EMS alarms — how they map, and how to use the endpoints

Reference for the active-alarm pipeline served by the EMS backend.

  • Engine: ems_alarm_status.py (aggregation, condition evaluation, message building)
  • HTTP surface: ems_settings_api.py (server sub-command)
  • Runtime container: ems-backend, listening on container port 8080 (not published; only the Modbus port 1540 is mapped to the host)
  • Verified against deployed ems_alarm_status.py md5 5a844794… and ems_settings_api.py md5 34e78342…, which are byte-identical to this tree. The live numbers and example payloads below were captured from that deployment.

The endpoint is read-only and stateless. It never writes a queue, never opens Modbus, and never touches controller state. It reports what is alarming right now, derived from the current lastValue files — there is no retained alarm history here. (The frontend's own alarm list is a separate, database-backed path; see §7.)


1. The mapping chain

Everything comes from four inputs, combined per device:

# Input Location Supplies
1 Register map emsConfig/<type>/<device>/<stem>_register*.json device_id, component_type, field→address
2 Alarm map emsConfig/<type>/<device>/<stem>_alarm_code*.json the alarm catalogue and its activation rules
3 Live reading lastValue/<stem>_lastValue.json the measured values
4 Settings emsConfig/ems/ems_control_setting.json status per device, and the gate that decides whether a device is reported at all

Per device the chain is:

discover device folder
  → read register map      → device_id, component_type, model, address index
  → pick alarm map         → entries (rules + display text)
  → resolve reading file   → sibling <stem>_lastValue.json
  → settings gate          → skip this device type if its group is switched off
  → evaluate each entry    → one row per entry whose rule is TRUE
  → sort + serialise

1.1 Device discovery

_iter_devices() walks emsConfig/<type>/:

  • Type folders ems, db, api_portal, api_vpn, bakup, backup, docs, modes, tmp are skipped.
  • Any sub-folder containing a *_alarm_code*.json or a *register*.json is a device (pcs1, pcs2, … pcs12).
  • If the type folder has no such sub-folder but has the files itself, the type folder is the single device (frequency_meter, bmu, ups, …).

1.2 Register map → identity and addresses

The device's register map is the first non-model file matching *register*.json in the device folder (e.g. pcs_register_full.json).

  • device_id → the report's device_id (falls back to the folder name).
  • component_type → component_type on every row.
  • categories.<category>.<section>.<field> = {scale, address, data_type, registers, value, rw_type} is flattened into a field → definition index. That index is the only source of register_address.

Real definition, pcs1:

"bc_battery_cluster": { "read_only": {
  "soc_state_of_charge_item": {
    "scale": 1, "address": 3005, "data_type": "UINT16",
    "registers": 1, "value": 0, "rw_type": "read_only" }
}}

1.3 Model resolution

The model selects the alarm map (and any model-specific register map) for a device. It comes from emsConfig/selected_model.json:

  1. by_register_file[<register file name, lowercased>]
  2. else the model key at the top of that file

The real file (abridged — it also lists solarMeter_register.json, frequencyMeter_register.json, ac_register.json, cooling_register.json, fss_register.json, sensorB_register.json and bmu_register_1..10.json):

{
  "model": "ME231",
  "by_register_file": {
    "pcs_register_full.json": "EPCS105",
    "gridMeter_register.json": "ME231",
    "ups_register.json": "UPS_10K",
    "bmu_register_1.json": "BMU100"
  }
}

The slug is tried lowercased first, then verbatim, which is why the files on disk are lowercase (pcs_alarm_code___epcs105.json) while selected_model.json says EPCS105. A model of default/none/empty is ignored (_model_slugs).

Consequence worth knowing: the two energy meters have no by_register_file entry, so they fall back to the top-level model and resolve to the default map — hence bessMeter_alarm_code.json with alarm_map_source: "default" in the live payload, while every PCS resolves to a model map.

1.4 Alarm-map selection

Inside the device folder, glob("*_alarm_code*.json"):

  1. first file whose stem ends with ___<model lowercased> → alarm_map_source: "model"
  2. then ___<Model> verbatim → "model"
  3. else the first file without ___ → "default"
  4. if the device folder has none, repeat 1–3 in the type folder

The separator is exactly three underscores (___), the same convention as the model register maps (pcs_register_full___sinexcel_pws1_250k.json).

If nothing is found, the device is still listed with "note": "no_alarm_map" and alarm_map: null.

1.5 Reading resolution

Which file. The stem is the first candidate that exists as lastValue/<candidate>_lastValue.json, in this order:

  1. the register map's device_id (gridEnergyMeter1)
  2. the config folder name (grid_energy_meter)
  3. the register-file prefix (gridMeter_register.json → gridMeter)

Failing all three, a unique prefix match against the files present is used (case-insensitive, either direction). A prefix matching more than one file resolves to nothing, so pcs1 is never satisfied by pcs10.

The winner is reported as reading_key (null when nothing matched). Seen live: gridEnergyMeter1 → gridMeter, ups_unit → ups, Cl1_P1 → null.

Which field. The entry's field (alias register) is resolved in order:

  1. an exact key in the reading
  2. "<stem>__<field>" — the merged form load_last_values() produces (pcs1__soc)
  3. a unique suffix match: key == field or key.endswith("_" + field)

Rule 3 exists because devices prefix their readings: frequency_hz finds gridMeter_frequency_hz, l1_fault finds pcs_l1_fault. Ambiguity resolves to nothing rather than guessing.

If all of those miss, the value falls back to the register definition's own value (the last value written into the register map). Verified against the engine, with a reading containing soc, pcs1__soc, pcs_l1_fault and gridMeter_frequency_hz, and a register index containing soc at address 3005:

field resolved value register_address matched by
soc 55 3005 exact key
pcs_l1_fault True null unique suffix
l1_fault True null unique suffix
frequency_hz 50.01 null unique suffix
frequency None → never fires — nothing (not a suffix)
(field absent from the reading) register definition's value its address register map

So register_address: null on a firing alarm means only that the field is not in the register map — the rule still works.

The keys timestamp, device_id, model, meter_key and alarm are stripped from the reading before evaluation; an entry may not use them as a field.

1.6 The settings gate

The live report only reports devices whose settings block is switched on. Each emsConfig folder maps to one general_settings group:

emsConfig folder (device_type) general_settings group
pcs pcs
bmu bmu_units
ups ups_units
air_condition_unit ac_units
fire_safety_system fss
liquid_cooling_unit cooling_unit
sensor_block sensor_blocks
grid_energy_meter grid_meters
solar_energy_meter solar_meters
frequency_meter frequency_meters
bess_energy_meter bess_energy_meters
ffr_energy_meter ffr_meters

The rule (_group_is_inactive) is deliberately conservative:

  • a device type is skipped only when its group exists, has at least one status field, and none of those statuses is active;
  • an unknown type, a missing group, or a group without any status field is reported normally — a status that cannot be read never hides a device.

Skipped devices increment totals.devices_skipped and are absent from devices. The gate exists because a switched-off device is polled by nobody, so its lastValue file stops being refreshed and any threshold read from it would be evaluated against a frozen reading — a permanent phantom alarm.

status on each reported device is that group's status value for the device key (or the folder name).

1.7 Evaluation

Per entry, in order:

  1. the self_test flag must match the report mode (see §4.2);
  2. field must be present — otherwise the entry is catalogue-only and never fires;
  3. the condition must parse (§3.1);
  4. the resolved value must not be None — a missing reading never alarms;
  5. ignore_zero: true skips the entry while the value is exactly 0;
  6. the comparison must be true.

Rows sort by severity rank, then device_id, then alarm_code.


2. Severity and message text

Severity must be one of four known words; anything else sorts last.

severity rank
critical 0
major 1
minor 2
warning 3
(other / missing) 99

message is not simply the map's text.

For self-test rows it is rewritten per device type and severity from SELF_TEST_CONDITIONS. Real examples:

device_type critical major warning
pcs Battery SOC critically low: below the minimum operating limit. Cell temperature abnormally high: above the safe operating limit. Battery SOH below 80%: state of health degraded.
fire_safety_system Fire detected: fire signal active. Smoke detected above the alarm threshold. Door open: enclosure unsealed.
ups Mains supply failed: UPS running on battery. UPS battery low: runtime below the safe limit. UPS overload: load above rated capacity.
frequency_meter Grid frequency out of range: above the upper limit. Grid frequency below 49.5 Hz. Grid power factor below 0.8.
liquid_cooling_unit Coolant flow lost: circulation below the minimum. Coolant temperature above the safe operating limit. Coolant level below the warning limit.

The map's own alarm_display_name is kept regardless.

For live rows the map's message (or description) is used, with the measured value appended. Verified against the engine — the message is passed through untouched when the value or the operator is missing, and a boolean flag never gets a measured clause:

map message value / rule resulting message
Battery state of charge below 3%, discharge must stop. 2.0, < 3 Battery state of charge below 3%, discharge must stop (measured 2%).
Grid frequency above 50.5 Hz. 51.5, > 50.5 Grid frequency above 50.5 Hz (measured 51.5 Hz).
Grid frequency above the upper limit. 51.5, > 50.5 Grid frequency above the upper limit (measured 51.5, above the limit of 50.5).
Coolant temperature too high, 70 degC limit. 74.25, > 70 Coolant temperature too high, 70 degC limit (measured 74.25 degC).
Power factor below the target. 0.0125, < 0.95 Power factor below the target (measured 0.013, below the limit of 0.95).
A-phase overvoltage fault: voltage has exceeded the safe operating limit. True, truthy A-phase overvoltage fault: voltage has exceeded the safe operating limit.
Alarm count: number of events recorded since the last reset. 3, > 0 Alarm count: number of events recorded since the last reset (measured 3).

The rules behind those outputs:

  • The unit comes from the map's wording, longest alternative first (kWh before W), and a unit glued to its number still matches (245V, 3%).
  • % and °C bind tight (measured 2%, measured 74.25 degC); other units get a space (measured 51.5 Hz).
  • When the wording carries no unit, the limit is phrased as above the limit of 50.5; with a unit it becomes above the 50.5 Hz limit.
  • The limit is added only when the wording does not already state that number, so “below 3%” is not repeated as “the 3% limit”.
  • A limit of 0 is a counter rule (> 0), not a threshold, so it is never phrased: a count of 3 reads (measured 3), never (measured 3, above the limit of 0).
  • Numbers render as 47, 49.2, 0.013 — never 49.200000000000003, and a small non-zero value is never rounded to 0.
  • A trailing . in the map text is dropped before the clause is appended, and re-added after it.

Because the wording drives the unit and the limit phrasing, write the map's message as a complete operator sentence that names the condition; the engine adds the measurement only.

Generated entries are worded the same way: tools/alarm_message_style.py turns a register field name into <condition>: <what it means>., and tools/rewrite_alarm_messages.py re-derived the 9,049 generated messages in 81 maps from the old "<Device> reported <Field>." template. Hand-authored wording was never touched; each rewritten map keeps the previous text in a .bak-msgstyle file beside it.


3. Authoring an alarm map

3.1 Entry schema

A map is a JSON object keyed by alarm code:

{
  "PCS-SOC-LOW": {
    "alarm_display_name": "Battery SOC Critically Low",
    "message": "Battery state of charge below 3%, discharge must stop.",
    "severity": "critical",
    "field": "soc_state_of_charge_item",
    "condition": "< 3",
    "ignore_zero": true
  },
  "PCS-1004": {
    "alarm_display_name": "A Phase Overvoltage Fault Flag",
    "message": "A-phase overvoltage fault: voltage has exceeded the safe operating limit.",
    "severity": "critical",
    "field": "a_phase_overvoltage_fault_flag",
    "op": "truthy"
  },
  "ALM-2100": {
    "alarm_display_name": "Hardware status word, bit 3",
    "message": "Status word bit 3 latched.",
    "severity": "major",
    "field": "gridMeter_status_word",
    "op": "bit", "value": 3
  },
  "CAT-0001": {
    "alarm_display_name": "Documented but not evaluated",
    "message": "No field key: this entry can never fire."
  }
}
key required meaning
alarm_display_name recommended falls back to name
message recommended falls back to description; the measured value is appended
severity recommended critical / major / minor / warning
field to fire reading/register name; alias register
op optional == != < <= > >= truthy falsy bit; alias operator; aliases eq ne lt le gt ge; = means ==
value with op right-hand operand; for op: "bit" it is the bit index
condition optional shorthand string "<op> <operand>"; alias active_when
bit optional legacy shorthand for op: "bit"
ignore_zero optional skip the rule while the value is exactly 0
self_test reserved marks a synthetic entry (§4.2)

Defaults and shorthands:

  • no field → catalogue only, never fires. Existing hand-written maps keep working untouched until given rules.
  • field present but no op/value/bit/condition → truthy.
  • condition with a bare word: truthy/active/alarm/fault → truthy; falsy/inactive/normal/ok → falsy; anything else → == <word>.
  • condition literal types: "< 3" → ('<', 3.0), ">= 80" → ('>=', 80.0), "== 12" → ('==', 12.0), "true" → ('==', True), "weird state" → ('==', 'weird state'). Numbers always become floats, which is why a stored "< 3" is reported back as "< 3.0" (§4.1).
  • op: "truthy" / "falsy" take their (unused) operand from value or bit.

3.2 Comparison semantics

Verified against _compare():

value op operand result why
"fault" == "FAULT" True string compare is case-insensitive
"FAULT " == "fault" True whitespace trimmed
"25.0" > 20.0 True numeric strings compare numerically
"idle" > 20.0 False non-numeric operand → ordered comparisons are False
0 == "0" True numeric-vs-string resolves numerically
3 bit 1 True 3 & (1 << 1)
"" truthy – False empty string is false

Truthiness for truthy/falsy: bool as-is; numbers != 0; these strings are true — 1, true, yes, on, active, alarm, alarm_active, fault, error, critical, major, minor, warning, high, low; these are false — "", 0, false, no, off, inactive, none, null, normal, ok, noerror, no_error, n/a, -, nan; any other numeric string by value; anything else true.

< <= > >= against a non-numeric value or operand → False (never fires). That is why a word-valued flag needs truthy, not > 0.

3.3 Why ignore_zero matters

Several devices publish 0 for a value they have not measured yet — an idle BMS reports SOC and SOH as 0. Without ignore_zero, an "< 3" SOC rule fires the moment a battery goes idle. All 192 threshold entries in this tree carry it.

3.4 Generating maps

python3 tools/gen_alarm_maps.py                       # dry run, prints a report
python3 tools/gen_alarm_maps.py --write               # apply
python3 tools/gen_alarm_maps.py --write --only pcs    # limit to one type
python3 tools/gen_alarm_maps.py --write --refresh     # re-roll owned rules

The run is add-only. A code the map already carries is left exactly as it is, including the codes this generator wrote earlier, so a threshold changed in the alarm editor (§5) is not reverted by the next generator run. --refresh is the opt-out: it overwrites every code the generator owns with the rule it computes now, which is what a deliberate message/rule roll-out wants. A threshold every model should carry still goes in EXTRA_RULES; a threshold for one device or model is just edited in that device's own map.

For every device folder it writes the default map plus one map per model variant (pcs_alarm_code___epcs105.json, ups_alarm_code___ups_10k.json, …), derived from that model's own register map, and:

  • selects fields that describe a real fault, by suffix (*_fault, *_alarm, *_too_high, *_too_low, *_overload, *_islanding, …) after excluding setpoints, thresholds, modes, counters and status words;
  • gives each one a rule — truthy for boolean flags, > 0 for counters;
  • words its message as <condition>: <what it means>. (see §2), so generated alarms read like the hand-authored ones instead of restating the field name;
  • adds the hand-authored numeric thresholds from EXTRA_RULES in the same file (PCS/battery SOC and SOH, UPS battery capacity/runtime/temperature, coolant inlet temperature and flow, room temperature and humidity, fire-panel faults and canister charge, …), all with ignore_zero: true;
  • infers severity from the field name (fire, epo, insulation, overcurrent, overload, islanding, … → critical; too_high, fault, communication, temperature, … → major; else warning);
  • names codes <PREFIX>-<NNNN> (PCS-1072) or <PREFIX>-<NAME> for thresholds (PCS-SOC-LOW), so generated codes never collide with existing ALM-* codes;
  • preserves existing entries verbatim, and the first time a file is rewritten copies the original to <name>.bak-precopilot;
  • adds the three SELFTEST-* entries to every map.

A rule is dropped when its field is not present in that model's register map, which is how one rule table serves every model without producing phantom alarms.

Current content of the tree: 86 maps, 9 754 entries — 9 241 carrying a rule, 255 catalogue-only, 258 self-test (3 × 86); 192 entries carry ignore_zero.


4. The endpoints

All three are GET, all read-only, all on the settings API server (ems_settings_api.py server, default port 8080).

Path Purpose
/api/v1/ems/alarms active alarms from live readings
/api/v1/ems/alarms/self-test the same pipeline against synthetic alarms
/api/v1/ems/alarms/definitions the catalogue — every alarm each map defines, firing or not

4.1 GET /api/v1/ems/alarms

No query parameters are read. ?device_type= has no effect on this path — filtering exists only on the self-test path below. The module docstring at ems_settings_api.py:133 claims otherwise; the code does not implement it, and live /api/v1/ems/alarms and /api/v1/ems/alarms?device_type=pcs return byte-identical payloads.

docker exec ems-backend curl -s http://127.0.0.1:8080/api/v1/ems/alarms

Response (top-level keys: timestamp, source, self_test, totals, alarms, devices):

{
  "timestamp": 1759279512000,
  "source": "ems-backend",
  "self_test": false,
  "totals": {
    "devices_checked": 18,
    "devices_skipped": 5,
    "devices_with_alarms": 1,
    "active_alarms": 1
  },
  "alarms": [
    {
      "device_type": "pcs",
      "component_type": "pcs",
      "device_id": "pcs1",
      "reading_key": "pcs1",
      "model": "EPCS105",
      "alarm_code": "PCS-SOC-LOW",
      "alarm_display_name": "Battery SOC Critically Low",
      "message": "Battery state of charge below 3%, discharge must stop (measured 2%).",
      "severity": "critical",
      "field": "soc_state_of_charge_item",
      "register_address": 3005,
      "value": 2,
      "condition": "< 3.0",
      "detected_at": "2026-10-01T01:23:22.261000+00:00",
      "detected_at_ms": 1759279512000
    }
  ],
  "devices": [
    {
      "device_type": "pcs",
      "component_type": "pcs",
      "device_id": "pcs1",
      "reading_key": "pcs1",
      "model": "EPCS105",
      "status": "active",
      "has_reading": true,
      "reading_timestamp_ms": 1759279512000,
      "alarm_map": "pcs_alarm_code___epcs105.json",
      "alarm_map_source": "model",
      "active_alarm_count": 1
    }
  ]
}

Field notes:

  • timestamp, detected_at_ms and reading_timestamp_ms are epoch milliseconds; detected_at is UTC ISO-8601 with microseconds, and is the timestamp of the reading that carried the alarm — not the moment the report was built.
  • totals.devices_checked counts devices after filtering, devices_skipped counts devices hidden by the settings gate, devices_with_alarms counts devices with at least one row.
  • Every checked device appears in devices even with zero alarms, so the response doubles as a coverage report.
  • condition is the normalised rule: "< 3.0" (floats, see §3.1), "truthy", "falsy", "bit 3", "== FAULT".
  • A device whose alarm map is missing carries "note": "no_alarm_map".
  • status is the settings group's value for that device key, so it is null for devices the group keys differently from the register map's device_id — live examples: Cl1_P1, ups_unit, gridEnergyMeter1, solarEnergyMeter1. It is informational; only the group-level gate in §1.6 acts on statuses.

Real rows observed on the live system (one per device type, showing both map sources and the stem fallback):

device_type device_id reading_key model source alarm_map
pcs pcs1 … pcs12 pcs1 … pcs12 EPCS105 model pcs_alarm_code___epcs105.json
bmu Cl1_P1 null BMU100 model bmu_alarm_code___bmu100.json
ups ups_unit ups UPS_10K model ups_alarm_code___ups_10k.json
grid_energy_meter gridEnergyMeter1 gridMeter ME231 model gridMeter_alarm_code___me231.json
solar_energy_meter solarEnergyMeter1 solarMeter ME231 model solarMeter_alarm_code___me231.json
bess_energy_meter bessEnergyMeter1 bessEnergyMeter1 ME231 default bessMeter_alarm_code.json
ffr_energy_meter ffrEnergyMeter1 ffrEnergyMeter1 ME231 default ffrMeter_alarm_code.json

Note reading_key differing from device_id (gridEnergyMeter1 → gridMeter, ups_unit → ups), and bmu with no reading at all yet still resolving its map.

4.2 GET /api/v1/ems/alarms/self-test

Every alarm map contains three synthetic alarms — SELFTEST-001 (critical), SELFTEST-002 (major), SELFTEST-003 (warning) — each marked "self_test": true. They are inert during normal operation (the live report never returns them) and are returned only here, where the identical pipeline runs: same discovery, model resolution, map selection, ordering and serialisation.

Query parameters (accepted here, and only here):

parameter effect
?device_type=<type> keep only that device_type
?device=<type> alias for the above

Filtering happens after each device is evaluated, so totals.devices_checked reflects the filter.

docker exec ems-backend curl -s http://127.0.0.1:8080/api/v1/ems/alarms/self-test
docker exec ems-backend curl -s 'http://127.0.0.1:8080/api/v1/ems/alarms/self-test?device_type=pcs'
docker exec ems-backend curl -s 'http://127.0.0.1:8080/api/v1/ems/alarms/self-test?device=ups'

A real row:

{
  "device_type": "air_condition_unit",
  "component_type": "airConditionor",
  "device_id": "airConditionor1",
  "reading_key": "acUnit",
  "model": "AC_STD",
  "alarm_code": "SELFTEST-001",
  "alarm_display_name": "Self-Test Alarm (Critical)",
  "severity": "critical",
  "message": "Cooling fault active: temperature control lost.",
  "field": "__self_test__",
  "register_address": null,
  "value": null,
  "condition": "self-test",
  "detected_at": "2026-10-01T01:23:22.261000+00:00",
  "detected_at_ms": 1790817802261,
  "self_test": true
}

Differences from the live payload:

  • "self_test": true at the top level, plus a note stating the alarms are synthetic and reported only by this endpoint;
  • "self_test": true on every row;
  • "value": null, "register_address": null, "condition": "self-test", "field": "__self_test__";
  • detected_at is the moment the report was built (there is no reading);
  • the settings gate is not applied, so devices_skipped is always 0 and every configured device is covered — switching a device off cannot hide a broken alarm map;
  • message comes from the per-device-type table in §2, not from the map, so the report reads like that device's real alarm list.

Because the alarms are synthetic, the result is deterministic and works while every device is offline (reading_key: null in that case).

4.3 Authentication and status codes

_authorized() returns True when no token is configured; otherwise it requires an exact Authorization: Bearer <token> match.

condition status
authorised 200
token configured, header missing or wrong 401 {"error": "unauthorized"}
path outside the known set 404 {"error": "not_found"}
engine raised 500 {"error": "alarm_report_failed"\|"alarm_self_test_failed", "detail": "…"}

On this deployment the endpoints are unauthenticated. The server is started with an empty --bearer-token (the launcher passes the flag with an empty value and EMS_SETTINGS_API_TOKEN is unset in the container), so _authorized() returns True for every caller. Verified: a request with Authorization: Bearer not-the-token returns 200.

The bearer_token in emsConfig/ems/ems_api_config.json → ems_control_json.bearer_token is a client credential used by the pull/push helpers, not by this server's authentication. It already includes the Bearer prefix, and _request_json() detects that and sends it verbatim — do not prepend a second Bearer.

The practical boundary is the Docker network: the HTTP API listens on container port 8080 and is not published (only 1540/tcp, the Modbus server, is mapped to the host). To require a token, start the server with one:

python3 -u ems_settings_api.py server --bearer-token "$EMS_SETTINGS_API_TOKEN"

4.4 Calling it from other places

From the host (the API is not published):

docker exec ems-backend curl -s http://127.0.0.1:8080/api/v1/ems/alarms

From another container on the same network, use the service name — 127.0.0.1 is refused (measured HTTP 000 from ems-frontend, HTTP 200 via the name):

docker exec ems-frontend curl -s http://ems-backend:8080/api/v1/ems/alarms

Both paths can be re-pointed for a test instance with --alarms-path and --alarms-self-test-path.

4.5 Live values at the time of writing

Request devices_checked devices_skipped active_alarms
/api/v1/ems/alarms 18 5 0
/api/v1/ems/alarms/self-test 23 0 69
/api/v1/ems/alarms/self-test?device_type=pcs 12 0 36
/api/v1/ems/alarms/self-test?device=ups 1 0 3
/api/v1/ems/alarms/definitions 23 — 2

The definitions call also reports alarm_definitions: 2345; it has no devices_skipped, because the settings gate does not apply to it (§4.6).

The 5 skipped types are exactly those whose devices are all inactive in ems_control_setting.json: air_condition_unit (ac_units, 6 devices), fire_safety_system (fss), frequency_meter (frequency_meters), liquid_cooling_unit (cooling_unit), sensor_block (sensor_blocks). The live report covers pcs (12), bmu, ups, grid_energy_meter, solar_energy_meter, bess_energy_meter and ffr_energy_meter.

Those five types are absent from the live report by design, not by fault: an inactive device has a frozen reading, and reporting thresholds from it would invent alarms. They remain fully visible through the self-test endpoint.

4.6 GET /api/v1/ems/alarms/definitions

The catalogue. Where the two endpoints above answer what is wrong right now, this answers what can go wrong here: each device's selected alarm map expanded into one row per entry, firing or not, carrying the message text the map defines.

docker exec ems-backend curl -s http://127.0.0.1:8080/api/v1/ems/alarms/definitions
docker exec ems-backend curl -s \
  'http://127.0.0.1:8080/api/v1/ems/alarms/definitions?device_type=pcs'

One row (alarms-api.md has the full shape and the device-row fields):

{
  "alarm_code": "PCS-1004",
  "alarm_display_name": "A Phase Overvoltage Fault Flag",
  "message": "A-phase overvoltage fault: voltage has exceeded the safe operating limit.",
  "severity": "critical",
  "field": "a_phase_overvoltage_fault_flag",
  "condition": "truthy",
  "active": false
}

Differences from the live report worth knowing when reading it:

  • message is the map's wording without the measured clause, because a row that is not firing has no reading to quote; it is the text a map editor edits.
  • The settings gate of §1.6 is not applied, so a switched-off device type is still catalogued (the same coverage as the self-test report): totals.devices_checked is 23, there is no devices_skipped, and active_alarms can therefore exceed the live report's. Each device row carries status, so a caller can still see which types are off.
  • SELFTEST-* entries are excluded, as in the live report.
  • ?device_type= / ?device= filter as on the self-test path.
  • 2,345 rows, roughly 845 KB as served — fetch it once and filter client-side, or narrow it with ?device_type=.

5. Worked example — adding a new alarm

Goal: alarm when the grid meter frequency is above 50.5 Hz.

  1. Find the field. Confirm the name in the device's register map and that the client publishes it: emsConfig/grid_energy_meter/gridMeter_register.json contains frequency_hz, and lastValue/gridMeter_lastValue.json contains gridMeter_frequency_hz — the unique-suffix rule in §1.5 bridges the two.

  2. Add the entry to the map the device actually uses. Check the model first:

python3 -c "import json;print(json.load(open('emsConfig/selected_model.json'))['by_register_file'])"

Then append to emsConfig/grid_energy_meter/gridMeter_alarm_code___me231.json:

"GRID-UF": {
  "alarm_display_name": "Grid Frequency Above Limit",
  "message": "Grid frequency above 50.5 Hz.",
  "severity": "major",
  "field": "frequency_hz",
  "condition": "> 50.5"
}

Name the unit in the wording (Hz): that is what makes the report read “(measured 51.5 Hz)” rather than “(measured 51.5, above the limit of 50.5)”. Add the entry to the default map too if every model should carry it, or put it in EXTRA_RULES in tools/gen_alarm_maps.py so every model whose register map has that field gets it (it drops rules whose field is absent from that model). Changing a threshold that already has an entry needs neither: the generator is add-only, so an edit to the map is the durable home for it.

  1. Verify the wiring without needing a fault:
docker exec ems-backend curl -s \
  'http://127.0.0.1:8080/api/v1/ems/alarms/self-test?device_type=grid_energy_meter'

A device row with alarm_map: gridMeter_alarm_code___me231.json and alarm_map_source: "model" proves discovery, model resolution and map selection. A wrong filename shows up as note: "no_alarm_map".

  1. Verify the rule. Force the value in the lastValue file. It lives inside the backend's bind-mounted tree, so edit it from the host (the client overwrites it on its next poll):
python3 - <<'PY'
import json
p = ("/opt/gess-stack/ems/backend/app/EnergySyc_EMS_ES100Cx12S/"
     "lastValue/gridMeter_lastValue.json")
d = json.load(open(p))
d["gridMeter_frequency_hz"] = 51.5
json.dump(d, open(p, "w"))
print("forced", p)
PY

docker exec ems-backend curl -s http://127.0.0.1:8080/api/v1/ems/alarms \
  | python3 -c 'import json,sys;d=json.load(sys.stdin);print([a for a in d["alarms"] if a["alarm_code"]=="GRID-UF"])'

Expect one row with "value": 51.5, "condition": "> 50.5", a filled register_address, and a message ending in “(measured 51.5 Hz)”.

  1. Watch the ignore_zero trap. A forced 0 will not fire a threshold rule that carries ignore_zero — by design (§3.3). Test with a non-zero value.

  2. Restore the reading. The next poll overwrites it; do not leave a hand-edited value behind if the device is offline.


6. Quick reference

Files

emsConfig/<type>/<device>/<stem>_register*.json            register map
emsConfig/<type>/<device>/<stem>_alarm_code.json           default alarm map
emsConfig/<type>/<device>/<stem>_alarm_code___<model>.json model alarm map
emsConfig/selected_model.json                              model per register file
emsConfig/ems/ems_control_setting.json                     status + gate
lastValue/<stem>_lastValue.json                            live readings

Functions (ems_alarm_status.py)

function role
build_alarm_report() whole report; self_test= and device_type= switches
evaluate_device_alarms() one device → rows + summary
_iter_devices() discovery
_pick_map() model/default map lookup
_model_slugs(), _model_for_device() model resolution
_resolve_lastvalue_stem() which reading file
_read_value() field → value and address
_register_index() register map → field index
_parse_condition(), _compare() rule grammar and semantics
_describe_condition() the condition string in the response
_alarm_message() self-test text, or map text + measured value
_group_is_inactive() the settings gate

Reading the report

  • active_alarms > 0 and a device missing from devices → check devices_skipped and that device's status in ems_control_setting.json.
  • A device present with reading_key: null → the client is not writing its lastValue file; check the client log in logs/, not the alarm map.
  • A device present with note: "no_alarm_map" → filename or model mismatch.
  • An alarm that never fires → check the field exists in the reading, that the operator suits the value type (truthy for words, not > 0), and that ignore_zero is not suppressing a 0 reading.
  • register_address: null on a firing alarm → the field is not in the register map; the rule still works, only the address is missing.

7. What the frontend uses

The frontend's alarm screens read a database table through App\Services\EvAlarmService (getAlarms(), getLastAlarms(), getCriticalAlarms() — pagination, filtering, severity, search), and rows are created by EvAlarmService::createFromOcpp(). No PHP file in the frontend references /api/v1/ems/alarms.

The two are separate views of related data:

/api/v1/ems/alarms frontend alarm list
source live lastValue files alarms DB table
history none — what is true now retained, paginated
write path read-only written by OCPP/EMS ingestion
callers scripts, monitoring, SCADA-side checks the UI