Plant aggregate registers
Generated from EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_register_full.json by EnergySyc_EMS_ES100Cx12S/tools/generate_register_map_docs.py. Do not edit by hand - re-run the generator after changing the register map.
These 12 registers are computed when read, never on a timer: the server
evaluates them from the live values of the PCS blocks, so a total that nobody
reads costs nothing. Sources marked active only skip units that are not
reporting valid data.
| Register | Address | Type | Regs | Access | Device | Notes |
|---|---|---|---|---|---|---|
total_active_power_kw |
@32061 | FLOAT32 | 2 | RO | - | - |
total_current_a |
@32063 | FLOAT32 | 2 | RO | - | - |
pcs_online_count |
@32065 | UINT16 | 1 | RO | - | - |
dc_voltage_avg_v |
@32066 | FLOAT32 | 2 | RO | - | - |
dc_voltage_min_v |
@32068 | FLOAT32 | 2 | RO | - | - |
dc_voltage_max_v |
@32070 | FLOAT32 | 2 | RO | - | - |
dc_current_avg_a |
@32072 | FLOAT32 | 2 | RO | - | - |
dc_current_max_a |
@32074 | FLOAT32 | 2 | RO | - | - |
dc_current_min_a |
@32076 | FLOAT32 | 2 | RO | - | - |
total_active_power_kw |
@32078 | FLOAT32 | 2 | RO | - | - |
total_reactive_power_kvar |
@32080 | FLOAT32 | 2 | RO | - | - |
reporting_pcs_count |
@32082 | UINT16 | 1 | RO | - | - |
Definitions
| Register | Address | Operation | Source registers | Unit |
|---|---|---|---|---|
plant__power.total_active_power_kw |
@32061 | sum(voltage*current/1000) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
kW |
plant__power.total_current_a |
@32063 | sum(current) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
A |
plant__power.pcs_online_count |
@32065 | count(voltage valid) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
count |
plant__voltage.dc_voltage_avg_v |
@32066 | mean(voltage) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
V |
plant__voltage.dc_voltage_min_v |
@32068 | min(voltage) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
V |
plant__voltage.dc_voltage_max_v |
@32070 | max(voltage) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
V |
plant__current.dc_current_avg_a |
@32072 | mean(current) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
A |
plant__current.dc_current_max_a |
@32074 | max(current) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
A |
plant__current.dc_current_min_a |
@32076 | min(current) | pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a |
A |
plant__ac_power.total_active_power_kw |
@32078 | sum(three_phase_total_active_power_kwh) | pcs1..pcs12 . pcs: three_phase_total_active_power_kwh (active units only) |
kW |
plant__ac_power.total_reactive_power_kvar |
@32080 | sum(three_phase_total_reactive_power_kvar) | pcs1..pcs12 . pcs: three_phase_total_reactive_power_kvar (active units only) |
kvar |
plant__ac_power.reporting_pcs_count |
@32082 | count(three_phase_total_active_power_kwh valid) | pcs1..pcs12 . pcs: three_phase_total_active_power_kwh (active units only) |
count |