How an alarm code gets its value — alarm map ↔ register map

Every active alarm the backend reports comes from two files per device. This document shows exactly how one points at the other, using PCS-1002 from emsConfig/pcs/pcs1/ as the worked example.

Companion to alarm-mapping-and-endpoints.md: that document covers the whole pipeline (device discovery, model selection, reading resolution, endpoints). This one zooms in on the single link between an alarm entry and the register it watches.

1. The pair

emsConfig/pcs/pcs1/
├── pcs_register_full___epcs105.json    what to read, where, how to decode it
└── pcs_alarm_code___epcs105.json       what it means, when it fires
  • Same folder = same device (device_type pcs, device_id pcs1).
  • Same ___epcs105 suffix = same device model (see §1.3 of the companion).
  • Neither file mentions the other. The device pairing comes from the directory; the field pairing is made at evaluation time.

2. The join key is the field name

An alarm entry's field must equal a register key in the register map. Not an address, not a register number, not the alarm code — the name string. The alarm codes (PCS-1001, PCS-1002, …) are the alarm file's own identifiers and mean nothing to the register file.

Alarm side — emsConfig/pcs/pcs1/pcs_alarm_code___epcs105.json:

"PCS-1002": {
  "alarm_display_name": "1 Cell Voltage Too High",
  "message": "1 cell voltage too high: the measured value is above the safe operating limit.",
  "severity": "major",
  "field": "1_cell_voltage_too_high",
  "op": "truthy"
}

Register side — emsConfig/pcs/pcs1/pcs_register_full___epcs105.json:

"categories": {
  "bc": {
    "read_only": {
      "1_cell_voltage_too_high": {
        "address": 1000,
        "data_type": "BOOL",
        "registers": 1,
        "value": false,
        "rw_type": "read_only"
      },

The string 1_cell_voltage_too_high appears on both sides. That single string is the entire relationship: it is how the alarm tells the engine which register to look at, and it is the only place the register's address (1000) can come from.

Alarm map Register map
Names the register field the key itself
Says what it means alarm_display_name, message, severity — (only a technical name)
Says where it is — address, data_type, registers, rw_type
Says when it fires op, condition, value, ignore_zero —
Holds the raw measurement — value (last written), and lastValue/pcs1_lastValue.json

2.1 One register, several alarms (and vice versa)

The link is a name lookup, so it is not one-to-one. The same address is reachable through more than one field name, and one register may be watched by several alarm codes — listing the pcs1 map shows, for example:

Address Fields pointing at it Alarm codes
1090 a_phase_overvoltage_fault_flag, phase_a_overvoltage_fault_flag PCS-1004, PCS-1150
1103 grid_current_imbalance, grid_current_unbalance PCS-1037, PCS-1038
1138 ac_main_relay_adhesion_fault, ac_main_relay_welding_fault PCS-1007, PCS-1008
1110 operating_bus_overvoltage, running_busbar_overvoltage PCS-1145, PCS-1174

So two spellings of the same condition can both be present and both fire; the alarm codes, alarm_display_name and wording are what distinguish them to the operator. Adding an alias is therefore safe, but expect the same physical bit to appear under each name.

Three places, all in the backend:

a. The register map is flattened into a name index. _register_index() (ems_alarm_status.py) walks categories → section → name → definition and builds {register_name: definition}. That is why the alarm file can use the bare leaf name 1_cell_voltage_too_high even though the register file nests it three levels deep. First occurrence wins if a name repeats.

b. The link is validated when a map is read or saved. validate_entries() (ems_alarm_maps.py:206) checks every entry against that index:

  • no field at all → error: 'field' is required (:254)
  • field not in the model's register map → warning: field 'x' is not in this model's register map, so the alarm can never fire (:257-261)

That warning is what the alarm editor page shows when you type a name the model does not define, and what register_fields in the API exists to prevent.

c. The value is resolved at runtime. _read_value() (ems_alarm_status.py) turns field into a live value, in this order:

  1. the exact key in the device reading (lastValue/pcs1_lastValue.json)
  2. the merged form "<stem>__<field>" (e.g. pcs1__soc)
  3. a unique suffix match — _match_reading_key() accepts key == field or key.endswith("_" + field), which is how the bare 1_cell_voltage_too_high finds the PCS client's prefixed pcs_1_cell_voltage_too_high. If more than one key matches, it resolves to nothing rather than guess.
  4. failing all of the above, the register definition's own value

The register_address reported with an alarm always comes from the register definition — never from the reading.

4. PCS-1002, end to end

pcs client polls the addresses from the register map (read_batches, Modbus)
        │
        ▼
lastValue/pcs1_lastValue.json        304 keys, 303 of them prefixed pcs_*
   pcs_1_cell_voltage_too_high = 0
        │                              (the register map's own "value" is updated too)
        ▼
evaluate_device_alarms()   ems_alarm_status.py:752
        │
        ├─ field          "1_cell_voltage_too_high"
        ├─ value          0            ← exact/suffix match in the reading
        ├─ ignore_zero    not set
        ├─ rule           op = truthy  → active only when the value is non-zero
        └─ address        1000         ← from the register definition
        │
        ▼
row emitted only when true:  message + severity come from the alarm map,
                             register_address from the register map

Right now pcs_1_cell_voltage_too_high is 0, so PCS-1002 does not fire. Set that bit to 1 on the device and the row appears with the alarm file's message (“1 cell voltage too high: the measured value is above the safe operating limit.”), severity major, and register_address: 1000.

5. The other rule shapes in the same file

Entry Field Rule Note
PCS-1002 1_cell_voltage_too_high (addr 1000, BOOL) op: truthy fires when the bit is non-zero
PCS-SOC-LOW soc_state_of_charge_item (addr 3005, UINT16) condition: "< 3", ignore_zero: true live value is 50 → no alarm; 0 would mean “not measured yet”, so it is skipped
PCS-SOH-LOW soh_state_of_health_item (addr 3006, UINT16) condition: "< 80", ignore_zero: true live value is 0 → would fire instantly without ignore_zero; this is exactly why the flag exists
SELFTEST-001..003 __self_test__ — (self_test: true) synthetic, no register behind it, only surfaced by the self-test endpoint
any entry with no field — — catalogue-only, never fires

op accepts truthy, falsy, bit, ==, !=, <, <=, >, >=, and condition is the shorthand string form ("< 3") for the numeric ones.

The last row of that table is a classification rather than a live case: the shipped maps contain no field-less entry any more. 255 of them were retired — 15 per file across 17 maps (the twelve pcs defaults plus the gridMeter, solarMeter, frequencyMeter, bessMeter and ffrMeter maps). They were spec imports whose threshold survived only as text inside the message, and because validate_entries requires field, any map holding them could not be saved through the editor at all. Retired in commit 84b42b7af; nothing was added and no entry with a real register binding was touched.

6. How a trigger is identified

An alarm is triggered when one entry's rule evaluates true against the current reading. Per entry, three gates in this order (evaluate_device_alarms(), ems_alarm_status.py:848-876):

  1. Is there a value? _read_value() must return something. No reading → the entry is skipped, so "unknown" is reported as nothing at all, never as healthy.
  2. ignore_zero? If set and the value is 0, the entry is skipped — 0 means "not measured yet" for several devices.
  3. Does the rule hold? _compare(value, op, operand).

_compare() semantics:

Rule True when Notes
truthy the reading is active _to_active(): booleans pass through, numbers and numeric strings are a non-zero test, anything unrecognised is not active
falsy the reading is inactive the inverse
bit int(value) & (1 << bit) is non-zero operand from value or bit
==, != equal / not equal string comparison when the operand is a string ("== Fault"), numeric otherwise
<, <=, >, >= numeric comparison non-numeric value or operand → false, the entry can never fire

The rule comes from whichever of these is present, first match winning:

  • op (alias operator; =, eq → ==, ne → !=, lt → <, le → <=, gt → >, ge → >=)
  • else condition, a string parsed by _CONDITION_RE (^\s*(==|!=|<=|>=|<|>|=)\s*(.+?)\s*$), also accepting the words truthy active alarm fault and falsy inactive normal ok
  • else bit
  • else a default of truthy — an entry with only a field fires whenever that reading is non-zero

A firing row carries alarm_code, alarm_display_name, severity and message from the alarm map, and field, value, condition, register_address and detected_at from the reading and the register map — which is why an operator can see both the wording and the exact number that tripped it.

Where to see the triggers:

  • GET /api/v1/ems/alarms — everything firing right now, optionally narrowed with ?device_type=pcs&device_id=pcs1. An empty list means nothing is firing; it does not mean the rules are missing.
  • lastValue/pcs1_lastValue.json — the raw inputs to that decision.
  • GET /api/v1/ems/alarms/self-test — synthetic alarms that exercise the message/severity pipeline without touching any register.

The engine is stateless: maps and readings are re-read on every request, so a rule change takes effect on the next request with no restart.

7. How a threshold is decided — is 3005 "ok" or "high"?

The register file never answers that. All it holds is what the number is — address, data_type, registers, scale, rw_type and the last value. There is no min, max, warning or trip field anywhere in it. soc_state_of_charge_item at 3005 is UINT16 with scale: 1: the file says "this is a 16-bit unsigned number", and nothing about whether 50 is acceptable.

The verdict lives on the alarm side, in the operand:

Register map (addr 3005) Alarm map (PCS-SOC-LOW)
Contents UINT16, scale: 1, value: 50 "condition": "< 3", "ignore_zero": true
Answers what the number is 3 is the line: 50 is fine, 2 fires
Changeable by the device / register map this document's subject — the alarm file

Two families, and they behave differently:

  • Device-decided (BOOL + truthy). 1_cell_voltage_too_high at 1000 is a fault bit the PCS sets itself. The threshold lives inside the device; the alarm file only relays it and supplies wording. You cannot tune it here.
  • Config-decided (numeric + comparison). SOC and SOH are measurements with no intrinsic limit, so we choose the number. < 3 for SOC and < 80 for SOH are our thresholds — editable, and worth repeating inside message so the operator knows where the line was drawn.

Units and scale. The engine compares the value exactly as the client wrote it and applies no scaling. Clients scale only integer types (apply_scale() in the pcs client, over SCALED_DATA_TYPES: INT16/INT32/UINT16/UINT32 and the trailing-U variants; BOOL and FLOAT32 pass through), and skip scale == 1. In the pcs1 map there are currently no registers with a scale other than 1, so every threshold is already in engineering units — SOC is 0-100, not 0-10000. If you ever add a register with scale: 0.1, write the threshold in the scaled unit; the engine will not convert it.

How to choose the number. Take it from the device or BMS specification, then check it against what the register actually reports (the lastValue file, or the maps API) before trusting it. A threshold the register can never reach is silently invisible.

Practical caveats:

  • ignore_zero: true means "0 = not measured". SOH reads 0 here, so without the flag "< 80" would fire the moment the pack is idle.
  • A missing reading is not OK — the entry is skipped, so a dead sensor looks quiet. Device-level status (the settings gate, companion §1.6) is what removes offline devices from the report.
  • data_type bounds the operand: a UINT16 can never be negative, so "< 0" is a reliable way to silence an entry, whereas on a BOOL any "< 3" rule is always true.
  • Mind raw versus scaled direction: >/< on a register reported in hundredths behaves nothing like the same numbers on a whole-unit register.
Entry Register Live value Rule Result now Fires at
PCS-1002 1000, BOOL 0 op: truthy not fired bit 1, set by the device
PCS-SOC-LOW 3005, UINT16 50 condition: "< 3", ignore_zero not fired 1 or 2
PCS-SOH-LOW 3006, UINT16 0 condition: "< 80", ignore_zero skipped (zero) 1-79

8. How to edit an alarm

Two routes, one file:

  • UI — /alarm-definition-editor (Admin / Super Admin only), which posts to the API.
  • API — GET/PUT /api/v1/ems/alarms/maps?device_type=pcs&device_id=pcs1; the SCADA app's EmsAlarmDefinitionsService reads with GET and writes with PUT.

A save runs this pipeline in write_alarm_map() (ems_alarm_maps.py:378):

  1. Validate — invalid entries are refused (400 alarm_map_rejected) with the first 12 problems listed. A missing field is an error; an unknown field is only a warning.
  2. Optimistic lock — the request carries expected_hash from the read. If the file changed in the meantime the save is refused (409), so you re-read and re-apply instead of silently overwriting someone else's edit.
  3. Back up — the current file is copied to <map>.bak-<YYYYmmdd_HHMMSS> before anything is written.
  4. Write atomically, prune old backups, then read the file back and verify it matches (a mismatch aborts and names the backup to restore).
  5. No-op detection — an edit identical to what is on disk returns changed: false and writes nothing.

The response reports changed, backup (file name, when one was made), warnings and the stored entries. Read the warnings: an entry pointing at a register the model does not define saves successfully but warns "not in this model's register map, so the alarm can never fire" — it looks accepted and can never trigger.

Edits take effect immediately; the engine re-reads the map per request, so nothing is restarted and no cache is cleared.

What an edit can and cannot do:

  • Can — rename alarm_display_name, rewrite message, change severity, change the comparison and operand, add ignore_zero, and repoint field at another register of the same model.
  • Cannot — change an address or a reading. Those live in the register map and in the device. Editing PCS-SOC-LOW never changes the value at 3005; it changes what the system says about it.
  • No enable/disable flag exists. To silence an entry, remove it or give it a condition that cannot be met ("< 0" on a UINT16). self_test entries cannot be edited and are preserved across saves.

Undo is the backup file beside the map (re-saving the previous entries restores it). Hand-editing the JSON also works and the engine will pick it up, but that path skips validation, the hash check and the backup.

Access: the UI needs Admin or Super Admin; the API itself is unauthenticated on the network, so keep its port off untrusted networks.

9. Pitfalls

An ambiguous name silently loses the live value. PCS-1004's field a_phase_overvoltage_fault_flag matches two keys in the pcs1 reading — pcs_a_phase_overvoltage_fault_flag and pcs_inverter_voltage_a_phase_overvoltage_fault_flag. The suffix rule refuses to choose, so the engine falls back to the register map's cached value. The alarm still works, but it is not driven by the live reading. If you want the live value, the field has to name a register whose suffix match is unique.

Renaming a register orphans alarms. Change a key in pcs_register_full___epcs105.json and every alarm whose field named it becomes unfireable — reported as the “can never fire” warning, not an error, so an existing map keeps loading. Re-check after editing either file.

Names must be unique per model. _register_index() keeps the first definition it meets for a repeated name, so two registers sharing a name cannot be distinguished by an alarm entry.

The model suffix couples the files. ___epcs105 on both names is what makes them the pair for model EPCS105 (selected_model.json maps pcs_register_full.json → EPCS105). A new PCS model needs its own register and alarm files, and the alarm entries must reference that model's register names.

An empty field is an error, an unknown field is only a warning. Saving an entry without field is rejected; an unknown field saves but never fires.

10. Checking the relationship live

  • API: GET /api/v1/ems/alarms/maps?device_type=pcs&device_id=pcs1 returns the entries and register_fields — the flattened allow-list an entry may point at.
  • UI: the alarm definition editor (/alarm-definition-editor) shows the same list next to each row and flags entries whose field the model does not define.
  • Shell, from the repo root:
python3 - <<'EOF'
import json
reg = json.load(open('emsConfig/pcs/pcs1/pcs_register_full___epcs105.json'))
alarm = json.load(open('emsConfig/pcs/pcs1/pcs_alarm_code___epcs105.json'))
index = {}
for cat in reg.get('categories', {}).values():
    for group in cat.values():
        for name, definition in group.items():
            index.setdefault(name, definition)
for code, entry in alarm.items():
    field = entry.get('field')
    if not field:
        print(f'{code:14} catalogue only')
        continue
    d = index.get(field)
    print(f'{code:14} {field:52} {"addr " + str(d["address"]) if d else "NOT IN REGISTER MAP"}')
EOF

11. Which file the editor writes (one file per device)

The editor works on one device at a time, so a save touches exactly one file:

emsConfig/<device_type>/<device_id>/<prefix>_alarm_code___<model-slug>.json

For pcs1 that is emsConfig/pcs/pcs1/pcs_alarm_code___epcs105.json. The choice is made by _pick_map(folder, "_alarm_code", model) (ems_alarm_status.py:84,775), which resolves in this order:

  1. Model-specific — a *_alarm_code*.json whose name ends with ___<model slug> (MODEL_SEPARATOR = "___", lowercased). Wins whenever it exists.
  2. Default — otherwise the first *_alarm_code*.json with no ___ variant suffix.
  3. Nothing → MapNotFound (the 404 for an unknown device).

The model comes from selected_model.json (by_register_file → model). Verified against the running backend:

Device queried map_path returned model
device_type=pcs&device_id=pcs1 pcs/pcs1/pcs_alarm_code___epcs105.json EPCS105
device_type=air_condition_unit&device_id=airConditionor1 air_condition_unit/ac_alarm_code___ac_std.json AC_STD

sha256sum of that file on disk equals the hash the API reports for the device, so the mapping is exact. device_id is the folder name or the register map's device_id — the UPS device is ups (not ups1, which returns 404).

Device type Model File written Sibling variants left untouched
pcs/pcs1…pcs12 EPCS105 pcs_alarm_code___epcs105.json pcs_alarm_code.json, …___sinexcel_pws1_250k.json, …___sungrow_sc250ud.json
air_condition_unit/* AC_STD ac_alarm_code___ac_std.json ac_alarm_code.json, …___ac_max.json, …___ac_pro.json
ups/* UPS_10K ups_alarm_code___ups_10k.json ups_alarm_code.json, …___ups_20k.json, …___ups_30k.json
grid_energy_meter/*, solar_energy_meter/*, frequency_meter/* ME231 …Meter_alarm_code___me231.json the ___p8000 and ___pm5560 variants
liquid_cooling_unit/* COOL_STD cooling_alarm_code___cool_std.json …___cool_max.json, …___cool_pro.json
fire_safety_system/* FSS_STD fss_alarm_code___fss_std.json …___fss_max.json, …___fss_pro.json
sensor_block/* SENS_STD sensorB_alarm_code___sens_std.json …___sens_max.json, …___sens_pro.json
bmu/bmu1…bmu10 BMU100 bmu_alarm_code___bmu100.json bmu_alarm_code.json, …___bmu200.json, …___bmu300.json
bess_energy_meter, ffr_energy_meter — bessMeter_alarm_code.json, ffrMeter_alarm_code.json only one file exists in each folder, so the default is used

The sibling variants are inert. In pcs/pcs1/ the live map has 190 entries while pcs_alarm_code.json has 205; for codes present in both the content is identical, and the extra 15 exist only in the unused file (ALM-1001, ALM-1002, and numeric ids such as 1065353216, which look like leftovers from an older import). Because EPCS105 resolves first, those 15 never load and can never fire for pcs1 — and editing that file there changes nothing. The map_path in the API response is the authoritative answer for "which file is live".

On saving, the current file is first copied to <same name>.bak-<YYYYmmdd_HHMMSS> (pruned over time; the .bak-msgstyle and .bak-precopilot files seen in the folder came from separate one-off scripts, not from the editor). Files the editor never writes: *register*.json, selected_model.json, ems_control_setting.json, lastValue/*.json.

12. There is no separate trigger file

The rule and the wording are ordinary fields of the alarm entry. Nothing else stores them:

"PCS-SOC-LOW": {
  "alarm_display_name": "Battery SOC Critically Low",
  "message": "Battery state of charge below 3%, discharge must stop.",   // wording
  "severity": "critical",                                                // wording
  "field": "soc_state_of_charge_item",                                   // which register
  "condition": "< 3",                                                    // the trigger logic
  "ignore_zero": true
}
Role Fields Comes from
Which register field alarm entry (must name a register in the device's register map)
Trigger logic op / condition / value / bit / ignore_zero alarm entry
Operator wording alarm_display_name, message, severity alarm entry
Address and measurement address, data_type, registers, scale, value register map, and the device reading

The verdict is computed, never stored: on each request _parse_condition() → _read_value() → _compare() in ems_alarm_status.py decides from the rule plus the live reading. Run against pcs1 as this was written:

Code Register field Rule Live value Verdict
PCS-1002 1_cell_voltage_too_high truthy 0 not active
PCS-1001 15v_power_supply_fault_flag truthy 0 not active
PCS-1010 air_conditioner_alarm truthy 0.0 not active
PCS-SOC-LOW soc_state_of_charge_item < 3.0 91 not active
PCS-SOH-LOW soh_state_of_health_item < 80.0 95 not active

Those numbers move with the device — the same entries read 50 and 0 earlier in the day, 91 and 95 here — which is why nothing on disk ever holds "alarm is active". What the editor saves is precisely these entry fields: validate_entries() stores alarm_display_name, message, severity, field, op/condition and ignore_zero (ems_alarm_maps.py:246-249) into the map file from §11. See §8 for the save pipeline itself.

So when a rule change appears to do nothing, the cause is almost always the wrong variant of the file: check map_path from the API, or open the device again in the editor, before concluding the rule was ignored.

13. Code map

Concern Where
Register name index ems_alarm_status.py — _register_index()
Which alarm map is live (model resolution) ems_alarm_status.py — _pick_map(), MODEL_SEPARATOR, selected_model.json
Field → value resolution ems_alarm_status.py — _read_value(), _match_reading_key()
Rule parsing (op, condition, aliases) ems_alarm_status.py — _parse_condition()
Comparison (truthy/falsy/bit/numeric) ems_alarm_status.py — _compare(), _to_active()
Trigger detection, ignore_zero ems_alarm_status.py — evaluate_device_alarms() (:752, firing logic :848-876)
Client-side scaling of readings pcs_client_save_data_*.py — apply_scale(), SCALED_DATA_TYPES
Map validation (errors vs warnings) ems_alarm_maps.py — validate_entries() (:206)
Map read / register_fields ems_alarm_maps.py — resolve_device(), read_alarm_map()
Map save (validate, lock, back up, atomic write) ems_alarm_maps.py — write_alarm_map() (:378), _backup_map(), _prune_backups()
Endpoint payloads and status codes ems_settings_api.py (server sub-command; GET/PUT /api/v1/ems/alarms/maps)
Admin-only editor UI SCADA app — /alarm-definition-editor, AlarmDefinitionsController, EmsAlarmDefinitionsService

Related: alarm-mapping-and-endpoints.md (§1.2 register index, §1.5 reading resolution), alarms-api.md.