POWER_FACTOR_CORRECTION

Drives the site power factor to a target by injecting or absorbing reactive power.

Mode string POWER_FACTOR_CORRECTION (EMS_OP_POWER_FACTOR_CORRECTION)
Dispatcher ems_main.py → control_logic_updated.control_step_power_factor_correction
Config block functions.Power_Factor_Correction
Queue action set_reactive_kvar (via _pcs_connect_and_set_reactive_power_kvar)
Queue source tag power_factor_correction
Status Implemented, actuation gated off by default

Purpose

Reads grid P, Q and power factor, computes the reactive power needed to move the power factor to target_pf within pf_deadband, and applies it.

How it decides

_pf_correction_q_kvar(P, Q, pf, cfg) returns the required total kvar, or None when it cannot compute:

  • None when P, Q or PF telemetry is missing.
  • None when target_pf is absent or non-positive.
  • When |pf - target_pf| <= pf_deadband the correction is 0 — inside the deadband, nothing moves.
  • With mode: "auto" the sign is chosen automatically so the correction always moves the actual PF towards the target rather than away from it (leading vs lagging depends on whether Q is already injective).
  • The result magnitude is bounded by q_max_kvar.

If the computed command is None the step logs the reason and returns without actuating.

Configuration

functions.Power_Factor_Correction

Key Live value Meaning
enabled false Master switch.
target_pf 0.98 Target power factor.
pf_deadband 0.01 Deadband around the target; no action inside it.
mode auto Direction selection (auto picks the sign).
q_max_kvar null Reactive ceiling. null ⇒ no action.
ramp_rate_limit_kvar_s null Ramp limit for the reactive setpoint.
response_time_ms null Recorded; not used.
soc_limits {null, null} SOC bounds.
power_caps_kw {null, null} Active-power caps (reserved).
priority_rule pf_correction_over_valley_arbitrage Outranks arbitrage/valley filling.
reactive_power_actuation enabled: false Same gate as Volt-VAR — see below.

The actuation gate

Identical mechanism to Voltage_Support: the required kvar is computed and logged every cycle, but nothing is queued unless reactive_power_actuation.enabled is true and register is non-null. Both a verified register in the PCS power sequence and an explicit operator opt-in are required.

Safety

  • Returns when is_external_control_active(), when enabled is false, or with no active PCS.
  • Returns when P/Q/PF telemetry is unavailable, or when q_max_kvar is missing/invalid.
  • Deadband prevents hunting around the target.
  • Total kvar split equally across active PCS; each clamped to that PCS's reactive_power_limits.max_capacitive_kvar / max_inductive_kvar before queueing.
  • Only the newest unapplied reactive setpoint is retained in the queue.

Shared reactive slot: this mode and Volt-VAR share one reactive queue slot. Whichever runs most recently overwrites the other's pending command.

Outputs

_pcs_connect_and_set_reactive_power_kvar(cfg, pcs_id, kvar) → queue action set_reactive_kvar, source power_factor_correction.