Skip to content

EMS telemetry registers

Generated from EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_register_full.json by EnergySyc_EMS_ES100Cx12S/tools/generate_register_map_docs.py. Do not edit by hand - re-run the generator after changing the register map.

Alarms

13 registers, @2400..@13600.

Register Address Type Regs Access Device Notes
digital_input_status_validity_base @2400 BITMAP32 2 RO - -
setpoint_status_validity @2420 BITMAP32 2 RO - -
digital_input_status_validity_slot_a @2550 BITMAP32 2 RO - -
digital_input_status_validity_slot_b @2552 BITMAP32 2 RO - -
digital_input_status_validity_slot_c @2554 BITMAP32 2 RO - -
digital_input_status_validity_slot_d @2556 BITMAP32 2 RO - -
digital_output_status_validity_slot_a @2566 BITMAP32 2 RO - -
digital_output_status_validity_slot_b @2568 BITMAP32 2 RO - -
digital_output_status_validity_slot_c @2570 BITMAP32 2 RO - -
digital_output_status_validity_slot_d @2572 BITMAP32 2 RO - -
alarm_code @3152 BITMAP32 2 RO - relocated from @3146
current_disturbance @13598 INT32U 2 RO - -
voltage_disturbance @13600 INT32U 2 RO - -

Currents

5 registers, @3002..@24669.

Register Address Type Regs Access Device Notes
current_b_a @3002 FLOAT32 2 RO - -
current_c_a @3004 FLOAT32 2 RO - -
current_n_a @3006 FLOAT32 2 RO - -
current_avg_a @3010 FLOAT32 2 RO - -
current_a_a @24669 FLOAT32 2 RO - -

Energies

7 registers, @2706..@2722.

Register Address Type Regs Access Device Notes
active_energy_delivered_minus_received_kwh @2706 FLOAT32 2 RO - -
reactive_energy_delivered_kvarh @2708 FLOAT32 2 RO - -
reactive_energy_received_kvarh @2710 FLOAT32 2 RO - -
reactive_energy_delivered_minus_received_kvarh @2714 FLOAT32 2 RO - -
apparent_energy_delivered_kvah @2716 FLOAT32 2 RO - -
apparent_energy_received_kvah @2718 FLOAT32 2 RO - -
apparent_energy_delivered_minus_received_kvah @2722 FLOAT32 2 RO - -

Frequency

1 registers, @3110..@3110.

Register Address Type Regs Access Device Notes
frequency_hz @3110 FLOAT32 2 RO - -

Power

12 registers, @3054..@3076.

Register Address Type Regs Access Device Notes
active_power_a_kw @3054 FLOAT32 2 RO - -
active_power_b_kw @3056 FLOAT32 2 RO - -
active_power_c_kw @3058 FLOAT32 2 RO - -
active_power_total_kw @3060 FLOAT32 2 RO - -
reactive_power_a_kvar @3062 FLOAT32 2 RO - -
reactive_power_b_kvar @3064 FLOAT32 2 RO - -
reactive_power_c_kvar @3066 FLOAT32 2 RO - -
reactive_power_total_kvar @3068 FLOAT32 2 RO - -
apparent_power_a_kva @3070 FLOAT32 2 RO - -
apparent_power_b_kva @3072 FLOAT32 2 RO - -
apparent_power_c_kva @3074 FLOAT32 2 RO - -
apparent_power_total_kva @3076 FLOAT32 2 RO - -

Power Factor

4 registers, @3144..@3150.

Register Address Type Regs Access Device Notes
pf_a @3144 FLOAT32 2 RO - -
pf_b @3146 FLOAT32 2 RO - -
pf_c @3148 FLOAT32 2 RO - -
pf_total @3150 FLOAT32 2 RO - -

Voltages

8 registers, @3020..@3036.

Register Address Type Regs Access Device Notes
voltage_ab_v @3020 FLOAT32 2 RW - -
voltage_bc_v @3022 FLOAT32 2 RW - -
voltage_ca_v @3024 FLOAT32 2 RW - -
voltage_ll_avg_v @3026 FLOAT32 2 RW - -
voltage_an_v @3028 FLOAT32 2 RW - -
voltage_bn_v @3030 FLOAT32 2 RW - -
voltage_cn_v @3032 FLOAT32 2 RW - -
voltage_ln_avg_v @3036 FLOAT32 2 RW - -