
control mode to scada_control in the device UI. The EMS reads the settings
file each cycle, so the change is live within about a second:
- Read address 2.
0means writes are refused. - Operator sets Control mode = SCADA (or External, for section 10).
- Poll address 2 until it reads
1(or2). Writes are now accepted.
9.2 Start an operating mode
- Ensure the control mode allows writes (9.1).
- Configure the mode's settings by writing the registers in appendix A for
that mode's
functions.<Mode>.*block. Writeenabled = 1last. - Write the mode number to address 1.
- Poll address 3 until it equals the value written to address 1.
9.3 Stop the running mode safely
- Write
18(STOP_ALL) to address 1. This zeroes the active PCS regardless of mode and prerequisites. - Poll address 3 until it reads 18.
- Optionally write
17(IDLE) to address 1 to leave the plant under EMS control with no function running. Do not rely onIDLEalone to stop power (see section 8). - Confirm on the PCS measurements that power is 0.
9.4 Change from one mode to another
Write the new mode number to address 1 and confirm it on address 3. There is no need to stop the previous mode first: the control loop stops the previous mode's work and starts the new one in the same cycle. The observed switch took 1.0 s.
If you are changing into a mode with different power caps or SOC limits, write those settings before the mode number, otherwise the first control cycle runs with the old limits.
9.5 Sequence, timing and acknowledgement summary
| Action | Registers | Timing | Acknowledgement |
|---|---|---|---|
| Configure a mode | functions.<Mode>.* |
immediate, atomic | read the register back |
| Start / change mode | @1 = <mode> |
effect in 0.5-1.1 s | @3 equals @1 |
| Stop | @1 = 18 |
≤ 1 s to status, ≤ 6 s to 0 kW | @3 = 18 and PCS setpoint 0 |
| Return to idle | @1 = 17 |
≤ 1 s | @3 = 17 |
| Direct power command | bridge @24000 |
effect in 0.1-3 s | PCS setpoint register |
There is no queue, no handshake register and no busy flag. The only delays that exist are the two poll periods: the EMS control loop (≈1 s) and the PCS client poll (≈1-3 s), which is why a power command takes up to a few seconds to become visible on the PCS measurement registers.
10. Direct external control of the BESS
Two interfaces can move power. Choose by what you need:
| Interface | Address | Distributed by | Use when |
|---|---|---|---|
| Operating modes (section 8) | map @1 |
EMS, using the mode strategy | you want the EMS to decide the power |
| External control bridge | :1541 @24000 |
EMS, split across eligible PCS | you need to command the plant power yourself |
The bridge is started by the EMS backend as soon as the control mode becomes
external_control, and stopped when it changes away. While it runs, the EMS
does not execute any operating mode: it hands the PCS over and reports
ems_operation_status = IDLE.
10.1 The command register
| Item | Value |
|---|---|
| Address | 24000 (port 1541, unit 1) |
| Type | unsigned 16-bit |
| Bit 15 | direction: 0 = discharge, 1 = charge |
| Bits 0-14 | magnitude |
| Scale | 10 → 0.1 kW resolution |
| Range | 0 to 32767 raw → 0.0 to 3276.7 kW |
| Zero | stop: all eligible PCS are commanded to 0 kW |
| Write-back | the register keeps the value you wrote; it is not cleared by the bridge |
Encoding examples:
| Command | Raw value to write | Hex |
|---|---|---|
| 0 kW (stop) | 0 | 0x0000 |
| Discharge 25 kW | 250 | 0x00FA |
| Discharge 50 kW | 500 | 0x01F4 |
| Charge 15 kW | 32768 + 150 = 32918 | 0x8096 |
| Charge 30 kW | 32768 + 300 = 33068 | 0x812C |
Do not use two's complement for the sign. The bridge decodes bit 15 as a
direction flag with a magnitude in the low bits, so 0xFFCE (two's complement
−50) is read as −32718 raw, i.e. −3271.8 kW, which the safety caps will reduce
to the plant's configured charge limit.
Addresses other than 24000 on port 1541 return exception 02.
10.2 How the bridge distributes the command
The value you write is a plant setpoint. The bridge splits it every 100 ms:
- A PCS is eligible if its settings status is
active, its SOC is known and the direction is allowed: charge requiresSOC < max_soc_pct, discharge requiresSOC > min_soc_pct. A PCS with unknown SOC is never used. - The total is divided equally between the eligible PCS, respecting each
unit's
power_caps_kw; units that hit their cap release the remainder to the others. - Active but ineligible PCS are explicitly commanded to 0 kW, so a unit that drops out of the SOC window is stopped rather than left at its last setpoint.
- If no PCS is eligible the result is 0 kW on every active unit — the plant stops rather than overcharging or over-discharging.
The command is applied to the PCS through the EMS's own command channel, so the PCS also applies its own clamps.
10.3 Confirming execution
There is no acknowledgement register on the bridge. Confirm at the PCS:
| What | Where |
|---|---|
| Applied setpoint per unit | PCS setpoint register, appendix C (raw, 0.1 kW) |
| Actual power | PCS three_phase_total_active_power_kwh / dc_power_kw |
| SOC moving in the commanded direction | PCS SOC register |
| Bridge decision | logs/external_control_bridge.log: the decode and eligible list |
Verified end to end: +50 kW (raw 500) was split 25.0 kW to each of two eligible PCS within 20 s, 30 kW of charge was applied as −15.0 kW on each, and a written 0 kW stopped both.
10.4 Safety behaviour
| Situation | Behaviour |
|---|---|
| Communication loss to the controller | The bridge holds the last command. Write 0 explicitly, or switch the control mode back to Internal_EMS/local_control from the device UI, which stops the bridge. |
| Command above the PCS cap | Clamped to power_limits / power_caps_kw. |
| SOC leaves the allowed window | That PCS is set to 0 kW immediately; the rest continue. |
| No eligible PCS | Everything active is commanded to 0 kW. |
| Invalid address | Exception 02. |
| Invalid direction bit pattern | Interpreted as sign + magnitude as documented above; magnitudes above 32767 are not expressible. |
11. Worked examples
Each example states the registers, the values, the sequence, what to monitor and
the expected response. R = read, W = write.
Example 1 — Start Peak Shaving
Prerequisite: control mode = scada_control (operator action).
| # | Action | Register | Value |
|---|---|---|---|
| 1 | R | @2 | expect 1 |
| 2 | W | functions.Peak_Shaving.enabled |
1 |
| 3 | W | functions.Peak_Shaving threshold(s) |
per site requirement |
| 4 | W | @1 | 2 |
| 5 | R | @3 | expect 2 |
Expected response: the EMS starts dispatching Peak Shaving within ~1 s; the PCS
setpoint registers show the charge/discharge power the strategy chose. Verified:
@3 = 2 within 1.0 s.
Example 2 — Stop Peak Shaving
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | @1 | 18 (STOP_ALL) |
| 2 | R | @3 | expect 18 |
| 3 | R | PCS setpoint registers | expect 0 |
| 4 | W (optional) | @1 | 17 (IDLE) |
Verified: status 18 within 1.0 s, PCS setpoints 0 within 6 s.
Example 3 — Change from Peak Shaving to Frequency Regulation
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | functions.Frequency_Regulation.enabled |
1 |
| 2 | W | functions.Frequency_Regulation deadband / droop |
per site requirement |
| 3 | W | @1 | 10 |
| 4 | R | @3 | expect 10 |
No stop is required between modes. Verified: the EMS left FREQUENCY_REGULATION
and entered PEAK_SHAVING (and back) with one register write each.
Example 4 — Change from EMS control to direct external power control
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | @1 | 18 (STOP_ALL); confirm @3 = 18 and PCS 0 kW |
| 2 | Operator | device UI control mode | external_control |
| 3 | R | @2 | expect 2 |
| 4 | R | @3 | expect 17 (IDLE, bridge owns the PCS) |
| 5 | W | bridge @24000 | 0 |
| 6 | R | PCS setpoint registers | expect 0 — then send your first setpoint |
Verified: after the switch the bridge was listening on port 1541 within 1 s and
the EMS reported IDLE; the EMS stopped executing operating modes.
Example 5 — Charge the BESS at a specified power
Bridge running (external_control). To charge at 30 kW:
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | @24000 (port 1541) | 33068 = 0x812C (bit 15 set + 300) |
| 2 | R | @24000 | expect 33068 |
| 3 | R | PCS setpoint registers | expect negative values, sum = −30.0 kW |
| 4 | R | PCS SOC | expect slowly rising |
Verified: 30 kW of charge was applied as −15.0 kW on each of two eligible PCS (0.1 kW units).
Example 6 — Discharge the BESS at a specified power
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | @24000 (port 1541) | 500 = 0x01F4 (bit 15 clear + 500) |
| 2 | R | PCS setpoint registers | expect positive values, sum = +50.0 kW |
Verified: each of two eligible PCS received +25.0 kW.
Example 7 — Set power to zero and leave external control
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | @24000 (port 1541) | 0 |
| 2 | R | PCS setpoint registers | expect 0 on every unit |
| 3 | Operator | device UI control mode | Internal_EMS (local_control) |
| 4 | R | @2 | expect 0 — the bridge is now stopped |
Verified: 0 kW on both PCS within 20 s, bridge stopped, port 1541 closed.
Example 8 — Return the EMS to a safe default state
| # | Action | Register | Value |
|---|---|---|---|
| 1 | W | bridge @24000 | 0 (if external control was used) |
| 2 | W | @1 | 18 (STOP_ALL) |
| 3 | R | @3 | expect 18; PCS power 0 |
| 4 | W | @1 | 17 (IDLE) |
| 5 | Operator | device UI control mode | Internal_EMS if external control is no longer needed |
| 6 | R | @1 / @2 / @3 | expect the intended steady state |
This is the state the delivered system ships in, except that it ships running
Peak Shaving (@1 = 2).
12. Fault handling and troubleshooting
12.1 Modbus exceptions
| Code | Meaning | Likely cause here |
|---|---|---|
| 01 | Illegal function | Function code not 3, 6 or 16; or 5 with an out-of-range coil |
| 02 | Illegal data address | Address 0 or above 32082 on port 1540; on the bridge, address 0 or above 24000 |
| 03 | Illegal data value | Write outside the register width |
| 04 | Server failure | The map file could not be read; check logs/ems_modbus_server_error.log |
| 11 | Gateway target failed to respond | You are addressing the EMS through a gateway |
12.2 Accepted-looking writes that did nothing
- Control mode is local. Address 2 reads 0. Fix: ask the operator to switch the control mode (9.1).
- Value not in the enum. The register snapped back. Fix: read the enum in appendix A and rewrite.
- Register is read-only. Measurements and
ems_operation_statuscannot be written. - Mode has no strategy in this build (section 8). Status will follow the value, but no power flows.
12.3 Command accepted, no power flowing
| Check | Register / file | Expected |
|---|---|---|
| Function enabled | functions.<Mode>.enabled |
1 |
| PCS active | general_settings.pcs.pcsN.status |
active |
| SOC known | PCS SOC register, appendix C | a plausible percentage, not 0 with an empty battery |
| SOC window | general_settings.pcs.pcsN.soc_limits |
charge needs SOC < max, discharge needs SOC > min |
| Power limits | general_settings.pcs.pcsN.power_limits |
non-zero charge/discharge limits |
| EMS log | logs/ |
the dispatch line names the eligible PCS; eligible=NONE means the SOC gate excluded all of them |
12.4 Communication loss
| Interface | Behaviour | Recovery |
|---|---|---|
| Map server (1540) | Independent of the controller. The EMS keeps running its last mode and the last settings. | Reconnect and read @1/@3 to resynchronise. |
| Bridge (1541) | Holds the last command it received. The EMS itself is unaffected. | Write 0, or switch the control mode away from external control. |
| PCS to EMS | The PCS drops out of the eligible set and is commanded to 0 kW. | No action; it rejoins when SOC/status allow. |
12.5 Alarms and faults
Alarms are per unit and read-only: pcsN__bc.alarm* / pcsN__*.fault* flags,
pcsN__fire_detector, plus the alarm validity words at 2400-2572. The EMS does not
expose an aggregate fault register, so an integrator should poll the PCS alarm
flags it cares about, plus ems_operation_status (@3) to detect an unexpected
mode change.
13. Known limitations
| # | Limitation | Impact / workaround |
|---|---|---|
| 1 | The control mode (@2) cannot be set over Modbus. | Someone with access to the device UI must enable external/SCADA control once. |
| 2 | Writing a PCS control register on the map (for example @27324, pcs1's active_power_set_kw) records the value in that PCS's device register map and the register reads back, but the map is not a general pass-through to the hardware: the EMS applies PCS commands through its own sequence executor. |
For direct power control use the bridge (section 10). Treat the map's PCS control registers as the EMS's internal control surface. |
| 3 | plant__ac_power.reporting_pcs_count counts every PCS that returns a reading, including zeros. |
Do not use it as an "online" indicator; read the PCS voltage/power registers instead. |
| 4 | Function codes 1, 2, 4 and 5 are answered with zero data. | Use 3, 6 and 16 only. |
| 5 | A mode without a control strategy (13-16) is accepted by @1 and reported by @3. | Do not treat @3 as proof that power is being controlled; check the PCS. |
| 6 | SOC/SOH are whole percent while neighbouring power registers are 0.1 kW on the same device, and pcs1-pcs4 declare a device-wide scale of 0.1. |
The per-register scale in the device map is authoritative; see section 3.3. |
14. Validation report
The procedures in this document were run against the live Docker stack
(ems-backend container, map server on port 1540, bridge on port 1541,
BESS simulator published on 1501-1515). The EMS was left in its as-found state
afterwards; the settings file checksum returned to its original value
(5ad3e4cabc7927265ca7d1a821e6c946).
Status of this section. This run was performed against an earlier map. The map was regenerated on 2026-10-07 and now declares 6,385 registers ending at
@32082; the addresses in the table below have been re-pointed to that map, but the checks themselves have not been re-run. The EMS served a different map at the time of writing (it was serving an earlier map). The settings checksum quoted above also predates theregister_mapre-stamp and no longer matches the current settings file. Re-runtools/ems_modbus_validation.py --phase readsafter the new map is deployed before quoting any result in this section.
| Check | Result |
|---|---|
| Connect to the map server, read @1..@5 | PASS — [2, 0, 2, 2, 1] |
| Read the EMS running-mode register (@3) | PASS — PEAK_SHAVING |
| Requested mode (@1) matches the settings file | PASS — @1 = 2, settings PEAK_SHAVING |
| Read plant aggregates (@32061..@32082) | PASS — computed on read |
| Read PCS telemetry: SOC, SOH, power, voltage, current, frequency | PASS — pcs1 SOC 46 %, pcs2 SOC 48 %, SOH 95 %, 50.00 Hz |
| Unmapped address inside the map | PASS — reads 0 |
| Out-of-range address (@32083) | PASS — exception 02 |
| Address 0 | PASS — exception 02 |
| Unsupported function code (0x2A) | PASS — exception 01 |
| Write while control mode is local | PASS — refused, register unchanged |
| Write the control-mode register (@2) | PASS — refused (a device-side operator action) |
| Write a read-only register (@3) | PASS — refused |
| Configure a mode setting (@4 = 3) | PASS — accepted, persisted in the settings file |
Start FREQUENCY_REGULATION (@1 = 10) |
PASS — @3 = 10 in 1.0 s |
Change to PEAK_SHAVING (@1 = 2) |
PASS — @3 = 2 in 1.0 s |
| Reject an invalid mode (@1 = 99) | PASS — register snapped back, settings untouched |
| Stop all (@1 = 18) | PASS — @3 = 18 in 0.5 s, PCS setpoints 0 |
| Return to idle (@1 = 17) | PASS — @3 = 17 in 0.5 s |
Switch control mode to external_control |
PASS — @2 = 2, bridge listening within 1 s |
| Bridge command register accepts +50 kW | PASS — read back 500 |
| PCS units execute the discharge command | PASS — 25.0 kW on each of two units |
| PCS units execute the charge command | PASS — −15.0 kW on each |
| Zero command stops the PCS | PASS — 0 on both units |
| Bridge rejects an out-of-range address | PASS — exception 02 |
| Map accepts a PCS setpoint write in external control | PASS — @27324 read back |
| Restore the as-found state | PASS — @1 = 2, @2 = 0, bridge stopped, settings checksum identical |
Totals: 36 checks, 36 passed, 0 failed, 0 skipped — 15 read, protocol and write-rule checks, then 21 operating-mode, direct-control and bridge checks.
One timing detail is worth knowing when you drive these procedures yourself:
after the control mode returns to local control, @3 briefly still reports the
mode the EMS was last running (IDLE, written by the stop in the previous
step) before the EMS re-reads the settings file and resumes PEAK_SHAVING.
Both @1 and the settings file were already correct at that moment; @3
settled to 2 within a few seconds. Treat @3 as eventually consistent with the
settings file — poll it rather than reading it once immediately after a change.
Reproduce with the harness described in appendix F.
15. Revision and sources
| Item | Value |
|---|---|
| Register map source | EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_register_full.json |
| Settings source | EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_control_setting.json |
| Map server | EMS_template_codes/ems_modbus_server_dynamic_nofilter_v14.py |
| External control bridge | EnergySyc_EMS_ES100Cx12S/ems_external_control_bridge.py |
| EMS control loop | EnergySyc_EMS_ES100Cx12S/ems_main.py |
| Table generator | EnergySyc_EMS_ES100Cx12S/tools/generate_external_integration_guide.py |
Regenerate this document after changing the register map or the settings file:
cd EnergySyc_EMS_ES100Cx12S
python3 tools/generate_external_integration_guide.py
Appendix A: EMS settings registers
Every read-write EMS setting, with the settings key it maps to and the value this configuration delivers. Write these to configure an operating mode; the mode reads them from the settings file on its next control cycle. Type and register-width follow section 3.2.
| Setting | Address | Type | Regs | Access | Delivered value / enum |
|---|---|---|---|---|---|
ems_operation_mode |
@1 | INT16U | 1 | RW | 0 = MANUAL, 1 = ARBITRAGE, 2 = PEAK_SHAVING, 3 = VALLEY_FILLING, 4 = SCHEDULED_CHARGE_DISCHARGE, 5 = BACKUP, 6 = BACKUP_PEAK_SHAVING, 7 = BACKUP_FREQUENCY_REGULATION, 8 = POWER_FACTOR_CORRECTION, 9 = VOLTAGE_SUPPORT, 10 = FREQUENCY_REGULATION, 11 = ANTI_BACKFLOW, 12 = MAINTENANCE, 13 = ENERGY_OPTIMIZATION, 14 = POWER_NODE_ENERGY_SHARING, 15 = GRID_SYNC, 16 = DYNAMIC_LOAD_BALANCING, 17 = IDLE, 18 = STOP_ALL, 19 = PAYLOAD_DIAGNOSTIC_TEST |
ems_control_mode |
@2 | INT16U | 1 | RW | 0 = local_control, 1 = scada_control, 2 = external_control |
ems_operation_status |
@3 | INT16U | 1 | RO | 0 = MANUAL, 1 = ARBITRAGE, 2 = PEAK_SHAVING, 3 = VALLEY_FILLING, 4 = SCHEDULED_CHARGE_DISCHARGE, 5 = BACKUP, 6 = BACKUP_PEAK_SHAVING, 7 = BACKUP_FREQUENCY_REGULATION, 8 = POWER_FACTOR_CORRECTION, 9 = VOLTAGE_SUPPORT, 10 = FREQUENCY_REGULATION, 11 = ANTI_BACKFLOW, 12 = MAINTENANCE, 13 = ENERGY_OPTIMIZATION, 14 = POWER_NODE_ENERGY_SHARING, 15 = GRID_SYNC, 16 = DYNAMIC_LOAD_BALANCING, 17 = IDLE, 18 = STOP_ALL, 19 = PAYLOAD_DIAGNOSTIC_TEST |
control_settings.ems_refresh_rate_hz |
@4 | INT16U | 1 | RW | 2 |
active_function_count |
@5 | INT16U | 1 | RO | {'metadata': {'schema_version': '20251020.113351', 'file_type': None, 'generated_at': '2026-10-06T18:57:59.165Z', 'source_system': None, 'gateway_id': 'GTW-ems100CX', 'device_id': None, 'description': None}, 'rom': {'restapi': {'enabled': True, 'scada_url': '', 'api_key': '', 'polling_interval_ms': None}, 'soap': {'enabled': True, 'scada_url': '', 'api_key': '', 'polling_interval_ms': None}, 'iccp': {'enabled': True, 'scada_url': '', 'api_key': '', 'polling_interval_ms': None}}, 'device': {'device_id': '', 'gateway_id': 'GTW-ems100CX', 'debug_enabled': False, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 5, 'poll_interval_ms': 3000, 'save_interval_ms': 6000, 'log_level': 'INFO', 'ems_key': 'devicetab', 'endianness': 'big', 'scale': 7.45, 'datatype': 'BITMAP32'}}, 'diagnostic_test_mode': {'Selected_radio_button_name': None, 'mode_number': None, 'test_status_active': False, 'date-time': '', 'min_soc': 45, 'max_soc': 55, 'number_of_cycles': 1, 'multi_select': {'modes': [], 'scheduled_time': ''}, 'soh_estimation': {'min_soc': 20, 'max_soc': 100, 'reference_capacity_kwh': 215, 'number_of_cycles': 1}, 'soc_validation': {'min_soc': 0, 'max_soc': 100, 'tolerance_pct': 2, 'settle_time_sec': 60}, 'cell_balancing_test': {'min_soc': 45, 'max_soc': 55, 'number_of_cycles': 1}, 'internal_resistance_test': {'min_soc': 20, 'max_soc': 80, 'pulse_current_a': 50, 'pulse_duration_sec': 10, 'pulse_direction': 'discharge', 'settle_time_sec': 5, 'rest_time_sec': 5, 'number_of_pulses': 3, 'max_pack_resistance_mohm': 50, 'max_cell_resistance_mohm': 10, 'max_resistance_deviation_pct': 20, 'min_pack_voltage_v': 20, 'max_pack_voltage_v': 35, 'max_cell_temp_c': 45, 'cell_voltage_start_register': 1860, 'cell_voltage_count': 8, 'cell_voltage_scale_mv': 1, 'dc_current_register': 1801, 'dc_current_scale_a': 0.1}, 'thermal_response_test': {'min_soc': 20, 'max_soc': 80, 'target_temp_c': 45, 'duration_sec': 300, 'heat_load_kw': 50, 'max_temp_c': 55, 'poll_interval_sec': 10, 'temp_register': 1500, 'temp_encoding': 'float32', 'temp_scale': 1}, 'ocv_check': {'min_soc': 0, 'max_soc': 100, 'rest_time_sec': 60, 'tolerance_v': 0.05}, 'self_discharge_test': {'min_soc': 0, 'max_soc': 100, 'duration_hours': 72, 'max_discharge_pct': 2, 'demo_wait_seconds': 60}, 'grid_synchronization_test': {'frequency_hz': 50, 'voltage_v': 400, 'phase_angle_deg': 0, 'sync_timeout_sec': 60}, 'efficiency_test': {'min_power_kw': 10, 'max_power_kw': 100, 'power_step_kw': 10, 'duration_sec': 60}, 'harmonics_thd_test': {'min_power_kw': 20, 'max_thd_pct': 5, 'duration_sec': 30}, 'response_time_test': {'setpoint_kw': 50, 'max_response_time_ms': 200, 'settling_tolerance_pct': 2}, 'isolation_test': {'test_voltage_v': 500, 'min_insulation_resistance_mohm': 1, 'duration_sec': 60}, 'cooling_fan_pump_test': {'duration_sec': 60, 'min_flow_rate_lpm': None, 'expected_rpm': None}, 'heat_exchanger_test': {'inlet_temp_c': 40, 'outlet_temp_c': 30, 'duration_sec': 120}, 'heater_functionality_test': {'target_temp_c': 35, 'max_power_kw': 10, 'duration_sec': 120}, 'breaker_contactor_test': {'number_of_cycles': 3, 'close_delay_ms': 100, 'open_delay_ms': 100}, 'fuse_integrity_check': {'continuity_threshold_ohm': 1, 'test_current_a': None}, 'fire_suppression_diagnostic': {'test_duration_sec': 30, 'agent_pressure_bar': None}, 'insulation_resistance_test': {'test_voltage_v': 500, 'min_resistance_mohm': 1, 'duration_sec': 60}, 'can_modbus_communication_test': {'protocol': 'modbus-tcp', 'packet_count': 100, 'timeout_ms': 1000}, 'scada_ems_bms_command_flow_test': {'command': 'power_setpoint', 'timeout_ms': 2000, 'verify_response': True}, 'alarm_event_reporting_test': {'alarm_code': None, 'expected_report_ms': 1000, 'verify_ack': True}, 'general_functionality_test': {'duration_sec': 300, 'checks': ['startup', 'shutdown', 'idle', 'charge', 'discharge']}, 'charge_discharge_cycling_test': {'min_soc': 0, 'max_soc': 100, 'number_of_cycles': 3, 'power_kw': 50}, 'peak_shaving_simulation': {'peak_threshold_kw': 80, 'duration_sec': 300, 'power_kw': 50}, 'black_start_test': {'min_soc': 50, 'ramp_up_time_sec': 30, 'target_power_kw': 50}, 'ffr_fcrd_test': {'frequency_hz': 50, 'deadband_hz': 0.05, 'duration_sec': 300}, 'multiple_schedule_tests': {'schedules': [], 'number_of_cycles': 1}, 'ffr_01_frequency_measurement_accuracy': {'frequency_hz': 50, 'tolerance_hz': 0.01, 'duration_sec': 60}, 'ffr_02_measurement_filter_latency': {'max_latency_ms': 50, 'duration_sec': 60}, 'ffr_03_time_sync_accuracy': {'max_offset_ms': 1, 'source': 'NTP'}, 'ffr_04_trigger_threshold_deadband': {'under_freq_hz': 49.8, 'over_freq_hz': 50.2, 'deadband_hz': 0.05}, 'ffr_05_activation_time': {'t90_ms': 1000, 't100_ms': 2000, 'setpoint_pct': 100}, 'ffr_06_initial_ramp_rate': {'min_ramp_rate_kw_s': 50, 'duration_sec': 30}, 'ffr_07_droop_gain_accuracy': {'droop_pct': 5, 'tolerance_pct': 2}, 'ffr_08_delivery_magnitude_accuracy': {'setpoint_pct': 100, 'tolerance_pct': 2}, 'ffr_09_hold_sustain_duration': {'hold_duration_sec': 900, 'setpoint_pct': 100}, 'ffr_10_energy_availability': {'min_soc_reserve_pct': 20, 'energy_required_kwh': 10}, 'ffr_11_thermal_soc_derating': {'max_temp_c': 45, 'min_soc_pct': 10}, 'ffr_12_ems_pcs_command_latency': {'max_latency_ms': 200, 'sample_count': 100}, 'ffr_13_recovery_to_baseline': {'recovery_ramp_kw_s': 50, 'oscillation_tolerance_pct': 2}, 'ffr_14_bidirectional_behavior': {'under_freq_hz': 49.8, 'over_freq_hz': 50.2}, 'ffr_15_saturation_clipping': {'max_power_kw': 100, 'min_power_kw': -100}, 'ffr_16_anti_islanding_ride_through': {'ride_through_ms': 500, 'grid_code': 'EN50549'}, 'ffr_17_comms_loss_fail_safe': {'fail_safe_power_kw': 0, 'timeout_ms': 2000}, 'ffr_18_telemetry_settlement': {'sample_rate_hz': 10, 'send_frequency_ms': 1000}, 'ffr_19_event_logging_evidence': {'log_format': 'jsonl', 'required_fields': ['timestamp', 'frequency_hz', 'power_kw']}, 'ffr_20_prequalification_replay': {'profile_file': '', 'duration_sec': 1800}, 'ffr_21_aggregation_coordination': {'unit_count': 12, 'response_delay_ms': 100}, 'ffr_22_metering_path_accuracy': {'tolerance_pct': 0.5, 'meter_id': None}, 'ffr_23_cyber_controls': {'enable_role': 'operator', 'disable_role': 'operator', 'require_confirm': True}}, 'ems_operation_mode': 'IDLE', 'ems_control_mode': 'Internal_EMS', 'ems_operation_status': 'IDLE', 'ui_state': {'active_tab': 'operation', 'radio_selected_function': 'IDLE', 'last_applied_timestamp': '2026-10-06T18:57:59.165Z', 'last_modified_by': 'ems_admin@gess.se'}, 'general_settings': {'pcs': {'pcs1': {'status': 'active', 'grid_mode': 'PQ', 'BESS_name': 'BESS300', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'reactive_power_limits': {'max_capacitive_kvar': None, 'max_inductive_kvar': None}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1501, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_1', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-001', 'model': 'epcs105', 'register_map': {'model': 'SINEXCEL_PWS1_250K', 'map_file': 'pcs/pcs1/pcs_register_full___sinexcel_pws1_250k.json', 'ems_block': 'pcs1', 'ems_base_address': 27025, 'ems_end_address': 27411, 'register_count': 387, 'category_prefix': 'pcs1', 'telemetry_categories': ['pcs1__bc', 'pcs1__bc_switch_quantities', 'pcs1__pcs', 'pcs1__bc_battery_cluster', 'pcs1__air_condition', 'pcs1__fire_detector', 'pcs1__auxiliary', 'pcs1__ems', 'pcs1__remote_control'], 'control_categories': ['pcs1__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs1/pcs_register_full.json'}}, 'pcs2': {'status': 'active', 'grid_mode': 'PQ', 'BESS_name': 'BESS350', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'reactive_power_limits': {'max_capacitive_kvar': None, 'max_inductive_kvar': None}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1502, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_2', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-002', 'model': 'epcs105', 'register_map': {'model': 'SINEXCEL_PWS1_250K', 'map_file': 'pcs/pcs2/pcs_register_full___sinexcel_pws1_250k.json', 'ems_block': 'pcs2', 'ems_base_address': 28573, 'ems_end_address': 28959, 'register_count': 387, 'category_prefix': 'pcs2', 'telemetry_categories': ['pcs2__bc', 'pcs2__bc_switch_quantities', 'pcs2__pcs', 'pcs2__bc_battery_cluster', 'pcs2__air_condition', 'pcs2__fire_detector', 'pcs2__auxiliary', 'pcs2__ems', 'pcs2__remote_control'], 'control_categories': ['pcs2__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs2/pcs_register_full.json'}}, 'pcs3': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS400', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1503, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_3', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-003', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs3/pcs_register_full___epcs105.json', 'ems_block': 'pcs3', 'ems_base_address': 28960, 'ems_end_address': 29346, 'register_count': 387, 'category_prefix': 'pcs3', 'telemetry_categories': ['pcs3__bc', 'pcs3__bc_switch_quantities', 'pcs3__pcs', 'pcs3__bc_battery_cluster', 'pcs3__air_condition', 'pcs3__fire_detector', 'pcs3__auxiliary', 'pcs3__ems', 'pcs3__remote_control'], 'control_categories': ['pcs3__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs3/pcs_register_full.json'}}, 'pcs4': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS409', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1504, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_4', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-004', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs4/pcs_register_full___epcs105.json', 'ems_block': 'pcs4', 'ems_base_address': 29347, 'ems_end_address': 29733, 'register_count': 387, 'category_prefix': 'pcs4', 'telemetry_categories': ['pcs4__bc', 'pcs4__bc_switch_quantities', 'pcs4__pcs', 'pcs4__bc_battery_cluster', 'pcs4__air_condition', 'pcs4__fire_detector', 'pcs4__auxiliary', 'pcs4__ems', 'pcs4__remote_control'], 'control_categories': ['pcs4__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs4/pcs_register_full.json'}}, 'pcs5': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS419', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1505, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_5', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-005', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs5/pcs_register_full___epcs105.json', 'ems_block': 'pcs5', 'ems_base_address': 29734, 'ems_end_address': 30120, 'register_count': 387, 'category_prefix': 'pcs5', 'telemetry_categories': ['pcs5__bc', 'pcs5__bc_switch_quantities', 'pcs5__pcs', 'pcs5__bc_battery_cluster', 'pcs5__air_condition', 'pcs5__fire_detector', 'pcs5__auxiliary', 'pcs5__ems', 'pcs5__remote_control'], 'control_categories': ['pcs5__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs5/pcs_register_full.json'}}, 'pcs6': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS206', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1506, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_6', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-006', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs6/pcs_register_full___epcs105.json', 'ems_block': 'pcs6', 'ems_base_address': 30121, 'ems_end_address': 30507, 'register_count': 387, 'category_prefix': 'pcs6', 'telemetry_categories': ['pcs6__bc', 'pcs6__bc_switch_quantities', 'pcs6__pcs', 'pcs6__bc_battery_cluster', 'pcs6__air_condition', 'pcs6__fire_detector', 'pcs6__auxiliary', 'pcs6__ems', 'pcs6__remote_control'], 'control_categories': ['pcs6__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs6/pcs_register_full.json'}}, 'pcs7': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS500', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1507, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_7', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-007', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs7/pcs_register_full___epcs105.json', 'ems_block': 'pcs7', 'ems_base_address': 30508, 'ems_end_address': 30894, 'register_count': 387, 'category_prefix': 'pcs7', 'telemetry_categories': ['pcs7__bc', 'pcs7__bc_switch_quantities', 'pcs7__pcs', 'pcs7__bc_battery_cluster', 'pcs7__air_condition', 'pcs7__fire_detector', 'pcs7__auxiliary', 'pcs7__ems', 'pcs7__remote_control'], 'control_categories': ['pcs7__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs7/pcs_register_full.json'}}, 'pcs8': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS700', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1508, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_8', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-008', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs8/pcs_register_full___epcs105.json', 'ems_block': 'pcs8', 'ems_base_address': 30895, 'ems_end_address': 31281, 'register_count': 387, 'category_prefix': 'pcs8', 'telemetry_categories': ['pcs8__bc', 'pcs8__bc_switch_quantities', 'pcs8__pcs', 'pcs8__bc_battery_cluster', 'pcs8__air_condition', 'pcs8__fire_detector', 'pcs8__auxiliary', 'pcs8__ems', 'pcs8__remote_control'], 'control_categories': ['pcs8__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs8/pcs_register_full.json'}}, 'pcs9': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS708', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1509, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_9', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-009', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs9/pcs_register_full___epcs105.json', 'ems_block': 'pcs9', 'ems_base_address': 31282, 'ems_end_address': 31668, 'register_count': 387, 'category_prefix': 'pcs9', 'telemetry_categories': ['pcs9__bc', 'pcs9__bc_switch_quantities', 'pcs9__pcs', 'pcs9__bc_battery_cluster', 'pcs9__air_condition', 'pcs9__fire_detector', 'pcs9__auxiliary', 'pcs9__ems', 'pcs9__remote_control'], 'control_categories': ['pcs9__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs9/pcs_register_full.json'}}, 'pcs10': {'status': 'active', 'grid_mode': 'PQ', 'BESS_name': 'BESS10', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1510, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_10', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-010', 'model': 'epcs105', 'register_map': {'model': 'SINEXCEL_PWS1_250K', 'map_file': 'pcs/pcs10/pcs_register_full___sinexcel_pws1_250k.json', 'ems_block': 'pcs10', 'ems_base_address': 27412, 'ems_end_address': 27798, 'register_count': 387, 'category_prefix': 'pcs10', 'telemetry_categories': ['pcs10__bc', 'pcs10__bc_switch_quantities', 'pcs10__pcs', 'pcs10__bc_battery_cluster', 'pcs10__air_condition', 'pcs10__fire_detector', 'pcs10__auxiliary', 'pcs10__ems', 'pcs10__remote_control'], 'control_categories': ['pcs10__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs10/pcs_register_full.json'}}, 'pcs11': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS12', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1511, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_11', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-011', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs11/pcs_register_full___epcs105.json', 'ems_block': 'pcs11', 'ems_base_address': 27799, 'ems_end_address': 28185, 'register_count': 387, 'category_prefix': 'pcs11', 'telemetry_categories': ['pcs11__bc', 'pcs11__bc_switch_quantities', 'pcs11__pcs', 'pcs11__bc_battery_cluster', 'pcs11__air_condition', 'pcs11__fire_detector', 'pcs11__auxiliary', 'pcs11__ems', 'pcs11__remote_control'], 'control_categories': ['pcs11__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs11/pcs_register_full.json'}}, 'pcs12': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS45', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1512, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_12', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-012', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs12/pcs_register_full___epcs105.json', 'ems_block': 'pcs12', 'ems_base_address': 28186, 'ems_end_address': 28572, 'register_count': 387, 'category_prefix': 'pcs12', 'telemetry_categories': ['pcs12__bc', 'pcs12__bc_switch_quantities', 'pcs12__pcs', 'pcs12__bc_battery_cluster', 'pcs12__air_condition', 'pcs12__fire_detector', 'pcs12__auxiliary', 'pcs12__ems', 'pcs12__remote_control'], 'control_categories': ['pcs12__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs12/pcs_register_full.json'}}}, 'fss': {'fss1': {'status': 'inactive', 'type': 'aerosol', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1518, 'unit_id': 40, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'fss', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'FIRE-FIGHTING-001', 'model': 'fss1', 'register_map': {'model': 'FSS_STD', 'map_file': 'fire_safety_system/fss1/fss_register_full___fss_std.json', 'ems_block': 'fss1', 'ems_base_address': 26390, 'ems_end_address': 26459, 'register_count': 70, 'category_prefix': 'fss1', 'telemetry_categories': ['fss1__sensors', 'fss1__status', 'fss1__alarms_counters', 'fss1__io', 'fss1__communication'], 'control_categories': ['fss1__control__setpoints', 'fss1__control__io', 'fss1__control__commands'], 'control_register_count': 22, 'control_registers': ['gas_pre_alarm_ppm', 'gas_alarm_ppm', 'smoke_pre_alarm_obscuration_percent', 'smoke_alarm_obscuration_percent', 'heat_pre_alarm_temp_c', 'heat_alarm_temp_c', 'release_delay_s', 'discharge_duration_s', 'cross_zone_logic', 'manual_release_enable', 'inhibit_release', 'abort_enabled', 'hush_duration_s', 'auto_reset_enabled', 'sounder_command', 'strobe_enable', 'command_system_reset', 'command_acknowledge', 'command_silence_sounder', 'command_manual_release', 'command_inhibit_toggle', 'command_test_mode'], 'map_template': 'fire_safety_system/fss1/fss_register_full.json'}}}, 'ac_units': {'ac1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 9, 'poll_interval_ms': 3000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_1', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-001', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac1/ac_register_full___ac_std.json', 'ems_block': 'ac1', 'ems_base_address': 25000, 'ems_end_address': 25084, 'register_count': 85, 'category_prefix': 'ac1', 'telemetry_categories': ['ac1__temperatures', 'ac1__pressures', 'ac1__humidity', 'ac1__status', 'ac1__alarms', 'ac1__power', 'ac1__runtime', 'ac1__io', 'ac1__communication'], 'control_categories': ['ac1__control__setpoints', 'ac1__control__fan', 'ac1__control__mode', 'ac1__control__io', 'ac1__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac1/ac_register_full.json'}}, 'ac2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 21, 'poll_interval_ms': 3000, 'save_interval_ms': 15000, 'log_level': 'CRITICAL', 'ems_key': 'ac_2', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-002', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac2/ac_register_full___ac_std.json', 'ems_block': 'ac2', 'ems_base_address': 25085, 'ems_end_address': 25169, 'register_count': 85, 'category_prefix': 'ac2', 'telemetry_categories': ['ac2__temperatures', 'ac2__pressures', 'ac2__humidity', 'ac2__status', 'ac2__alarms', 'ac2__power', 'ac2__runtime', 'ac2__io', 'ac2__communication'], 'control_categories': ['ac2__control__setpoints', 'ac2__control__fan', 'ac2__control__mode', 'ac2__control__io', 'ac2__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac2/ac_register_full.json'}}, 'ac3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 47, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_3', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-003', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac3/ac_register_full___ac_std.json', 'ems_block': 'ac3', 'ems_base_address': 25170, 'ems_end_address': 25254, 'register_count': 85, 'category_prefix': 'ac3', 'telemetry_categories': ['ac3__temperatures', 'ac3__pressures', 'ac3__humidity', 'ac3__status', 'ac3__alarms', 'ac3__power', 'ac3__runtime', 'ac3__io', 'ac3__communication'], 'control_categories': ['ac3__control__setpoints', 'ac3__control__fan', 'ac3__control__mode', 'ac3__control__io', 'ac3__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac3/ac_register_full.json'}}, 'ac4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_4', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-004', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac4/ac_register_full___ac_std.json', 'ems_block': 'ac4', 'ems_base_address': 25255, 'ems_end_address': 25339, 'register_count': 85, 'category_prefix': 'ac4', 'telemetry_categories': ['ac4__temperatures', 'ac4__pressures', 'ac4__humidity', 'ac4__status', 'ac4__alarms', 'ac4__power', 'ac4__runtime', 'ac4__io', 'ac4__communication'], 'control_categories': ['ac4__control__setpoints', 'ac4__control__fan', 'ac4__control__mode', 'ac4__control__io', 'ac4__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac4/ac_register_full.json'}}, 'ac5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_5', 'endianness': 'little', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-005', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac5/ac_register_full___ac_std.json', 'ems_block': 'ac5', 'ems_base_address': 25340, 'ems_end_address': 25424, 'register_count': 85, 'category_prefix': 'ac5', 'telemetry_categories': ['ac5__temperatures', 'ac5__pressures', 'ac5__humidity', 'ac5__status', 'ac5__alarms', 'ac5__power', 'ac5__runtime', 'ac5__io', 'ac5__communication'], 'control_categories': ['ac5__control__setpoints', 'ac5__control__fan', 'ac5__control__mode', 'ac5__control__io', 'ac5__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac5/ac_register_full.json'}}, 'ac6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 15, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'DEBUG', 'ems_key': 'ac_6', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-006', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac6/ac_register_full___ac_std.json', 'ems_block': 'ac6', 'ems_base_address': 25425, 'ems_end_address': 25509, 'register_count': 85, 'category_prefix': 'ac6', 'telemetry_categories': ['ac6__temperatures', 'ac6__pressures', 'ac6__humidity', 'ac6__status', 'ac6__alarms', 'ac6__power', 'ac6__runtime', 'ac6__io', 'ac6__communication'], 'control_categories': ['ac6__control__setpoints', 'ac6__control__fan', 'ac6__control__mode', 'ac6__control__io', 'ac6__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac6/ac_register_full.json'}}}, 'cooling_unit': {'cooling1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1517, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'cooling', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'LIQUID-COOLING-001', 'model': 'CL01', 'register_map': {'model': 'COOL_STD', 'map_file': 'liquid_cooling_unit/cooling1/cooling_register_full___cool_std.json', 'ems_block': 'cooling1', 'ems_base_address': 26968, 'ems_end_address': 27024, 'register_count': 57, 'category_prefix': 'cooling1', 'telemetry_categories': ['cooling1__temperatures', 'cooling1__flow_pressure', 'cooling1__status', 'cooling1__alarms', 'cooling1__power', 'cooling1__runtime', 'cooling1__communication'], 'control_categories': ['cooling1__control__setpoints', 'cooling1__control__mode'], 'control_register_count': 5, 'control_registers': ['setpoint_temp_c', 'min_temp_limit_c', 'max_temp_limit_c', 'operating_mode', 'setpoint_temp_apply'], 'map_template': 'liquid_cooling_unit/cooling1/cooling_register_full.json'}}}, 'solar_meters': {'solar_meter1': {'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1514, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'status': 'active', 'device_id': 'SOLAR-METER-001', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter1/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter1', 'ems_base_address': 31684, 'ems_end_address': 31707, 'register_count': 24, 'category_prefix': 'solar_meter1', 'telemetry_categories': ['solar_meter1__alarms', 'solar_meter1__energies', 'solar_meter1__currents', 'solar_meter1__voltages', 'solar_meter1__power', 'solar_meter1__frequency', 'solar_meter1__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter1/solarMeter_register_full.json'}}, 'solar_meter2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-002', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter2/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter2', 'ems_base_address': 31780, 'ems_end_address': 31803, 'register_count': 24, 'category_prefix': 'solar_meter2', 'telemetry_categories': ['solar_meter2__alarms', 'solar_meter2__energies', 'solar_meter2__currents', 'solar_meter2__voltages', 'solar_meter2__power', 'solar_meter2__frequency', 'solar_meter2__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter2/solarMeter_register_full.json'}}, 'solar_meter3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 3, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-003', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter3/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter3', 'ems_base_address': 31804, 'ems_end_address': 31827, 'register_count': 24, 'category_prefix': 'solar_meter3', 'telemetry_categories': ['solar_meter3__alarms', 'solar_meter3__energies', 'solar_meter3__currents', 'solar_meter3__voltages', 'solar_meter3__power', 'solar_meter3__frequency', 'solar_meter3__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter3/solarMeter_register_full.json'}}, 'solar_meter4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 4, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-004', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter4/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter4', 'ems_base_address': 31828, 'ems_end_address': 31851, 'register_count': 24, 'category_prefix': 'solar_meter4', 'telemetry_categories': ['solar_meter4__alarms', 'solar_meter4__energies', 'solar_meter4__currents', 'solar_meter4__voltages', 'solar_meter4__power', 'solar_meter4__frequency', 'solar_meter4__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter4/solarMeter_register_full.json'}}, 'solar_meter5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 5, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-005', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter5/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter5', 'ems_base_address': 31852, 'ems_end_address': 31875, 'register_count': 24, 'category_prefix': 'solar_meter5', 'telemetry_categories': ['solar_meter5__alarms', 'solar_meter5__energies', 'solar_meter5__currents', 'solar_meter5__voltages', 'solar_meter5__power', 'solar_meter5__frequency', 'solar_meter5__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter5/solarMeter_register_full.json'}}, 'solar_meter6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 6, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-006', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter6/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter6', 'ems_base_address': 31876, 'ems_end_address': 31899, 'register_count': 24, 'category_prefix': 'solar_meter6', 'telemetry_categories': ['solar_meter6__alarms', 'solar_meter6__energies', 'solar_meter6__currents', 'solar_meter6__voltages', 'solar_meter6__power', 'solar_meter6__frequency', 'solar_meter6__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter6/solarMeter_register_full.json'}}, 'solar_meter7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 7, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-007', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter7/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter7', 'ems_base_address': 31900, 'ems_end_address': 31923, 'register_count': 24, 'category_prefix': 'solar_meter7', 'telemetry_categories': ['solar_meter7__alarms', 'solar_meter7__energies', 'solar_meter7__currents', 'solar_meter7__voltages', 'solar_meter7__power', 'solar_meter7__frequency', 'solar_meter7__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter7/solarMeter_register_full.json'}}, 'solar_meter8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-008', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter8/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter8', 'ems_base_address': 31924, 'ems_end_address': 31947, 'register_count': 24, 'category_prefix': 'solar_meter8', 'telemetry_categories': ['solar_meter8__alarms', 'solar_meter8__energies', 'solar_meter8__currents', 'solar_meter8__voltages', 'solar_meter8__power', 'solar_meter8__frequency', 'solar_meter8__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter8/solarMeter_register_full.json'}}, 'solar_meter9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-009', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter9/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter9', 'ems_base_address': 31948, 'ems_end_address': 31971, 'register_count': 24, 'category_prefix': 'solar_meter9', 'telemetry_categories': ['solar_meter9__alarms', 'solar_meter9__energies', 'solar_meter9__currents', 'solar_meter9__voltages', 'solar_meter9__power', 'solar_meter9__frequency', 'solar_meter9__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter9/solarMeter_register_full.json'}}, 'solar_meter10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 10, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-010', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter10/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter10', 'ems_base_address': 31708, 'ems_end_address': 31731, 'register_count': 24, 'category_prefix': 'solar_meter10', 'telemetry_categories': ['solar_meter10__alarms', 'solar_meter10__energies', 'solar_meter10__currents', 'solar_meter10__voltages', 'solar_meter10__power', 'solar_meter10__frequency', 'solar_meter10__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter10/solarMeter_register_full.json'}}, 'solar_meter11': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 11, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-011', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter11/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter11', 'ems_base_address': 31732, 'ems_end_address': 31755, 'register_count': 24, 'category_prefix': 'solar_meter11', 'telemetry_categories': ['solar_meter11__alarms', 'solar_meter11__energies', 'solar_meter11__currents', 'solar_meter11__voltages', 'solar_meter11__power', 'solar_meter11__frequency', 'solar_meter11__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter11/solarMeter_register_full.json'}}, 'solar_meter12': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 12, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-012', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter12/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter12', 'ems_base_address': 31756, 'ems_end_address': 31779, 'register_count': 24, 'category_prefix': 'solar_meter12', 'telemetry_categories': ['solar_meter12__alarms', 'solar_meter12__energies', 'solar_meter12__currents', 'solar_meter12__voltages', 'solar_meter12__power', 'solar_meter12__frequency', 'solar_meter12__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter12/solarMeter_register_full.json'}}}, 'frequency_meters': {'frequency_meter1': {'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1515, 'unit_id': 1, 'poll_interval_ms': 3000, 'save_interval_ms': 6000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'status': 'inactive', 'device_id': 'FREQUENCY-METER-001', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'frequency_meter/frequency_meter1/frequencyMeter_register_full___me231.json', 'ems_block': 'frequency_meter1', 'ems_base_address': 26462, 'ems_end_address': 26485, 'register_count': 24, 'category_prefix': 'frequency_meter1', 'telemetry_categories': ['frequency_meter1__alarms', 'frequency_meter1__energies', 'frequency_meter1__currents', 'frequency_meter1__voltages', 'frequency_meter1__power', 'frequency_meter1__frequency', 'frequency_meter1__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'frequency_meter/frequency_meter1/frequencyMeter_register_full.json'}}}, 'grid_meters': {'grid_meter1': {'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1513, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'status': 'active', 'device_id': 'GRID-METER-001', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter1/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter1', 'ems_base_address': 26486, 'ems_end_address': 26525, 'register_count': 40, 'category_prefix': 'grid_meter1', 'telemetry_categories': ['grid_meter1__currents', 'grid_meter1__voltages', 'grid_meter1__power', 'grid_meter1__power_factor', 'grid_meter1__frequency', 'grid_meter1__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter1/gridMeter_register_full.json'}}, 'grid_meter2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-002', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter2/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter2', 'ems_base_address': 26646, 'ems_end_address': 26685, 'register_count': 40, 'category_prefix': 'grid_meter2', 'telemetry_categories': ['grid_meter2__currents', 'grid_meter2__voltages', 'grid_meter2__power', 'grid_meter2__power_factor', 'grid_meter2__frequency', 'grid_meter2__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter2/gridMeter_register_full.json'}}, 'grid_meter3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 3, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-003', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter3/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter3', 'ems_base_address': 26686, 'ems_end_address': 26725, 'register_count': 40, 'category_prefix': 'grid_meter3', 'telemetry_categories': ['grid_meter3__currents', 'grid_meter3__voltages', 'grid_meter3__power', 'grid_meter3__power_factor', 'grid_meter3__frequency', 'grid_meter3__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter3/gridMeter_register_full.json'}}, 'grid_meter4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 4, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-004', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter4/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter4', 'ems_base_address': 26726, 'ems_end_address': 26765, 'register_count': 40, 'category_prefix': 'grid_meter4', 'telemetry_categories': ['grid_meter4__currents', 'grid_meter4__voltages', 'grid_meter4__power', 'grid_meter4__power_factor', 'grid_meter4__frequency', 'grid_meter4__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter4/gridMeter_register_full.json'}}, 'grid_meter5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 5, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-005', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter5/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter5', 'ems_base_address': 26766, 'ems_end_address': 26805, 'register_count': 40, 'category_prefix': 'grid_meter5', 'telemetry_categories': ['grid_meter5__currents', 'grid_meter5__voltages', 'grid_meter5__power', 'grid_meter5__power_factor', 'grid_meter5__frequency', 'grid_meter5__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter5/gridMeter_register_full.json'}}, 'grid_meter6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 6, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-006', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter6/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter6', 'ems_base_address': 26806, 'ems_end_address': 26845, 'register_count': 40, 'category_prefix': 'grid_meter6', 'telemetry_categories': ['grid_meter6__currents', 'grid_meter6__voltages', 'grid_meter6__power', 'grid_meter6__power_factor', 'grid_meter6__frequency', 'grid_meter6__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter6/gridMeter_register_full.json'}}, 'grid_meter7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 7, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-007', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter7/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter7', 'ems_base_address': 26846, 'ems_end_address': 26885, 'register_count': 40, 'category_prefix': 'grid_meter7', 'telemetry_categories': ['grid_meter7__currents', 'grid_meter7__voltages', 'grid_meter7__power', 'grid_meter7__power_factor', 'grid_meter7__frequency', 'grid_meter7__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter7/gridMeter_register_full.json'}}, 'grid_meter8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-008', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter8/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter8', 'ems_base_address': 26886, 'ems_end_address': 26925, 'register_count': 40, 'category_prefix': 'grid_meter8', 'telemetry_categories': ['grid_meter8__currents', 'grid_meter8__voltages', 'grid_meter8__power', 'grid_meter8__power_factor', 'grid_meter8__frequency', 'grid_meter8__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter8/gridMeter_register_full.json'}}, 'grid_meter9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-009', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter9/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter9', 'ems_base_address': 26926, 'ems_end_address': 26965, 'register_count': 40, 'category_prefix': 'grid_meter9', 'telemetry_categories': ['grid_meter9__currents', 'grid_meter9__voltages', 'grid_meter9__power', 'grid_meter9__power_factor', 'grid_meter9__frequency', 'grid_meter9__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter9/gridMeter_register_full.json'}}, 'grid_meter10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 10, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-010', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter10/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter10', 'ems_base_address': 26526, 'ems_end_address': 26565, 'register_count': 40, 'category_prefix': 'grid_meter10', 'telemetry_categories': ['grid_meter10__currents', 'grid_meter10__voltages', 'grid_meter10__power', 'grid_meter10__power_factor', 'grid_meter10__frequency', 'grid_meter10__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter10/gridMeter_register_full.json'}}, 'grid_meter11': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 11, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-011', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter11/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter11', 'ems_base_address': 26566, 'ems_end_address': 26605, 'register_count': 40, 'category_prefix': 'grid_meter11', 'telemetry_categories': ['grid_meter11__currents', 'grid_meter11__voltages', 'grid_meter11__power', 'grid_meter11__power_factor', 'grid_meter11__frequency', 'grid_meter11__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter11/gridMeter_register_full.json'}}, 'grid_meter12': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 12, 'poll_interval_ms': 1000, 'save_interval_ms': 5000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-012', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter12/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter12', 'ems_base_address': 26606, 'ems_end_address': 26645, 'register_count': 40, 'category_prefix': 'grid_meter12', 'telemetry_categories': ['grid_meter12__currents', 'grid_meter12__voltages', 'grid_meter12__power', 'grid_meter12__power_factor', 'grid_meter12__frequency', 'grid_meter12__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter12/gridMeter_register_full.json'}}}, 'door_sensors': {'door_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-001', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor1/door_sensor_register_full.json', 'ems_block': 'door_sensor1', 'ems_base_address': 26230, 'ems_end_address': 26241, 'register_count': 12, 'category_prefix': 'door_sensor1', 'telemetry_categories': ['door_sensor1__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor1/door_sensor_register_full.json'}}, 'door_sensor2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-002', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor2/door_sensor_register_full.json', 'ems_block': 'door_sensor2', 'ems_base_address': 26254, 'ems_end_address': 26265, 'register_count': 12, 'category_prefix': 'door_sensor2', 'telemetry_categories': ['door_sensor2__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor2/door_sensor_register_full.json'}}, 'door_sensor3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 3, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-003', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor3/door_sensor_register_full.json', 'ems_block': 'door_sensor3', 'ems_base_address': 26266, 'ems_end_address': 26277, 'register_count': 12, 'category_prefix': 'door_sensor3', 'telemetry_categories': ['door_sensor3__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor3/door_sensor_register_full.json'}}, 'door_sensor4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 4, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-004', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor4/door_sensor_register_full.json', 'ems_block': 'door_sensor4', 'ems_base_address': 26278, 'ems_end_address': 26289, 'register_count': 12, 'category_prefix': 'door_sensor4', 'telemetry_categories': ['door_sensor4__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor4/door_sensor_register_full.json'}}, 'door_sensor5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 5, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-005', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor5/door_sensor_register_full.json', 'ems_block': 'door_sensor5', 'ems_base_address': 26290, 'ems_end_address': 26301, 'register_count': 12, 'category_prefix': 'door_sensor5', 'telemetry_categories': ['door_sensor5__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor5/door_sensor_register_full.json'}}, 'door_sensor6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 6, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-006', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor6/door_sensor_register_full.json', 'ems_block': 'door_sensor6', 'ems_base_address': 26302, 'ems_end_address': 26313, 'register_count': 12, 'category_prefix': 'door_sensor6', 'telemetry_categories': ['door_sensor6__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor6/door_sensor_register_full.json'}}, 'door_sensor7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 7, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-007', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor7/door_sensor_register_full.json', 'ems_block': 'door_sensor7', 'ems_base_address': 26314, 'ems_end_address': 26325, 'register_count': 12, 'category_prefix': 'door_sensor7', 'telemetry_categories': ['door_sensor7__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor7/door_sensor_register_full.json'}}, 'door_sensor8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-008', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor8/door_sensor_register_full.json', 'ems_block': 'door_sensor8', 'ems_base_address': 26326, 'ems_end_address': 26337, 'register_count': 12, 'category_prefix': 'door_sensor8', 'telemetry_categories': ['door_sensor8__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor8/door_sensor_register_full.json'}}, 'door_sensor9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-009', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor9/door_sensor_register_full.json', 'ems_block': 'door_sensor9', 'ems_base_address': 26338, 'ems_end_address': 26349, 'register_count': 12, 'category_prefix': 'door_sensor9', 'telemetry_categories': ['door_sensor9__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor9/door_sensor_register_full.json'}}, 'door_sensor10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 10, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-010', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor10/door_sensor_register_full.json', 'ems_block': 'door_sensor10', 'ems_base_address': 26242, 'ems_end_address': 26253, 'register_count': 12, 'category_prefix': 'door_sensor10', 'telemetry_categories': ['door_sensor10__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor10/door_sensor_register_full.json'}}}, 'flood_sensors': {'flood_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1521, 'unit_id': 11, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'FLOOD-SENSOR-001', 'model': 'FS1', 'register_map': {'model': 'default', 'map_file': 'flood_sensor/flood_sensor1/flood_sensor_register_full.json', 'ems_block': 'flood_sensor1', 'ems_base_address': 26460, 'ems_end_address': 26461, 'register_count': 2, 'category_prefix': 'flood_sensor1', 'telemetry_categories': ['flood_sensor1__flood'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'flood_sensor/flood_sensor1/flood_sensor_register_full.json'}}}, 'smoke_detectors': {'smoke_detector1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1522, 'unit_id': 12, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SMOKE-DETECTOR-001', 'model': 'SS1', 'register_map': {'model': 'default', 'map_file': 'smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json', 'ems_block': 'smoke_sensor1', 'ems_base_address': 31682, 'ems_end_address': 31683, 'register_count': 2, 'category_prefix': 'smoke_sensor1', 'telemetry_categories': ['smoke_sensor1__alarms'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json'}}}, 'heat_sensors': {'heat_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1523, 'unit_id': 13, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'HEAT-SENSOR-001', 'model': 'HS1', 'register_map': {'model': 'default', 'map_file': 'heat_sensor/heat_sensor1/heat_sensor_register_full.json', 'ems_block': 'heat_sensor1', 'ems_base_address': 26966, 'ems_end_address': 26967, 'register_count': 2, 'category_prefix': 'heat_sensor1', 'telemetry_categories': ['heat_sensor1__alarms'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'heat_sensor/heat_sensor1/heat_sensor_register_full.json'}}}, 'temperature_sensors': {'temperature_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1524, 'unit_id': 14, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'TEMP-SENSOR-001', 'model': 'TS1', 'register_map': {'model': 'default', 'map_file': 'temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json', 'ems_block': 'temperature_sensor1', 'ems_base_address': 31972, 'ems_end_address': 31979, 'register_count': 8, 'category_prefix': 'temperature_sensor1', 'telemetry_categories': ['temperature_sensor1__temperatures'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json'}}}, 'sensor_blocks': {'sensor_block1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1525, 'unit_id': 15, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SENSOR-BLOCK-001', 'model': 'SB1', 'register_map': {'model': 'SENS_STD', 'map_file': 'sensor_block/sensorB1/sensorB_register_full___sens_std.json', 'ems_block': 'sensor_block1', 'ems_base_address': 31669, 'ems_end_address': 31681, 'register_count': 13, 'category_prefix': 'sensor_block1', 'telemetry_categories': ['sensor_block1__humidity', 'sensor_block1__light'], 'control_categories': ['sensor_block1__control__relay'], 'control_register_count': 1, 'control_registers': ['alarm_activation_relay'], 'map_template': 'sensor_block/sensorB1/sensorB_register_full.json'}}}, 'bmu_units': {'bmu1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1543, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P1', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu1/bmu_register_full___bmu100.json', 'ems_block': 'bmu1', 'ems_base_address': 25610, 'ems_end_address': 25671, 'register_count': 62, 'category_prefix': 'bmu1', 'telemetry_categories': ['bmu1__cell_voltage', 'bmu1__temperature_sensors', 'bmu1__status', 'bmu1__alarms'], 'control_categories': ['bmu1__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu1/bmu_register_full.json'}}, 'bmu2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1544, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P2', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu2/bmu_register_full___bmu100.json', 'ems_block': 'bmu2', 'ems_base_address': 25734, 'ems_end_address': 25795, 'register_count': 62, 'category_prefix': 'bmu2', 'telemetry_categories': ['bmu2__cell_voltage', 'bmu2__temperature_sensors', 'bmu2__status', 'bmu2__alarms'], 'control_categories': ['bmu2__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu2/bmu_register_full.json'}}, 'bmu3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1545, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P3', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu3/bmu_register_full___bmu100.json', 'ems_block': 'bmu3', 'ems_base_address': 25796, 'ems_end_address': 25857, 'register_count': 62, 'category_prefix': 'bmu3', 'telemetry_categories': ['bmu3__cell_voltage', 'bmu3__temperature_sensors', 'bmu3__status', 'bmu3__alarms'], 'control_categories': ['bmu3__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu3/bmu_register_full.json'}}, 'bmu4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1546, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P4', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu4/bmu_register_full___bmu100.json', 'ems_block': 'bmu4', 'ems_base_address': 25858, 'ems_end_address': 25919, 'register_count': 62, 'category_prefix': 'bmu4', 'telemetry_categories': ['bmu4__cell_voltage', 'bmu4__temperature_sensors', 'bmu4__status', 'bmu4__alarms'], 'control_categories': ['bmu4__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu4/bmu_register_full.json'}}, 'bmu5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1547, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P5', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu5/bmu_register_full___bmu100.json', 'ems_block': 'bmu5', 'ems_base_address': 25920, 'ems_end_address': 25981, 'register_count': 62, 'category_prefix': 'bmu5', 'telemetry_categories': ['bmu5__cell_voltage', 'bmu5__temperature_sensors', 'bmu5__status', 'bmu5__alarms'], 'control_categories': ['bmu5__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu5/bmu_register_full.json'}}, 'bmu6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1548, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P6', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu6/bmu_register_full___bmu100.json', 'ems_block': 'bmu6', 'ems_base_address': 25982, 'ems_end_address': 26043, 'register_count': 62, 'category_prefix': 'bmu6', 'telemetry_categories': ['bmu6__cell_voltage', 'bmu6__temperature_sensors', 'bmu6__status', 'bmu6__alarms'], 'control_categories': ['bmu6__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu6/bmu_register_full.json'}}, 'bmu7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1549, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P7', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu7/bmu_register_full___bmu100.json', 'ems_block': 'bmu7', 'ems_base_address': 26044, 'ems_end_address': 26105, 'register_count': 62, 'category_prefix': 'bmu7', 'telemetry_categories': ['bmu7__cell_voltage', 'bmu7__temperature_sensors', 'bmu7__status', 'bmu7__alarms'], 'control_categories': ['bmu7__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu7/bmu_register_full.json'}}, 'bmu8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1550, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P8', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu8/bmu_register_full___bmu100.json', 'ems_block': 'bmu8', 'ems_base_address': 26106, 'ems_end_address': 26167, 'register_count': 62, 'category_prefix': 'bmu8', 'telemetry_categories': ['bmu8__cell_voltage', 'bmu8__temperature_sensors', 'bmu8__status', 'bmu8__alarms'], 'control_categories': ['bmu8__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu8/bmu_register_full.json'}}, 'bmu9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1551, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P9', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu9/bmu_register_full___bmu100.json', 'ems_block': 'bmu9', 'ems_base_address': 26168, 'ems_end_address': 26229, 'register_count': 62, 'category_prefix': 'bmu9', 'telemetry_categories': ['bmu9__cell_voltage', 'bmu9__temperature_sensors', 'bmu9__status', 'bmu9__alarms'], 'control_categories': ['bmu9__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu9/bmu_register_full.json'}}, 'bmu10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1552, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P10', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu10/bmu_register_full___bmu100.json', 'ems_block': 'bmu10', 'ems_base_address': 25672, 'ems_end_address': 25733, 'register_count': 62, 'category_prefix': 'bmu10', 'telemetry_categories': ['bmu10__cell_voltage', 'bmu10__temperature_sensors', 'bmu10__status', 'bmu10__alarms'], 'control_categories': ['bmu10__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu10/bmu_register_full.json'}}}, 'ups_units': {'ups1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1530, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'ups_unit', 'model': 'UPS-X3000', 'register_map': {'model': 'UPS_10K', 'map_file': 'ups/ups1/ups_register_full___ups_10k.json', 'ems_block': 'ups1', 'ems_base_address': 31980, 'ems_end_address': 32060, 'register_count': 81, 'category_prefix': 'ups1', 'telemetry_categories': ['ups1__input', 'ups1__output', 'ups1__battery', 'ups1__status', 'ups1__alarms'], 'control_categories': ['ups1__control__control'], 'control_register_count': 5, 'control_registers': ['output_voltage_setpoint_v', 'battery_low_threshold_percent', 'shutdown_delay_min', 'battery_test_start', 'buzzer_enable'], 'map_template': 'ups/ups1/ups_register_full.json'}}}, 'bess_energy_meters': {'bessEnergyMeter1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1531, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'bessEnergyMeter1', 'model': 'Schneider PM8000', 'register_map': {'model': 'default', 'map_file': 'bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json', 'ems_block': 'bessEnergyMeter1', 'ems_base_address': 25510, 'ems_end_address': 25609, 'register_count': 100, 'category_prefix': 'bessEnergyMeter1', 'telemetry_categories': ['bessEnergyMeter1__alarms', 'bessEnergyMeter1__energies', 'bessEnergyMeter1__currents', 'bessEnergyMeter1__power', 'bessEnergyMeter1__power_factor'], 'control_categories': ['bessEnergyMeter1__control__voltages', 'bessEnergyMeter1__control__frequency'], 'control_register_count': 9, 'control_registers': ['voltage_ab_v', 'voltage_bc_v', 'voltage_ca_v', 'voltage_ll_avg_v', 'voltage_an_v', 'voltage_bn_v', 'voltage_cn_v', 'voltage_ln_avg_v', 'frequency_hz'], 'map_template': 'bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json'}}}, 'ffr_meters': {'ffrEnergyMeter1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1532, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': None, 'model': None, 'register_map': {'model': 'default', 'map_file': 'ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json', 'ems_block': 'ffrEnergyMeter1', 'ems_base_address': 26350, 'ems_end_address': 26389, 'register_count': 40, 'category_prefix': 'ffrEnergyMeter1', 'telemetry_categories': ['ffrEnergyMeter1__currents', 'ffrEnergyMeter1__voltages', 'ffrEnergyMeter1__power', 'ffrEnergyMeter1__power_factor', 'ffrEnergyMeter1__frequency', 'ffrEnergyMeter1__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json'}}}}, 'protections': {'overvoltage_v': None, 'undervoltage_v': None, 'overcurrent_a': None, 'over_frequency_hz': None, 'under_frequency_hz': None, 'temperature_thresholds': {'cell_max_c': None, 'pcs_max_c': None, 'cabinet_max_c': None, 'cell_min_c': None, 'pcs_min_c': None, 'cabinet_min_c': None}, 'fire_suppression_integration': None, 'ems_bms_comm_timeout_ms': None}, 'monitoring_logging': {'data_push_interval_ms': None, 'logging_level': None, 'alarm_notifications': []}, 'functions': {'Manual_Operation': {'enabled': True, 'operation_type': 'charge', 'power_setpoint_kw': 150, 'ramp_rate_kw_s': 100, 'soc_limits': {'min_soc_pct': 50, 'max_soc_pct': 90}, 'soc_recovery_target_pct': 12, 'power_caps_kw': {'charge_cap_kw': 100, 'discharge_cap_kw': 90}, 'mode_priority': 'override-all', 'telemetry_control': {'control_channel': 'local-hmi', 'command_confirmation': True, 'status_feedback': 'mode'}, 'safety': {'trip_on_overvoltage': True, 'trip_on_undervoltage': True, 'trip_on_overtemperature': True, 'grid_fault_action': 'PCS_shutdown'}}, 'Arbitrage': {'enabled': False, 'timezone': 'Europe/Stockholm', 'tick': {'interval_seconds': 300, 'run_on_start': True, 'skip_cycles_log': True, 'zero_power_on_skip': True}, 'price_zone': 'SE4', 'price_currency': 'SEK', 'price_source': {'provider': 'elprisetjustnu', 'url_template': 'https.gess.se', 'timeout_ms': 4000, 'http': {'user_agent': 'GESS-EMS/1.0', 'headers': ''}, 'format': 'json_array', 'fields': {'time_start': 'time_start', 'time_end': 'time_end', 'price_sek': 'SEK_per_kWh', 'price_eur': 'EUR_per_kWh'}, 'resolution_minutes': 15, 'slot_mode': 'current_only'}, 'strategy': {'prefer_next_slot': True, 'min_spread': 0, 'buy_threshold': 0.1, 'sell_threshold': 0.12, 'buy_power_kw': 20, 'sell_power_kw': 20, 'tomorrow_plan': {'enabled': True, 'charge_cheapest_slots': 8, 'discharge_most_expensive_slots': 8, 'charge_power_kw': 20, 'discharge_power_kw': 20, 'tie_breaker': 'earlier_first'}}, 'optional': {'hysteresis': 0, 'conflict_rule': '', 'hysteresis_kw': 0}, 'ramp_rate_kw_s': 100}, 'Peak_Shaving': {'enabled': True, 'peak_threshold_kw': 50, 'discharge_power_limit_kw': 50, 'min_soc_pct': 10, 'recovery_soc_pct': 67, 'response_time_ms': 90, 'timezone': 'Europe/Stockholm', 'discharge_windows': [{'start': '13:00', 'end': '23:06', 'enabled': False, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '02:00', 'end': '08:50', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '10:00', 'end': '18:00', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}], 'charge_windows': [{'start': '01:00', 'end': '17:30', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '18:00', 'end': '23:00', 'enabled': False, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '01:00', 'end': '06:00', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}], 'optional': {'hysteresis_kw': 2, 'conflict_rule': 'discharge_overrides_charge'}, 'ramp_rate_kw_s': 100}, 'Valley_Filling': {'enabled': False, 'valley_threshold_kw': 75, 'charge_power_limit_kw': 120, 'max_soc_pct': None, 'min_soc_pct': None, 'response_time_ms': None, 'timezone': 'Europe/Stockholm', 'charge_windows': [{'start': '02:00', 'end': '22:00', 'enabled': True, 'charge_cap_kw': 100, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '14:00', 'end': '08:00', 'enabled': True, 'charge_cap_kw': 20, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '00:00', 'end': '08:00', 'enabled': True, 'charge_cap_kw': 20, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon']}], 'optional': {'hysteresis_kw': 2, 'conflict_rule': 'discharge_overrides_charge'}, 'ramp_rate_kw_s': 100}, 'Scheduled_Charge_Discharge': {'enabled': False, 'timezone': 'Europe/Stockholm', 'soc_limits': {'min_soc_pct': 40, 'max_soc_pct': 20}, 'power_limits': {'charge_power_limit_kw': 30, 'discharge_power_limit_kw': 30}, 'response_time_ms': 1, 'conflict_rule': 'discharge_overrides_charge', 'validation': {'prevent_overlaps': True, 'min_duration_minutes': 5, 'time_format': 'HH:MM'}, 'weekly': {'MonFri': [{'start': '12:50', 'end': '12:57', 'enabled': True, 'action': 'charge', 'powerSetpoint': 25.3, 'operationType': 'charge'}, {'start': '17:58', 'end': '19:05', 'enabled': True, 'action': 'discharge', 'powerSetpoint': 26, 'operationType': 'discharge'}, {'enabled': True, 'start': '01:00', 'end': '18:00', 'powerSetpoint': 25.1, 'action': 'charge', 'operationType': 'charge'}, {'enabled': False, 'start': '01:00', 'end': '17:04', 'powerSetpoint': 25.2, 'action': 'charge', 'operationType': 'charge'}, {'enabled': False, 'start': '11:00', 'end': '16:00', 'powerSetpoint': 25.3, 'action': 'charge', 'operationType': 'charge'}, {'enabled': False, 'start': '02:00', 'end': '12:00', 'powerSetpoint': 25.4, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '01:00', 'end': '16:00', 'powerSetpoint': 25.5, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '00:00', 'end': '17:00', 'powerSetpoint': 25.6, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '00:00', 'end': '12:00', 'powerSetpoint': 25.7, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '02:00', 'end': '12:00', 'powerSetpoint': 25.8, 'action': 'discharge', 'operationType': 'discharge'}], 'Sat': [{'start': '04:00', 'end': '04:00', 'enabled': True, 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '11:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:04', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '01:00', 'end': '12:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': False, 'start': '08:01', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '15:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': False, 'start': '11:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}], 'Sun': [{'enabled': True, 'start': '11:00', 'end': '12:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '15:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': False, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}]}, 'specific_dates': {'dates': '2026-09-24', 'entries': {'2026-09-24': [{'enabled': True, 'start': '10:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': None}]}}, 'ramp_rate_kw_s': 100}, 'Backup': {'enabled': False, 'backup_power_setpoint_kw': None, 'min_soc_pct': None, 'recovery_soc_pct': None, 'response_time_ms': None, 'black_start_enable': True, 'grid_mode_switch': {'enabled': False, 'grid_loss_voltage_v': 100, 'grid_loss_frequency_hz_low': 47, 'grid_loss_frequency_hz_high': 53, 'switch_delay_s': 3}, 'power_dispatch': {'enabled': False}, 'priority_rule': 'backup_overrides_all', 'ramp_rate_kw_s': 100}, 'Backup_Peak_Shaving': {'enabled': False, 'priority_rule': 'backup_over_peak_shaving', 'peak_shaving_ref': 'Peak_Shaving'}, 'Backup_Frequency_Regulation': {'enabled': False, 'priority_rule': 'backup_over_frequency_regulation', 'frequency_regulation_ref': 'Peak_Shaving'}, 'Power_Factor_Correction': {'enabled': False, 'target_pf': 0.98, 'pf_deadband': 0.01, 'mode': 'auto', 'q_max_kvar': None, 'ramp_rate_limit_kvar_s': None, 'response_time_ms': None, 'soc_limits': {'min_soc_pct': None, 'max_soc_pct': None}, 'power_caps_kw': {'charge_cap_kw': None, 'discharge_cap_kw': None}, 'priority_rule': 'pf_correction_over_valley_arbitrage', 'reactive_power_actuation': {'enabled': False, 'register': None, 'scale_kvar_per_unit': None, 'sign_convention': 'positive_capacitive', 'rated_kva': None}}, 'Voltage_Support': {'enabled': False, 'nominal_voltage_v': 230, 'v_low_pu': 0.9, 'v1_pu': 0.98, 'v2_pu': 1.02, 'v_high_pu': 1.1, 'q_max_kvar': None, 'ramp_rate_limit_kvar_s': None, 'response_time_ms': None, 'soc_limits': {'min_soc_pct': None, 'max_soc_pct': None}, 'power_caps_kw': {'charge_cap_kw': None, 'discharge_cap_kw': None}, 'priority_rule': 'voltage_support_over_pf_correction', 'reactive_power_actuation': {'enabled': False, 'register': None, 'scale_kvar_per_unit': None, 'sign_convention': 'positive_capacitive', 'rated_kva': None}}, 'Frequency_Regulation': {'enabled': False, 'grid_mode': 'on-grid-only', 'droop_pct': 50, 'deadband_hz': 0.5, 'participation_pct': 7, 'response_time_ms': 6, 'ramp_rate_limit_kw_s': 67, 'soc_limits': {'min_soc_pct': 60, 'max_soc_pct': 50}, 'soc_recovery_target_pct': 50, 'power_caps_kw': {'charge_cap_kw': 50, 'discharge_cap_kw': 50}, 'frequency_measurement_interval_ms': 50, 'priority_rule': 'frequency_over_arbitrage_valley', 'telemetry_api': {'endpoint_url': '', 'api_key': '', 'send_frequency_ms': 1000, 'payload_schema_version': '1.1', 'timeout_ms': 30, 'retry_policy': {'retries': 3, 'backoff_ms': 500}, 'failover_behavior': 'last-setpoint'}, 'recharge_windows': [{'start': '22:00', 'end': '06:00', 'enabled': True, 'charge_cap_kw': None}, {'start': '12:00', 'end': '14:00', 'enabled': False, 'charge_cap_kw': None}, {'start': '', 'end': '', 'enabled': False, 'charge_cap_kw': None}, {'start': '', 'end': '', 'enabled': False, 'charge_cap_kw': None}, {'start': '', 'end': '', 'enabled': False, 'charge_cap_kw': None}], 'logging': {'enabled': True, 'format': 'jsonl', 'flush_interval_ms': 500, 'max_batch_records': 5000, 'rotate_every_seconds': 300, 'folder': 'setting'}, 'soc_source': {'type': 'lastValue_json', 'refresh_interval_ms': 500, 'folder': 'soc', 'file_pattern': 'soc', 'soc_key': '', 'missing_soc_behavior': 'allow'}, 'nominal_hz': 50}, 'Anti_Backflow': {'enabled': False, 'export_limit_kw': 50, 'response_time_ms': 50, 'ramp_rate_limit_kw_s': 60, 'soc_limits': {'min_soc_pct': 48, 'max_soc_pct': 30}, 'priority_rule': 'anti_backflow_over_arbitrage_freq', 'timezone': 'Europe/Stockholm', 'control_windows': [{'start': '00:00', 'end': '23:59', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri', 'Sat', 'Sun']}, {'start': '09:00', 'end': '17:00', 'enabled': True, 'export_cap_kw': 5, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon']}], 'optional': {'specific_dates': '', 'fail_safe_behavior': 'clamp-zero', 'specific_date_controls': []}, 'ramp_rate_kw_s': 100}, 'Maintenance': {'hold_zero_power': True}, 'Energy_Optimization': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'energy_optimization_over_arbitrage_valley'}, 'Power_Node_Energy_Sharing': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'power_node_over_local_dispatch'}, 'Grid_Sync': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'grid_sync_over_grid_modes'}, 'Dynamic_Load_Balancing': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'load_balancing_over_peak_shaving'}}, 'control_settings': {'ems_control_mode': 'Internal_EMS', 'ems_refresh_rate_hz': 2, 'ems_refresh_rate_options_hz': [0.5, 1, 2, 5, 10]}} |
functions.Manual_Operation.enabled |
@6 | INT16U | 1 | RW | 1 (true) |
functions.Manual_Operation.power_setpoint_kw |
@7 | INT16U | 1 | RW | 150 |
functions.Manual_Operation.ramp_rate_kw_s |
@8 | INT16U | 1 | RW | 100 |
functions.Manual_Operation.soc_limits.min_soc_pct |
@9 | INT16U | 1 | RW | 50 |
functions.Manual_Operation.soc_limits.max_soc_pct |
@10 | INT16U | 1 | RW | 90 |
functions.Manual_Operation.soc_recovery_target_pct |
@11 | INT16U | 1 | RW | 12 |
functions.Manual_Operation.power_caps_kw.charge_cap_kw |
@12 | INT16U | 1 | RW | 100 |
functions.Manual_Operation.power_caps_kw.discharge_cap_kw |
@13 | INT16U | 1 | RW | 90 |
functions.Manual_Operation.telemetry_control.command_confirmation |
@14 | INT16U | 1 | RW | 1 (true) |
functions.Manual_Operation.safety.trip_on_overvoltage |
@15 | INT16U | 1 | RW | 1 (true) |
functions.Manual_Operation.safety.trip_on_undervoltage |
@16 | INT16U | 1 | RW | 1 (true) |
functions.Manual_Operation.safety.trip_on_overtemperature |
@17 | INT16U | 1 | RW | 1 (true) |
functions.Arbitrage.enabled |
@18 | INT16U | 1 | RW | 0 (false) |
functions.Arbitrage.tick.interval_seconds |
@19 | INT16U | 1 | RW | 300 |
functions.Arbitrage.tick.run_on_start |
@20 | INT16U | 1 | RW | 1 (true) |
functions.Arbitrage.tick.skip_cycles_log |
@21 | INT16U | 1 | RW | 1 (true) |
functions.Arbitrage.tick.zero_power_on_skip |
@22 | INT16U | 1 | RW | 1 (true) |
functions.Arbitrage.price_source.timeout_ms |
@23 | INT16U | 1 | RW | 4000 |
functions.Arbitrage.price_source.resolution_minutes |
@24 | INT16U | 1 | RW | 15 |
functions.Arbitrage.strategy.prefer_next_slot |
@25 | INT16U | 1 | RW | 1 (true) |
functions.Arbitrage.strategy.min_spread |
@26 | INT16U | 1 | RW | 0 |
functions.Arbitrage.strategy.buy_threshold |
@27 | FLOAT32 | 2 | RW | 0.1 |
functions.Arbitrage.strategy.sell_threshold |
@29 | FLOAT32 | 2 | RW | 0.12 |
functions.Arbitrage.strategy.buy_power_kw |
@31 | INT16U | 1 | RW | 20 |
functions.Arbitrage.strategy.sell_power_kw |
@32 | INT16U | 1 | RW | 20 |
functions.Arbitrage.strategy.tomorrow_plan.enabled |
@33 | INT16U | 1 | RW | 1 (true) |
functions.Arbitrage.strategy.tomorrow_plan.charge_cheapest_slots |
@34 | INT16U | 1 | RW | 8 |
functions.Arbitrage.strategy.tomorrow_plan.discharge_most_expensive_slots |
@35 | INT16U | 1 | RW | 8 |
functions.Arbitrage.strategy.tomorrow_plan.charge_power_kw |
@36 | INT16U | 1 | RW | 20 |
functions.Arbitrage.strategy.tomorrow_plan.discharge_power_kw |
@37 | INT16U | 1 | RW | 20 |
functions.Arbitrage.optional.hysteresis |
@38 | INT16U | 1 | RW | 0 |
functions.Arbitrage.optional.hysteresis_kw |
@39 | INT16U | 1 | RW | 0 |
functions.Arbitrage.ramp_rate_kw_s |
@40 | INT16U | 1 | RW | 100 |
functions.Peak_Shaving.enabled |
@41 | INT16U | 1 | RW | 1 (true) |
functions.Peak_Shaving.peak_threshold_kw |
@42 | INT16U | 1 | RW | 50 |
functions.Peak_Shaving.discharge_power_limit_kw |
@43 | INT16U | 1 | RW | 50 |
functions.Peak_Shaving.min_soc_pct |
@44 | INT16U | 1 | RW | 10 |
functions.Peak_Shaving.recovery_soc_pct |
@45 | INT16U | 1 | RW | 67 |
functions.Peak_Shaving.response_time_ms |
@46 | INT16U | 1 | RW | 90 |
functions.Peak_Shaving.optional.hysteresis_kw |
@47 | INT16U | 1 | RW | 2 |
functions.Peak_Shaving.ramp_rate_kw_s |
@48 | INT16U | 1 | RW | 100 |
functions.Valley_Filling.enabled |
@49 | INT16U | 1 | RW | 0 (false) |
functions.Valley_Filling.valley_threshold_kw |
@50 | INT16U | 1 | RW | 75 |
functions.Valley_Filling.charge_power_limit_kw |
@51 | INT16U | 1 | RW | 120 |
functions.Valley_Filling.max_soc_pct |
@52 | FLOAT32 | 2 | RW | - |
functions.Valley_Filling.min_soc_pct |
@54 | FLOAT32 | 2 | RW | - |
functions.Valley_Filling.response_time_ms |
@56 | FLOAT32 | 2 | RW | - |
functions.Valley_Filling.optional.hysteresis_kw |
@58 | INT16U | 1 | RW | 2 |
functions.Valley_Filling.ramp_rate_kw_s |
@59 | INT16U | 1 | RW | 100 |
functions.Scheduled_Charge_Discharge.enabled |
@60 | INT16U | 1 | RW | 0 (false) |
functions.Scheduled_Charge_Discharge.soc_limits.min_soc_pct |
@61 | INT16U | 1 | RW | 40 |
functions.Scheduled_Charge_Discharge.soc_limits.max_soc_pct |
@62 | INT16U | 1 | RW | 20 |
functions.Scheduled_Charge_Discharge.power_limits.charge_power_limit_kw |
@63 | INT16U | 1 | RW | 30 |
functions.Scheduled_Charge_Discharge.power_limits.discharge_power_limit_kw |
@64 | INT16U | 1 | RW | 30 |
functions.Scheduled_Charge_Discharge.response_time_ms |
@65 | INT16U | 1 | RW | 1 |
functions.Scheduled_Charge_Discharge.validation.prevent_overlaps |
@66 | INT16U | 1 | RW | 1 (true) |
functions.Scheduled_Charge_Discharge.validation.min_duration_minutes |
@67 | INT16U | 1 | RW | 5 |
functions.Scheduled_Charge_Discharge.ramp_rate_kw_s |
@68 | INT16U | 1 | RW | 100 |
functions.Backup.enabled |
@69 | INT16U | 1 | RW | 0 (false) |
functions.Backup.backup_power_setpoint_kw |
@70 | FLOAT32 | 2 | RW | - |
functions.Backup.min_soc_pct |
@72 | FLOAT32 | 2 | RW | - |
functions.Backup.recovery_soc_pct |
@74 | FLOAT32 | 2 | RW | - |
functions.Backup.response_time_ms |
@76 | FLOAT32 | 2 | RW | - |
functions.Backup.black_start_enable |
@78 | INT16U | 1 | RW | 1 (true) |
functions.Backup.grid_mode_switch.enabled |
@79 | INT16U | 1 | RW | 0 (false) |
functions.Backup.grid_mode_switch.grid_loss_voltage_v |
@80 | INT16U | 1 | RW | 100 |
functions.Backup.grid_mode_switch.grid_loss_frequency_hz_low |
@81 | INT16U | 1 | RW | 47 |
functions.Backup.grid_mode_switch.grid_loss_frequency_hz_high |
@82 | INT16U | 1 | RW | 53 |
functions.Backup.grid_mode_switch.switch_delay_s |
@83 | INT16U | 1 | RW | 3 |
functions.Backup.power_dispatch.enabled |
@84 | INT16U | 1 | RW | 0 (false) |
functions.Backup.ramp_rate_kw_s |
@85 | INT16U | 1 | RW | 100 |
functions.Backup_Peak_Shaving.enabled |
@86 | INT16U | 1 | RW | 0 (false) |
functions.Backup_Frequency_Regulation.enabled |
@87 | INT16U | 1 | RW | 0 (false) |
functions.Power_Factor_Correction.enabled |
@88 | INT16U | 1 | RW | 0 (false) |
functions.Power_Factor_Correction.target_pf |
@89 | FLOAT32 | 2 | RW | 0.98 |
functions.Power_Factor_Correction.pf_deadband |
@91 | FLOAT32 | 2 | RW | 0.01 |
functions.Power_Factor_Correction.q_max_kvar |
@93 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.ramp_rate_limit_kvar_s |
@95 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.response_time_ms |
@97 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.soc_limits.min_soc_pct |
@99 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.soc_limits.max_soc_pct |
@101 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.power_caps_kw.charge_cap_kw |
@103 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.power_caps_kw.discharge_cap_kw |
@105 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.reactive_power_actuation.enabled |
@107 | INT16U | 1 | RW | 0 (false) |
functions.Power_Factor_Correction.reactive_power_actuation.register |
@108 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.reactive_power_actuation.scale_kvar_per_unit |
@110 | FLOAT32 | 2 | RW | - |
functions.Power_Factor_Correction.reactive_power_actuation.rated_kva |
@112 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.enabled |
@114 | INT16U | 1 | RW | 0 (false) |
functions.Voltage_Support.nominal_voltage_v |
@115 | INT16U | 1 | RW | 230 |
functions.Voltage_Support.v_low_pu |
@116 | FLOAT32 | 2 | RW | 0.9 |
functions.Voltage_Support.v1_pu |
@118 | FLOAT32 | 2 | RW | 0.98 |
functions.Voltage_Support.v2_pu |
@120 | FLOAT32 | 2 | RW | 1.02 |
functions.Voltage_Support.v_high_pu |
@122 | FLOAT32 | 2 | RW | 1.1 |
functions.Voltage_Support.q_max_kvar |
@124 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.ramp_rate_limit_kvar_s |
@126 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.response_time_ms |
@128 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.soc_limits.min_soc_pct |
@130 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.soc_limits.max_soc_pct |
@132 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.power_caps_kw.charge_cap_kw |
@134 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.power_caps_kw.discharge_cap_kw |
@136 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.reactive_power_actuation.enabled |
@138 | INT16U | 1 | RW | 0 (false) |
functions.Voltage_Support.reactive_power_actuation.register |
@139 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.reactive_power_actuation.scale_kvar_per_unit |
@141 | FLOAT32 | 2 | RW | - |
functions.Voltage_Support.reactive_power_actuation.rated_kva |
@143 | FLOAT32 | 2 | RW | - |
functions.Frequency_Regulation.enabled |
@145 | INT16U | 1 | RW | 0 (false) |
functions.Frequency_Regulation.droop_pct |
@146 | INT16U | 1 | RW | 50 |
functions.Frequency_Regulation.deadband_hz |
@147 | FLOAT32 | 2 | RW | 0.5 |
functions.Frequency_Regulation.participation_pct |
@149 | INT16U | 1 | RW | 7 |
functions.Frequency_Regulation.response_time_ms |
@150 | INT16U | 1 | RW | 6 |
functions.Frequency_Regulation.ramp_rate_limit_kw_s |
@151 | INT16U | 1 | RW | 67 |
functions.Frequency_Regulation.soc_limits.min_soc_pct |
@152 | INT16U | 1 | RW | 60 |
functions.Frequency_Regulation.soc_limits.max_soc_pct |
@153 | INT16U | 1 | RW | 50 |
functions.Frequency_Regulation.soc_recovery_target_pct |
@154 | INT16U | 1 | RW | 50 |
functions.Frequency_Regulation.power_caps_kw.charge_cap_kw |
@155 | INT16U | 1 | RW | 50 |
functions.Frequency_Regulation.power_caps_kw.discharge_cap_kw |
@156 | INT16U | 1 | RW | 50 |
functions.Frequency_Regulation.frequency_measurement_interval_ms |
@157 | INT16U | 1 | RW | 50 |
functions.Frequency_Regulation.telemetry_api.send_frequency_ms |
@158 | INT16U | 1 | RW | 1000 |
functions.Frequency_Regulation.telemetry_api.timeout_ms |
@159 | INT16U | 1 | RW | 30 |
functions.Frequency_Regulation.telemetry_api.retry_policy.retries |
@160 | INT16U | 1 | RW | 3 |
functions.Frequency_Regulation.telemetry_api.retry_policy.backoff_ms |
@161 | INT16U | 1 | RW | 500 |
functions.Frequency_Regulation.logging.enabled |
@162 | INT16U | 1 | RW | 1 (true) |
functions.Frequency_Regulation.logging.flush_interval_ms |
@163 | INT16U | 1 | RW | 500 |
functions.Frequency_Regulation.logging.max_batch_records |
@164 | INT16U | 1 | RW | 5000 |
functions.Frequency_Regulation.logging.rotate_every_seconds |
@165 | INT16U | 1 | RW | 300 |
functions.Frequency_Regulation.soc_source.refresh_interval_ms |
@166 | INT16U | 1 | RW | 500 |
functions.Frequency_Regulation.nominal_hz |
@167 | INT16U | 1 | RW | 50 |
functions.Anti_Backflow.enabled |
@168 | INT16U | 1 | RW | 0 (false) |
functions.Anti_Backflow.export_limit_kw |
@169 | INT16U | 1 | RW | 50 |
functions.Anti_Backflow.response_time_ms |
@170 | INT16U | 1 | RW | 50 |
functions.Anti_Backflow.ramp_rate_limit_kw_s |
@171 | INT16U | 1 | RW | 60 |
functions.Anti_Backflow.soc_limits.min_soc_pct |
@172 | INT16U | 1 | RW | 48 |
functions.Anti_Backflow.soc_limits.max_soc_pct |
@173 | INT16U | 1 | RW | 30 |
functions.Anti_Backflow.ramp_rate_kw_s |
@174 | INT16U | 1 | RW | 100 |
functions.Maintenance.hold_zero_power |
@175 | INT16U | 1 | RW | 1 (true) |
functions.Energy_Optimization.enabled |
@176 | INT16U | 1 | RW | 0 (false) |
functions.Power_Node_Energy_Sharing.enabled |
@177 | INT16U | 1 | RW | 0 (false) |
functions.Grid_Sync.enabled |
@178 | INT16U | 1 | RW | 0 (false) |
functions.Dynamic_Load_Balancing.enabled |
@179 | INT16U | 1 | RW | 0 (false) |
protections.overvoltage_v |
@180 | FLOAT32 | 2 | RW | - |
protections.undervoltage_v |
@182 | FLOAT32 | 2 | RW | - |
protections.overcurrent_a |
@184 | FLOAT32 | 2 | RW | - |
protections.over_frequency_hz |
@186 | FLOAT32 | 2 | RW | - |
protections.under_frequency_hz |
@188 | FLOAT32 | 2 | RW | - |
protections.temperature_thresholds.cell_max_c |
@190 | FLOAT32 | 2 | RW | - |
protections.temperature_thresholds.pcs_max_c |
@192 | FLOAT32 | 2 | RW | - |
protections.temperature_thresholds.cabinet_max_c |
@194 | FLOAT32 | 2 | RW | - |
protections.temperature_thresholds.cell_min_c |
@196 | FLOAT32 | 2 | RW | - |
protections.temperature_thresholds.pcs_min_c |
@198 | FLOAT32 | 2 | RW | - |
protections.temperature_thresholds.cabinet_min_c |
@200 | FLOAT32 | 2 | RW | - |
protections.fire_suppression_integration |
@202 | FLOAT32 | 2 | RW | - |
protections.ems_bms_comm_timeout_ms |
@204 | FLOAT32 | 2 | RW | - |
monitoring_logging.data_push_interval_ms |
@206 | FLOAT32 | 2 | RW | - |
monitoring_logging.logging_level |
@208 | FLOAT32 | 2 | RW | - |
Appendix B: PCS remote-control registers
One row per PCS register that the map exposes for control. Map address is the
address on port 1540; PCS register is the address in the PCS's own register
numbering. In external-control mode the EMS drives the PCS through this block; an
integrator writing it directly should read section 13, limitation 2.
| Unit | Register | Map address | PCS register | Type |
|---|---|---|---|---|
pcs1 |
start_stop_command |
@27025 | @20657 | INT16 |
pcs1 |
active_power_set_kw |
@27324 | @23415 | INT16 |
pcs1 |
start_stop_control_item |
@27399 | @28000 | INT16 |
pcs1 |
operation_mode_setting_item |
@27400 | @28001 | INT16 |
pcs1 |
scheduling_mode_item |
@27401 | @28002 | INT16 |
pcs1 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@27402 | @28003 | INT16 |
pcs1 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@27403 | @28004 | INT16 |
pcs1 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@27404 | @28005 | INT16 |
pcs1 |
ems_time_setting_item |
@27405 | @28006 | UINT32 |
pcs1 |
ems_reset_pcs_item |
@27407 | @28007 | UINT16 |
pcs1 |
ems_reset_bms_item |
@27408 | @28008 | UINT16 |
pcs1 |
mode_pq_vf_command_item |
@27411 | @40582 | INT16 |
pcs10 |
start_stop_command |
@27412 | @20657 | INT16 |
pcs10 |
active_power_set_kw |
@27711 | @23415 | INT16 |
pcs10 |
start_stop_control_item |
@27786 | @28000 | INT16 |
pcs10 |
operation_mode_setting_item |
@27787 | @28001 | INT16 |
pcs10 |
scheduling_mode_item |
@27788 | @28002 | INT16 |
pcs10 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@27789 | @28003 | INT16 |
pcs10 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@27790 | @28004 | INT16 |
pcs10 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@27791 | @28005 | INT16 |
pcs10 |
ems_time_setting_item |
@27792 | @28006 | UINT32 |
pcs10 |
ems_reset_pcs_item |
@27794 | @28007 | UINT16 |
pcs10 |
ems_reset_bms_item |
@27795 | @28008 | UINT16 |
pcs10 |
mode_pq_vf_command_item |
@27798 | @40582 | INT16 |
pcs11 |
start_stop_command |
@27799 | @657 | INT16 |
pcs11 |
active_power_set_kw |
@28098 | @3415 | INT16 |
pcs11 |
start_stop_control_item |
@28173 | @8000 | INT16 |
pcs11 |
operation_mode_setting_item |
@28174 | @8001 | INT16 |
pcs11 |
scheduling_mode_item |
@28175 | @8002 | INT16 |
pcs11 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@28176 | @8003 | INT16 |
pcs11 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@28177 | @8004 | INT16 |
pcs11 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@28178 | @8005 | INT16 |
pcs11 |
ems_time_setting_item |
@28179 | @8006 | UINT32 |
pcs11 |
ems_reset_pcs_item |
@28181 | @8007 | UINT16 |
pcs11 |
ems_reset_bms_item |
@28182 | @8008 | UINT16 |
pcs11 |
mode_pq_vf_command_item |
@28185 | @20582 | INT16 |
pcs12 |
start_stop_command |
@28186 | @657 | INT16 |
pcs12 |
active_power_set_kw |
@28485 | @3415 | INT16 |
pcs12 |
start_stop_control_item |
@28560 | @8000 | INT16 |
pcs12 |
operation_mode_setting_item |
@28561 | @8001 | INT16 |
pcs12 |
scheduling_mode_item |
@28562 | @8002 | INT16 |
pcs12 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@28563 | @8003 | INT16 |
pcs12 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@28564 | @8004 | INT16 |
pcs12 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@28565 | @8005 | INT16 |
pcs12 |
ems_time_setting_item |
@28566 | @8006 | UINT32 |
pcs12 |
ems_reset_pcs_item |
@28568 | @8007 | UINT16 |
pcs12 |
ems_reset_bms_item |
@28569 | @8008 | UINT16 |
pcs12 |
mode_pq_vf_command_item |
@28572 | @20582 | INT16 |
pcs2 |
start_stop_command |
@28573 | @20657 | INT16 |
pcs2 |
active_power_set_kw |
@28872 | @23415 | INT16 |
pcs2 |
start_stop_control_item |
@28947 | @28000 | INT16 |
pcs2 |
operation_mode_setting_item |
@28948 | @28001 | INT16 |
pcs2 |
scheduling_mode_item |
@28949 | @28002 | INT16 |
pcs2 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@28950 | @28003 | INT16 |
pcs2 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@28951 | @28004 | INT16 |
pcs2 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@28952 | @28005 | INT16 |
pcs2 |
ems_time_setting_item |
@28953 | @28006 | UINT32 |
pcs2 |
ems_reset_pcs_item |
@28955 | @28007 | UINT16 |
pcs2 |
ems_reset_bms_item |
@28956 | @28008 | UINT16 |
pcs2 |
mode_pq_vf_command_item |
@28959 | @40582 | INT16 |
pcs3 |
start_stop_command |
@28960 | @657 | INT16 |
pcs3 |
active_power_set_kw |
@29259 | @3415 | INT16 |
pcs3 |
start_stop_control_item |
@29334 | @8000 | INT16 |
pcs3 |
operation_mode_setting_item |
@29335 | @8001 | INT16 |
pcs3 |
scheduling_mode_item |
@29336 | @8002 | INT16 |
pcs3 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@29337 | @8003 | INT16 |
pcs3 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@29338 | @8004 | INT16 |
pcs3 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@29339 | @8005 | INT16 |
pcs3 |
ems_time_setting_item |
@29340 | @8006 | UINT32 |
pcs3 |
ems_reset_pcs_item |
@29342 | @8007 | UINT16 |
pcs3 |
ems_reset_bms_item |
@29343 | @8008 | UINT16 |
pcs3 |
mode_pq_vf_command_item |
@29346 | @20582 | INT16 |
pcs4 |
start_stop_command |
@29347 | @657 | INT16 |
pcs4 |
active_power_set_kw |
@29646 | @3415 | INT16 |
pcs4 |
start_stop_control_item |
@29721 | @8000 | INT16 |
pcs4 |
operation_mode_setting_item |
@29722 | @8001 | INT16 |
pcs4 |
scheduling_mode_item |
@29723 | @8002 | INT16 |
pcs4 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@29724 | @8003 | INT16 |
pcs4 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@29725 | @8004 | INT16 |
pcs4 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@29726 | @8005 | INT16 |
pcs4 |
ems_time_setting_item |
@29727 | @8006 | UINT32 |
pcs4 |
ems_reset_pcs_item |
@29729 | @8007 | UINT16 |
pcs4 |
ems_reset_bms_item |
@29730 | @8008 | UINT16 |
pcs4 |
mode_pq_vf_command_item |
@29733 | @20582 | INT16 |
pcs5 |
start_stop_command |
@29734 | @657 | INT16 |
pcs5 |
active_power_set_kw |
@30033 | @3415 | INT16 |
pcs5 |
start_stop_control_item |
@30108 | @8000 | INT16 |
pcs5 |
operation_mode_setting_item |
@30109 | @8001 | INT16 |
pcs5 |
scheduling_mode_item |
@30110 | @8002 | INT16 |
pcs5 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@30111 | @8003 | INT16 |
pcs5 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@30112 | @8004 | INT16 |
pcs5 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@30113 | @8005 | INT16 |
pcs5 |
ems_time_setting_item |
@30114 | @8006 | UINT32 |
pcs5 |
ems_reset_pcs_item |
@30116 | @8007 | UINT16 |
pcs5 |
ems_reset_bms_item |
@30117 | @8008 | UINT16 |
pcs5 |
mode_pq_vf_command_item |
@30120 | @20582 | INT16 |
pcs6 |
start_stop_command |
@30121 | @657 | INT16 |
pcs6 |
active_power_set_kw |
@30420 | @3415 | INT16 |
pcs6 |
start_stop_control_item |
@30495 | @8000 | INT16 |
pcs6 |
operation_mode_setting_item |
@30496 | @8001 | INT16 |
pcs6 |
scheduling_mode_item |
@30497 | @8002 | INT16 |
pcs6 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@30498 | @8003 | INT16 |
pcs6 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@30499 | @8004 | INT16 |
pcs6 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@30500 | @8005 | INT16 |
pcs6 |
ems_time_setting_item |
@30501 | @8006 | UINT32 |
pcs6 |
ems_reset_pcs_item |
@30503 | @8007 | UINT16 |
pcs6 |
ems_reset_bms_item |
@30504 | @8008 | UINT16 |
pcs6 |
mode_pq_vf_command_item |
@30507 | @20582 | INT16 |
pcs7 |
start_stop_command |
@30508 | @657 | INT16 |
pcs7 |
active_power_set_kw |
@30807 | @3415 | INT16 |
pcs7 |
start_stop_control_item |
@30882 | @8000 | INT16 |
pcs7 |
operation_mode_setting_item |
@30883 | @8001 | INT16 |
pcs7 |
scheduling_mode_item |
@30884 | @8002 | INT16 |
pcs7 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@30885 | @8003 | INT16 |
pcs7 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@30886 | @8004 | INT16 |
pcs7 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@30887 | @8005 | INT16 |
pcs7 |
ems_time_setting_item |
@30888 | @8006 | UINT32 |
pcs7 |
ems_reset_pcs_item |
@30890 | @8007 | UINT16 |
pcs7 |
ems_reset_bms_item |
@30891 | @8008 | UINT16 |
pcs7 |
mode_pq_vf_command_item |
@30894 | @20582 | INT16 |
pcs8 |
start_stop_command |
@30895 | @657 | INT16 |
pcs8 |
active_power_set_kw |
@31194 | @3415 | INT16 |
pcs8 |
start_stop_control_item |
@31269 | @8000 | INT16 |
pcs8 |
operation_mode_setting_item |
@31270 | @8001 | INT16 |
pcs8 |
scheduling_mode_item |
@31271 | @8002 | INT16 |
pcs8 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@31272 | @8003 | INT16 |
pcs8 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@31273 | @8004 | INT16 |
pcs8 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@31274 | @8005 | INT16 |
pcs8 |
ems_time_setting_item |
@31275 | @8006 | UINT32 |
pcs8 |
ems_reset_pcs_item |
@31277 | @8007 | UINT16 |
pcs8 |
ems_reset_bms_item |
@31278 | @8008 | UINT16 |
pcs8 |
mode_pq_vf_command_item |
@31281 | @20582 | INT16 |
pcs9 |
start_stop_command |
@31282 | @657 | INT16 |
pcs9 |
active_power_set_kw |
@31581 | @3415 | INT16 |
pcs9 |
start_stop_control_item |
@31656 | @8000 | INT16 |
pcs9 |
operation_mode_setting_item |
@31657 | @8001 | INT16 |
pcs9 |
scheduling_mode_item |
@31658 | @8002 | INT16 |
pcs9 |
pcs_switch_control_valid_when_8002_register_value_is_2_item |
@31659 | @8003 | INT16 |
pcs9 |
pcs_power_control_valid_when_8002_register_value_is_2_kw |
@31660 | @8004 | INT16 |
pcs9 |
pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item |
@31661 | @8005 | INT16 |
pcs9 |
ems_time_setting_item |
@31662 | @8006 | UINT32 |
pcs9 |
ems_reset_pcs_item |
@31664 | @8007 | UINT16 |
pcs9 |
ems_reset_bms_item |
@31665 | @8008 | UINT16 |
pcs9 |
mode_pq_vf_command_item |
@31668 | @20582 | INT16 |
Appendix C: PCS addresses per unit
Every PCS block has the same layout, so the address of a register on unit N is
base(N) + offset. The offsets below are measured from pcs1.
| Unit | Block base | Block end | Model | SOC | SOH | Setpoint | Run/stop command | AC active power | DC power |
|---|---|---|---|---|---|---|---|---|---|
pcs1 |
@27025 | @27411 | SINEXCEL_PWS1_250K | @27299 | @27300 | @27324 | @27025 | @27339 | @27347 |
pcs10 |
@27412 | @27798 | SINEXCEL_PWS1_250K | @27686 | @27687 | @27711 | @27412 | @27726 | @27734 |
pcs11 |
@27799 | @28185 | EPCS105 | @28073 | @28074 | @28098 | @27799 | @28113 | @28121 |
pcs12 |
@28186 | @28572 | EPCS105 | @28460 | @28461 | @28485 | @28186 | @28500 | @28508 |
pcs2 |
@28573 | @28959 | SINEXCEL_PWS1_250K | @28847 | @28848 | @28872 | @28573 | @28887 | @28895 |
pcs3 |
@28960 | @29346 | EPCS105 | @29234 | @29235 | @29259 | @28960 | @29274 | @29282 |
pcs4 |
@29347 | @29733 | EPCS105 | @29621 | @29622 | @29646 | @29347 | @29661 | @29669 |
pcs5 |
@29734 | @30120 | EPCS105 | @30008 | @30009 | @30033 | @29734 | @30048 | @30056 |
pcs6 |
@30121 | @30507 | EPCS105 | @30395 | @30396 | @30420 | @30121 | @30435 | @30443 |
pcs7 |
@30508 | @30894 | EPCS105 | @30782 | @30783 | @30807 | @30508 | @30822 | @30830 |
pcs8 |
@30895 | @31281 | EPCS105 | @31169 | @31170 | @31194 | @30895 | @31209 | @31217 |
pcs9 |
@31282 | @31668 | EPCS105 | @31556 | @31557 | @31581 | @31282 | @31596 | @31604 |
C.1 Block layout
| Block | Base | End | Regs | Nodes | Source map | Model |
|---|---|---|---|---|---|---|
ac1 |
@25000 | @25084 | 85 | 56 | air_condition_unit/ac1/ac_register_full___ac_std.json |
AC_STD |
ac2 |
@25085 | @25169 | 85 | 56 | air_condition_unit/ac2/ac_register_full___ac_std.json |
AC_STD |
ac3 |
@25170 | @25254 | 85 | 56 | air_condition_unit/ac3/ac_register_full___ac_std.json |
AC_STD |
ac4 |
@25255 | @25339 | 85 | 56 | air_condition_unit/ac4/ac_register_full___ac_std.json |
AC_STD |
ac5 |
@25340 | @25424 | 85 | 56 | air_condition_unit/ac5/ac_register_full___ac_std.json |
AC_STD |
ac6 |
@25425 | @25509 | 85 | 56 | air_condition_unit/ac6/ac_register_full___ac_std.json |
AC_STD |
bessEnergyMeter1 |
@25510 | @25609 | 100 | 55 | bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json |
default |
bmu1 |
@25610 | @25671 | 62 | 62 | bmu/bmu1/bmu_register_full___bmu100.json |
BMU100 |
bmu10 |
@25672 | @25733 | 62 | 62 | bmu/bmu10/bmu_register_full___bmu100.json |
BMU100 |
bmu2 |
@25734 | @25795 | 62 | 62 | bmu/bmu2/bmu_register_full___bmu100.json |
BMU100 |
bmu3 |
@25796 | @25857 | 62 | 62 | bmu/bmu3/bmu_register_full___bmu100.json |
BMU100 |
bmu4 |
@25858 | @25919 | 62 | 62 | bmu/bmu4/bmu_register_full___bmu100.json |
BMU100 |
bmu5 |
@25920 | @25981 | 62 | 62 | bmu/bmu5/bmu_register_full___bmu100.json |
BMU100 |
bmu6 |
@25982 | @26043 | 62 | 62 | bmu/bmu6/bmu_register_full___bmu100.json |
BMU100 |
bmu7 |
@26044 | @26105 | 62 | 62 | bmu/bmu7/bmu_register_full___bmu100.json |
BMU100 |
bmu8 |
@26106 | @26167 | 62 | 62 | bmu/bmu8/bmu_register_full___bmu100.json |
BMU100 |
bmu9 |
@26168 | @26229 | 62 | 62 | bmu/bmu9/bmu_register_full___bmu100.json |
BMU100 |
door_sensor1 |
@26230 | @26241 | 12 | 12 | door_sensor/door_sensor1/door_sensor_register_full.json |
default |
door_sensor10 |
@26242 | @26253 | 12 | 12 | door_sensor/door_sensor10/door_sensor_register_full.json |
default |
door_sensor2 |
@26254 | @26265 | 12 | 12 | door_sensor/door_sensor2/door_sensor_register_full.json |
default |
door_sensor3 |
@26266 | @26277 | 12 | 12 | door_sensor/door_sensor3/door_sensor_register_full.json |
default |
door_sensor4 |
@26278 | @26289 | 12 | 12 | door_sensor/door_sensor4/door_sensor_register_full.json |
default |
door_sensor5 |
@26290 | @26301 | 12 | 12 | door_sensor/door_sensor5/door_sensor_register_full.json |
default |
door_sensor6 |
@26302 | @26313 | 12 | 12 | door_sensor/door_sensor6/door_sensor_register_full.json |
default |
door_sensor7 |
@26314 | @26325 | 12 | 12 | door_sensor/door_sensor7/door_sensor_register_full.json |
default |
door_sensor8 |
@26326 | @26337 | 12 | 12 | door_sensor/door_sensor8/door_sensor_register_full.json |
default |
door_sensor9 |
@26338 | @26349 | 12 | 12 | door_sensor/door_sensor9/door_sensor_register_full.json |
default |
ffrEnergyMeter1 |
@26350 | @26389 | 40 | 20 | ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json |
default |
fss1 |
@26390 | @26459 | 70 | 57 | fire_safety_system/fss1/fss_register_full___fss_std.json |
FSS_STD |
flood_sensor1 |
@26460 | @26461 | 2 | 2 | flood_sensor/flood_sensor1/flood_sensor_register_full.json |
default |
frequency_meter1 |
@26462 | @26485 | 24 | 12 | frequency_meter/frequency_meter1/frequencyMeter_register_full___me231.json |
ME231 |
grid_meter1 |
@26486 | @26525 | 40 | 20 | grid_energy_meter/grid_meter1/gridMeter_register_full___me231.json |
ME231 |
grid_meter10 |
@26526 | @26565 | 40 | 20 | grid_energy_meter/grid_meter10/gridMeter_register_full___me231.json |
ME231 |
grid_meter11 |
@26566 | @26605 | 40 | 20 | grid_energy_meter/grid_meter11/gridMeter_register_full___me231.json |
ME231 |
grid_meter12 |
@26606 | @26645 | 40 | 20 | grid_energy_meter/grid_meter12/gridMeter_register_full___me231.json |
ME231 |
grid_meter2 |
@26646 | @26685 | 40 | 20 | grid_energy_meter/grid_meter2/gridMeter_register_full___me231.json |
ME231 |
grid_meter3 |
@26686 | @26725 | 40 | 20 | grid_energy_meter/grid_meter3/gridMeter_register_full___me231.json |
ME231 |
grid_meter4 |
@26726 | @26765 | 40 | 20 | grid_energy_meter/grid_meter4/gridMeter_register_full___me231.json |
ME231 |
grid_meter5 |
@26766 | @26805 | 40 | 20 | grid_energy_meter/grid_meter5/gridMeter_register_full___me231.json |
ME231 |
grid_meter6 |
@26806 | @26845 | 40 | 20 | grid_energy_meter/grid_meter6/gridMeter_register_full___me231.json |
ME231 |
grid_meter7 |
@26846 | @26885 | 40 | 20 | grid_energy_meter/grid_meter7/gridMeter_register_full___me231.json |
ME231 |
grid_meter8 |
@26886 | @26925 | 40 | 20 | grid_energy_meter/grid_meter8/gridMeter_register_full___me231.json |
ME231 |
grid_meter9 |
@26926 | @26965 | 40 | 20 | grid_energy_meter/grid_meter9/gridMeter_register_full___me231.json |
ME231 |
heat_sensor1 |
@26966 | @26967 | 2 | 1 | heat_sensor/heat_sensor1/heat_sensor_register_full.json |
default |
cooling1 |
@26968 | @27024 | 57 | 35 | liquid_cooling_unit/cooling1/cooling_register_full___cool_std.json |
COOL_STD |
pcs1 |
@27025 | @27411 | 387 | 372 | pcs/pcs1/pcs_register_full___sinexcel_pws1_250k.json |
SINEXCEL_PWS1_250K |
pcs10 |
@27412 | @27798 | 387 | 372 | pcs/pcs10/pcs_register_full___sinexcel_pws1_250k.json |
SINEXCEL_PWS1_250K |
pcs11 |
@27799 | @28185 | 387 | 372 | pcs/pcs11/pcs_register_full___epcs105.json |
EPCS105 |
pcs12 |
@28186 | @28572 | 387 | 372 | pcs/pcs12/pcs_register_full___epcs105.json |
EPCS105 |
pcs2 |
@28573 | @28959 | 387 | 372 | pcs/pcs2/pcs_register_full___sinexcel_pws1_250k.json |
SINEXCEL_PWS1_250K |
pcs3 |
@28960 | @29346 | 387 | 372 | pcs/pcs3/pcs_register_full___epcs105.json |
EPCS105 |
pcs4 |
@29347 | @29733 | 387 | 372 | pcs/pcs4/pcs_register_full___epcs105.json |
EPCS105 |
pcs5 |
@29734 | @30120 | 387 | 372 | pcs/pcs5/pcs_register_full___epcs105.json |
EPCS105 |
pcs6 |
@30121 | @30507 | 387 | 372 | pcs/pcs6/pcs_register_full___epcs105.json |
EPCS105 |
pcs7 |
@30508 | @30894 | 387 | 372 | pcs/pcs7/pcs_register_full___epcs105.json |
EPCS105 |
pcs8 |
@30895 | @31281 | 387 | 372 | pcs/pcs8/pcs_register_full___epcs105.json |
EPCS105 |
pcs9 |
@31282 | @31668 | 387 | 372 | pcs/pcs9/pcs_register_full___epcs105.json |
EPCS105 |
sensor_block1 |
@31669 | @31681 | 13 | 7 | sensor_block/sensorB1/sensorB_register_full___sens_std.json |
SENS_STD |
smoke_sensor1 |
@31682 | @31683 | 2 | 1 | smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json |
default |
solar_meter1 |
@31684 | @31707 | 24 | 12 | solar_energy_meter/solar_meter1/solarMeter_register_full___me231.json |
ME231 |
solar_meter10 |
@31708 | @31731 | 24 | 12 | solar_energy_meter/solar_meter10/solarMeter_register_full___me231.json |
ME231 |
solar_meter11 |
@31732 | @31755 | 24 | 12 | solar_energy_meter/solar_meter11/solarMeter_register_full___me231.json |
ME231 |
solar_meter12 |
@31756 | @31779 | 24 | 12 | solar_energy_meter/solar_meter12/solarMeter_register_full___me231.json |
ME231 |
solar_meter2 |
@31780 | @31803 | 24 | 12 | solar_energy_meter/solar_meter2/solarMeter_register_full___me231.json |
ME231 |
solar_meter3 |
@31804 | @31827 | 24 | 12 | solar_energy_meter/solar_meter3/solarMeter_register_full___me231.json |
ME231 |
solar_meter4 |
@31828 | @31851 | 24 | 12 | solar_energy_meter/solar_meter4/solarMeter_register_full___me231.json |
ME231 |
solar_meter5 |
@31852 | @31875 | 24 | 12 | solar_energy_meter/solar_meter5/solarMeter_register_full___me231.json |
ME231 |
solar_meter6 |
@31876 | @31899 | 24 | 12 | solar_energy_meter/solar_meter6/solarMeter_register_full___me231.json |
ME231 |
solar_meter7 |
@31900 | @31923 | 24 | 12 | solar_energy_meter/solar_meter7/solarMeter_register_full___me231.json |
ME231 |
solar_meter8 |
@31924 | @31947 | 24 | 12 | solar_energy_meter/solar_meter8/solarMeter_register_full___me231.json |
ME231 |
solar_meter9 |
@31948 | @31971 | 24 | 12 | solar_energy_meter/solar_meter9/solarMeter_register_full___me231.json |
ME231 |
temperature_sensor1 |
@31972 | @31979 | 8 | 4 | temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json |
default |
ups1 |
@31980 | @32060 | 81 | 54 | ups/ups1/ups_register_full___ups_10k.json |
UPS_10K |
Appendix D: Key operating values per PCS
Addresses are for pcs1; add the offset in appendix C for another unit.
| Value | Register | pcs1 address | Offset | Type | Wire unit | Engineering value |
|---|---|---|---|---|---|---|
| SOC | bc_battery_cluster.soc_state_of_charge_item |
@27299 | +274 | UINT16 | percent | raw |
| SOH | bc_battery_cluster.soh_state_of_health_item |
@27300 | +275 | UINT16 | percent | raw |
| Applied power setpoint | control.remote_control.active_power_set_kw |
@27324 | +299 | INT16 | 0.1 kW, signed | raw / 10 kW |
| Battery cluster voltage | bc_battery_cluster.cluster_voltage_v |
@27295 | +270 | UINT16 | 0.1 V | raw / 10 V |
| Battery cluster current | bc_battery_cluster.cluster_current_a |
@27296 | +271 | INT16 | 0.1 A, signed | raw / 10 A |
| BMS DC current | bc_battery_cluster.dc_current_a |
@27285 | +260 | INT16 | 0.1 A, signed | raw / 10 A |
| AC active power | pcs.three_phase_total_active_power_kwh |
@27339 | +314 | INT16 | 0.1 kW, signed | raw / 10 kW |
| AC reactive power | pcs.three_phase_total_reactive_power_kvar |
@27340 | +315 | INT16 | 0.1 kvar, signed | raw / 10 kvar |
| DC power (PCS side) | pcs.dc_power_kw |
@27347 | +322 | INT16 | 0.1 kW, signed | raw / 10 kW |
| DC voltage | pcs.dc_voltage_v |
@27348 | +323 | INT16 | 0.1 V, signed | raw / 10 V |
| Grid frequency | auxiliary.grid_frequency_hz |
@27386 | +361 | FLOAT32 | Hz | raw |
| Max allowed charge power | bc_battery_cluster.maximum_allowable_charging_power_kw |
@27297 | +272 | UINT16 | kW | raw |
| Max allowed discharge power | bc_battery_cluster.maximum_allowable_discharging_power_kw |
@27298 | +273 | UINT16 | kW | raw |
| PCS run/stop status | pcs.pcs_start_stop_status |
@27350 | +325 | UINT16 | code | raw |
| PCS grid-connected | pcs.pcs_grid_connected_status |
@27351 | +326 | UINT16 | 0/1 | raw |
| PCS alarm present | pcs.pcs_alarm_present |
@27353 | +328 | UINT16 | 0/1 | raw |
| PCS fault present | pcs.pcs_fault_present |
@27354 | +329 | UINT16 | 0/1 | raw |
| PCS communication status | pcs.communication_status |
@27355 | +330 | UINT16 | code | raw |
| BMS communication status | bc_battery_cluster.communication_status |
@27320 | +295 | UINT16 | code | raw |
| BMS alarm level ½/3 | bc_battery_cluster.bms_level_3_alarm |
@27323 | +298 | UINT16 | code | raw |
Appendix E: Plant aggregates
These registers are computed when read, never cached, from the live PCS values. They are read-only. Where the source PCS reports zeros (a simulator that does not model voltage or current, for example) the aggregate is zero as well: the EMS does not invent values it does not measure.
| Register | Address | Operation | Unit | Source | Units aggregated |
|---|---|---|---|---|---|
plant__power.total_active_power_kw |
@32061 | sum(voltage*current/1000) | kW | bc_battery_cluster . - |
12 PCS |
plant__power.total_current_a |
@32063 | sum(current) | A | bc_battery_cluster . - |
12 PCS |
plant__power.pcs_online_count |
@32065 | count(voltage valid) | count | bc_battery_cluster . - |
12 PCS |
plant__voltage.dc_voltage_avg_v |
@32066 | mean(voltage) | V | bc_battery_cluster . - |
12 PCS |
plant__voltage.dc_voltage_min_v |
@32068 | min(voltage) | V | bc_battery_cluster . - |
12 PCS |
plant__voltage.dc_voltage_max_v |
@32070 | max(voltage) | V | bc_battery_cluster . - |
12 PCS |
plant__current.dc_current_avg_a |
@32072 | mean(current) | A | bc_battery_cluster . - |
12 PCS |
plant__current.dc_current_max_a |
@32074 | max(current) | A | bc_battery_cluster . - |
12 PCS |
plant__current.dc_current_min_a |
@32076 | min(current) | A | bc_battery_cluster . - |
12 PCS |
plant__ac_power.total_active_power_kw |
@32078 | sum(three_phase_total_active_power_kwh) | kW | pcs . three_phase_total_active_power_kwh (active units only) |
12 PCS |
plant__ac_power.total_reactive_power_kvar |
@32080 | sum(three_phase_total_reactive_power_kvar) | kvar | pcs . three_phase_total_reactive_power_kvar (active units only) |
12 PCS |
plant__ac_power.reporting_pcs_count |
@32082 | count(three_phase_total_active_power_kwh valid) | count | pcs . three_phase_total_active_power_kwh (active units only) |
12 PCS |
Appendix F: Validation harness
The checks in section 14 are produced by EnergySyc_EMS_ES100Cx12S/tools/ems_modbus_validation.py,
which talks to the map server and the bridge the way a third-party controller
would. It is safe to re-run: the control phase snapshots the settings file,
restores the as-found mode and control mode, and prints one PASS/FAIL line per
check.
| Phase | Covers | Mutates |
|---|---|---|
--phase reads |
connection, EMS status, aggregates, PCS telemetry, protocol edge cases, write-refusal rules | no |
--phase control |
mode start / stop / change, settings writes, external control bridge, PCS execution | yes, restores the as-found state |
# the run behind section 14, in one pass
python3 tools/ems_modbus_validation.py --phase all --host <ems-host> \
--ssh-host root@<ems-host> \
--settings /opt/gess-stack/ems/backend/app/EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_control_setting.json
# non-mutating, no host access needed
python3 tools/ems_modbus_validation.py --phase reads --host <ems-host>
# mutating only; --ssh-host is needed only to change ems_control_mode (an operator action)
python3 tools/ems_modbus_validation.py --phase control --host <ems-host> \
--ssh-host root@<ems-host> \
--settings /opt/gess-stack/ems/backend/app/EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_control_setting.json \
--sim-ports 1501,1502
A check is a PASS only when the EMS confirms the effect: a mode is confirmed by
ems_operation_status (@3), a setting by reading the register back, a bridge command
by reading the PCS setpoint registers. Checks that cannot run in a given environment
(no host access, PCS simulators unreachable) are reported as SKIPPED, never as PASS.