How to Simulate Grid Conditions

Purpose

Vary grid voltage, frequency and power at the point of measurement so the EMS's measurement handling, frequency response and protection can be tested.

Prerequisites

  • Simulator stack up.
  • The meters are served and the EMS polls them.

The meter devices

Device Port Configuration
Grid Meter 1513 emsConfig/grid_energy_meter/gridMeter_*
Solar Meter 1514 emsConfig/solar_energy_meter/solarMeter_*
Frequency Meter 1515 emsConfig/frequency_meter/frequencyMeter_*

These three are single devices, not ranges — there is no Grid Meter 2.

Simulating each quantity

All changes go through the Config Editor (/) unless the change is alarm-shaped, in which case use the Alarms page.

Grid voltage

  1. Config Editor → the grid meter → the voltage register.
  2. Write a value above or below the alarm limit.
  3. Read back to confirm, then check the EMS sees it.
  4. For an over/under-voltage alarm, prefer the Alarms page on the rule itself: it writes a value known to satisfy the condition.

Frequency

  1. Config Editor → the frequency meter (or the grid meter, whichever the rule watches) → the frequency register.
  2. Write a value outside the allowed band.
  3. Confirm the EMS reports it.

For overfrequency and underfrequency, the Watched register, Rule and Writes columns on the Alarms page tell you exactly which register to move and to what — use them instead of guessing the band.

Active and reactive power

Write the meter's power registers. As always, raw values are unsigned: a negative import/export value appears as a large number (65403 is -133). Decode against the register's declared type.

Frequency response testing

There is no automated frequency-ramp feature. A frequency-response test is:

  1. Record the baseline frequency and the EMS's output commands.
  2. Change the frequency value in steps, waiting between steps.
  3. At each step, read the EMS's response and the commands it issues.
  4. Confirm the response direction and magnitude match the requirement.
  5. Restore the frequency.

Because write timestamps have one-second resolution, this works for control behaviour but not for sub-second response claims.

Functions the brief asks for that are NOT implemented

Requested Status
Grid connection / disconnection simulation No built-in control. No verified register or UI action that models the grid contactor. Approximate by driving the measurement values, or break the poll path
Automated frequency ramp Not present — step the value manually
Frequency meter in the dashboard's device list Known discrepancy. The frequency meter has a readable register map but has been observed absent from the device list the alarm-map reader enumerates (103 devices). If its alarms do not appear on the Alarms page, this is why — see Troubleshooting

Verification

Check Expected
Voltage change Read-back shows the new value; EMS view follows
Frequency change Same
Power change Same, with the sign decoded correctly
Alarm Fires on the rule's watched register, appears on the EMS side
Response EMS commands appear in the Write Monitor, on the correct port

Troubleshooting

Symptom Cause Fix
Changed a meter, EMS saw nothing The EMS polls a different device for that quantity Find which device the rule watches
Frequency alarm missing Frequency meter absent from the device enumeration Check the device list; the alarm-map reader and the device enumerator disagree here
Alarm fires but no EMS action The alarm has no actions configured See HOW_TO_ADD_ALARM_ACTION
Value looks wrong Signed value read as unsigned Decode against the register type