EnergySync EMS100CX12S — Modbus register map and external integration guide

Document EnergySync EMS100CX12S register map
Applies to EMS backend EnergySyc_EMS_ES100Cx12S, register map emsConfig/ems/ems_register_full.json
Interface Modbus TCP, EMS register map server port 1540, unit id 1
Direct control interface Modbus TCP, external control bridge port 1541, unit id 1
Status Verified against the running Docker stack (see Validation report)

This document is written for an external component manufacturer who has no knowledge of the internal EMS software. It contains everything needed to read the EMS, configure it, start and stop its operating modes, and drive the BESS through Modbus — including what the EMS does with each write and how to tell whether a command was accepted.

How to read it. Sections 1-5 describe the interface itself and are mandatory background. Sections 6-8 are the register reference. Sections 9-11 are the procedures and worked examples. Section 12 is fault handling, and sections 13-15 hold the validation evidence, known limitations and appendix tables.

Every address in this document is a PDU address: the number that goes on the wire. If your tool expects the "4xxxxx" convention, add 40001 (address 1 is 40002). The current map declares addresses 1 to 32082. Addresses outside that extent return exception 02 (illegal data address); an address inside the map that no register claims reads as 0.


1. Scope

The EMS exposes one holding-register map that serves three purposes:

  1. Measurements — plant, PCS, battery, meter and peripheral values, read-only.
  2. Configuration — the EMS settings an operator would otherwise change in the device UI, read-write.
  3. Commands — the operating mode and the PCS control registers, read-write.

Everything is reachable through a single Modbus TCP server on port 1540, unit id 1. The map is generated from the EMS's own register map file and the settings file, so it is the authoritative description of the interface.

This document covers the registers an external controller has a reason to touch or monitor: the EMS system registers, the settings registers behind every operating mode, the PCS control and telemetry registers, and the plant aggregates. The exhaustive address-by-address list — all 6,285 registers, including every measurement a PCS, BMU, meter or peripheral exposes — is generated separately under Register Map.

A second, optional interface exists for direct power control: the external control bridge on port 1541. It is started by the EMS backend only while the control mode is external_control. See section 10.

2. Interfaces and data flow

Component Protocol Address Notes
EMS register map server Modbus TCP <ems-host>:1540, unit 1 The map in this document. Always running.
External control bridge Modbus TCP <ems-host>:1541, unit 1 Started by the EMS in external_control mode only. One command register.
EMS settings file JSON on disk emsConfig/ems/ems_control_setting.json Where configuration from this map is persisted, and where measurements of EMS state come from.
Device register maps JSON on disk emsConfig/pcs/pcsN/pcs_register_full*.json PCS register image. Written by the PCS client with the values it polls, read by the map server.

Data flow for measurements:

PCS / BMS device ──poll──► PCS client ──latest values──► emsConfig/pcs/pcsN/…
                                    │                              │
                                    └──rows──► SCADA database       └──read──► EMS Modbus map (port 1540)

Data flow for configuration and commands:

external controller ──write──► EMS Modbus map ──► ems_control_setting.json ──read every cycle──► EMS control loop
                                             └──► device register map (PCS control registers)

The EMS control loop re-reads its settings file on every cycle (nominally 1 s), so a change made through Modbus takes effect without a restart and without an explicit "apply" command.

3. Protocol and addressing conventions

Item Value
Transport Modbus TCP (MBAP), port 1540
Unit / slave id 1 (any unit id is accepted on the standard port; use 1)
Highest declared register 32082 (the current map's last register). Reads beyond the map's extent return exception 02
Address 0 Invalid, returns exception 02. The map is 1-based: @1 is the first register.
Unmapped address inside the map Reads as 0
Address outside the map Exception 02 (illegal data address)

3.1 Function codes

Code Function Supported Use
1 Read coils answers, all zero not meaningful
2 Read discrete inputs answers, all zero not meaningful
3 Read holding registers yes read everything
4 Read input registers answers, all zero not meaningful
5 Write single coil echoes, no effect not meaningful
6 Write single register yes write one register
16 Write multiple registers yes write several registers

Use 3, 6 and 16. The other codes are answered by the server with empty data because the map only models holding registers; relying on them will silently give you zeros.

3.2 Data types and encodings

Registers are big-endian in both word order and byte order.

Type in this map Words Meaning
BOOL 1 0 = false, 1 = true
INT16 1 signed 16-bit, two's complement
INT16U / UINT16 1 unsigned 16-bit
UINT32 / INT32U 2 unsigned 32-bit, high word first
BITMAP32 2 32 flags, high word first, bit 0 = first flag
FLOAT32 2 IEEE-754 single, high word first
INT64U 4 unsigned 64-bit, high word first

Example — functions.Voltage_Support.v_low_pu at address 119 is FLOAT32 and reads 0x3F666666, i.e. 0.9. Always read the whole width of a register; reading only the first word of a FLOAT32 gives you 0x3F66, which is not the value.

3.3 Scaling

Two rules apply, and both matter.

  1. The map serves raw register values. It does not convert units. Apply the register's scale yourself.
  2. A register's scale is declared per register in the device map the EMS map is built from. Where a register declares no scale, the device-wide scale applies.

The practical cases:

Register group Wire unit Engineering value
PCS SOC, SOH (pcsN__bc_battery_cluster) percent, whole numbers as read (scale 1)
PCS power setpoint active_power_set_kw 0.1 kW raw ÷ 10
PCS cluster voltage / current V / A × 0.1 raw ÷ 10
PCS grid frequency 0.01 Hz raw ÷ 100
EMS FLOAT32 settings (thresholds, limits) engineering units as decoded

So a PCS SOC register reading 48 means 48 %, and a setpoint register reading 65386 means −150 raw, i.e. −15.0 kW. Signedness follows the register's declared type; read INT16 registers with your client's signed option or subtract 65536 when the top bit is set.

4. Read and write rules

4.1 The control-mode gate

The EMS only accepts writes to this map while it is under external or SCADA control. This is a deliberate safety property: the registers exist on the same port that a monitoring system uses, so writability is tied to an operator decision rather than to network reachability.

ems_control_mode (@2) Value Writes to the map
local_control (shown in the UI as Internal_EMS) 0 refused — the map is read-only
scada_control 1 accepted
external_control 2 accepted, and the EMS hands the PCS to the bridge

The control mode itself is not writable over Modbus: address 2 is refused with the reason "control mode is frontend-only". It must be set by the operator in the device UI (or the equivalent settings API call). See section 9.1.

4.2 Registers that are always read-only

rw_type = read_only registers — all measurements, plus ems_operation_status (@3) — can never be written, in any control mode.

4.3 What a refused write looks like

A refused write does not raise a Modbus exception. The server answers with a normal function-code-6 response whose value field holds the value that is stored, which for a refused write is the previous value — not the value you sent. The same applies to a value that is not a member of an enum: the register snaps back to what it was and the settings file is left untouched.

Measured on the delivered system, with the EMS in local control:

Request On the wire (response) Value field Register afterwards
write @1 = 10 06 0001 0002 2 (the old value) 2 (PEAK_SHAVING)
write @4 = 7 06 0004 0002 2 (the old value) 2
write @3 = 5 (read-only) 06 0003 0002 2 (the old value) 2

So a refusal is visible straight away: compare the value field of the response with the value you sent. If they differ, the EMS did not accept the command. Still read the register back after writing — for a setting, that also confirms the value reached the settings file the control loop reads.

Fault Modbus response Register afterwards Detect by
Control mode is local FC6, value field = old value previous value response value, read back
Register is read-only FC6, value field = old value previous value response value, read back
Value not in the enum FC6, value field = old value previous value response value, read back
Address outside the map exception 02 n/a exception
Unsupported function code exception 01 n/a exception

4.4 Persistence

An accepted write is persisted immediately and atomically:

  • EMS settings registers (addresses 1-224) are written into emsControl/ems/ems_control_setting.json under the settings key shown for the register in appendix A.
  • Device-backed registers (the PCS telemetry and PCS control blocks) are written into that PCS's device register map file.

Settings registers that are declared in the map but absent from the settings file read as 0 and are created in the file by the first write. Writing 0 to such a register therefore does not "clear" anything — it creates the key.

5. Register map layout

Range Block Access Contents
1-208 EMS control and status mixed operation mode, control mode, status, refresh rate, active function count, and every EMS configuration setting behind the operating modes (see appendix A)
2400-2572 EMS alarm and status words read-only alarm, validity and setpoint status words carried over from the EMS's own map (section 12.5)
2706-3152, 13598-13600, 24669 Preserved EMS registers read-only 50 registers kept at their original addresses: energy, current, voltage, power and frequency totals
25000-32060 Device blocks - 73 units mixed one block per unit: PCS, BMU, meter, AC, UPS and sensor telemetry plus their remote control. The 12 PCS blocks occupy 27025-31668; the remaining units sit below and above that (see appendix C)
32061-32082 Plant aggregates read-only computed on read from the PCS blocks

Per unit, the PCS block contains pcsN__bc* (battery cluster), pcsN__pcs (converter), pcsN__auxiliary, pcsN__ems, pcsN__air_condition, pcsN__fire_detector and pcsN__remote_control (measurements) plus pcsN__control__remote_control (commands). The per-unit addresses are listed in appendix C.

6. EMS system registers

Address Register Type Access Values
1 ems_operation_mode INT16U RW The requested operating mode. See section 8.
2 ems_control_mode INT16U RW (refused) 0 = local_control, 1 = scada_control, 2 = external_control
3 ems_operation_status INT16U RO The mode the EMS is actually running. Same numbering as address 1.
4 control_settings.ems_refresh_rate_hz INT16U RW EMS control loop rate in Hz (delivered value 2)
5 active_function_count INT16U RO Number of operating functions currently enabled

How to use 1 and 3. Write the mode you want to address 1, then poll address 3 until it equals it. Address 3 is written by the EMS control loop after it resolves the request, so it is the only trustworthy confirmation:

  • @3 == @1 → the requested mode is running.
  • @3 stays at the old value → the request was not accepted (see 4.3).
  • @3 == 17 (IDLE) while @1 requested something else → the EMS fell back to idle because it did not register the request.

Observed response time: 0.5-1.1 s.

7. Prerequisites for running an operating mode

An operating mode does nothing at all unless its prerequisites are met. The EMS reports readiness in its log rather than as a fault register, so check these before you write the mode:

Prerequisite Where it comes from Effect if unmet
Control mode is scada_control or external_control device UI (ems_control_mode) every write refused
The function is enabled: functions.<Mode>.enabled = 1 settings register, appendix A mode runs but performs no control action
At least one PCS has general_settings.pcs.pcsN.status = active device UI / settings API no PCS is dispatched
SOC is known for the PCS PCS measurement (appendix C) PCS is treated as unavailable
SOC limits allow the direction: charge needs SOC < max_soc_pct, discharge needs SOC > min_soc_pct general_settings.pcs.pcsN.soc_limits PCS is excluded from dispatch, others still run
Power limits set: general_settings.pcs.pcsN.power_limits.max_charge_kw / max_discharge_kw device UI / settings API the EMS clamps the command to the limit, i.e. 0 kW if unset

When the EMS runs a mode with no eligible PCS it keeps running and reports eligible=NONE in logs/ rather than raising an alarm. Read the PCS measurement registers (SOC, setpoint) to confirm that power is actually flowing.

8. Operating modes

Value Mode What it does Settings block Enabled in the delivered configuration
0 MANUAL runs the manual charge / discharge / stop action from the settings functions.Manual_Operation.* yes
1 ARBITRAGE charges and discharges on the configured price or period schedule functions.Arbitrage.* no
2 PEAK_SHAVING discharges to hold the site import below the threshold functions.Peak_Shaving.* yes
3 VALLEY_FILLING charges inside the configured valley window functions.Valley_Filling.* no
4 SCHEDULED_CHARGE_DISCHARGE follows the configured charge / discharge schedule functions.Scheduled_Charge_Discharge.* no
5 BACKUP handled by the backup controller (grid-mode governor + backup dispatch) functions.Backup.* no
6 BACKUP_PEAK_SHAVING peak shaving while the backup controller holds the grid mode functions.Backup_Peak_Shaving.* no
7 BACKUP_FREQUENCY_REGULATION frequency regulation with backup reserve held functions.Backup_Frequency_Regulation.* no
8 POWER_FACTOR_CORRECTION reactive power to hold the power-factor target functions.Power_Factor_Correction.* no
9 VOLTAGE_SUPPORT reactive power to hold the voltage band functions.Voltage_Support.* no
10 FREQUENCY_REGULATION charges / discharges on frequency deviation functions.Frequency_Regulation.* no
11 ANTI_BACKFLOW limits export at the grid connection point functions.Anti_Backflow.* no
12 MAINTENANCE suspends dispatch; the plant is parked functions.Maintenance.* no enabled key
13 ENERGY_OPTIMIZATION no control strategy in this build - no action functions.Energy_Optimization.* no
14 POWER_NODE_ENERGY_SHARING no control strategy in this build - no action functions.Power_Node_Energy_Sharing.* no
15 GRID_SYNC no control strategy in this build - no action functions.Grid_Sync.* no
16 DYNAMIC_LOAD_BALANCING no control strategy in this build - no action functions.Dynamic_Load_Balancing.* no
17 IDLE no control action (the last setpoint stands) none always available
18 STOP_ALL zeroes every active PCS none always available
19 PAYLOAD_DIAGNOSTIC_TEST diagnostic interlock takes exclusive control none always available

Notes on specific modes:

  • STOP_ALL (18) is the safety stop. It discards pending automatic setpoints and holds every active PCS at 0 kW. It is not gated by an enabled flag. Verified: the PCS setpoint registers went to 0 within 6 s.
  • MAINTENANCE (12) suspends automatic control and parks the plant, but leaves manual commands usable.
  • IDLE (17) is the "no operating mode" state. It issues no power command — the plant keeps whatever setpoint was last applied. Use STOP_ALL when you want zero power, then IDLE to leave the plant under EMS control without an active function.
  • MANUAL (0) runs the manual charge/discharge/stop step from the EMS settings; the stop action forces 0 kW to active PCS.
  • PAYLOAD_DIAGNOSTIC_TEST (19) — formerly DIAGNOSTIC_TEST — is handled by an interlock that takes exclusive control of the BESS before normal dispatch.
  • BACKUP (5), BACKUP_PEAK_SHAVING (6) and BACKUP_FREQUENCY_REGULATION (7) are handled by the backup controller before the mode dispatcher runs: it governs the PQ/VF grid mode and the backup power dispatch. Set functions.Backup.enabled when you rely on them.
  • ENERGY_OPTIMIZATION (13), POWER_NODE_ENERGY_SHARING (14), GRID_SYNC (15), DYNAMIC_LOAD_BALANCING (16) are accepted and reported by address 3, but have no control strategy in this build: the EMS logs "has no control strategy yet" and performs no action.

8.1 Per-mode settings

Each mode reads its parameters from the settings registers named functions.<Mode>.*. The complete list, with addresses, types and delivered values, is in appendix A. Every mode has the same shape:

Setting Purpose
functions.<Mode>.enabled Master enable. 0 = the mode runs but never acts.
functions.<Mode>.soc_limits.min_soc_pct / max_soc_pct SOC window for dispatch
functions.<Mode>.power_caps_kw.charge_cap_kw / discharge_cap_kw Power ceiling for this mode
functions.<Mode>.* (mode specific) Thresholds, deadbands, schedules

Example — Peak Shaving (functions.Peak_Shaving.*): the mode-specific parameters are the import threshold and the power to use when the threshold is exceeded; Frequency Regulation (functions.Frequency_Regulation.*) adds a deadband, droop and actuation point. Read appendix A for the exact names and addresses of the mode you are integrating.

9. Procedures

All procedures assume the map server is at <ems-host>:1540, unit 1.

9.1 Enable external configuration (one-off, by the operator)

Modbus cannot promote itself: address 2 is refused. The operator sets the control mode to scada_control in the device UI. The EMS reads the settings file each cycle, so the change is live within about a second:

  1. Read address 2. 0 means writes are refused.
  2. Operator sets Control mode = SCADA (or External, for section 10).
  3. Poll address 2 until it reads 1 (or 2). Writes are now accepted.

9.2 Start an operating mode

  1. Ensure the control mode allows writes (9.1).
  2. Configure the mode's settings by writing the registers in appendix A for that mode's functions.<Mode>.* block. Write enabled = 1 last.
  3. Write the mode number to address 1.
  4. Poll address 3 until it equals the value written to address 1.

9.3 Stop the running mode safely

  1. Write 18 (STOP_ALL) to address 1. This zeroes the active PCS regardless of mode and prerequisites.
  2. Poll address 3 until it reads 18.
  3. Optionally write 17 (IDLE) to address 1 to leave the plant under EMS control with no function running. Do not rely on IDLE alone to stop power (see section 8).
  4. Confirm on the PCS measurements that power is 0.

9.4 Change from one mode to another

Write the new mode number to address 1 and confirm it on address 3. There is no need to stop the previous mode first: the control loop stops the previous mode's work and starts the new one in the same cycle. The observed switch took 1.0 s.

If you are changing into a mode with different power caps or SOC limits, write those settings before the mode number, otherwise the first control cycle runs with the old limits.

9.5 Sequence, timing and acknowledgement summary

Action Registers Timing Acknowledgement
Configure a mode functions.<Mode>.* immediate, atomic read the register back
Start / change mode @1 = <mode> effect in 0.5-1.1 s @3 equals @1
Stop @1 = 18 ≤ 1 s to status, ≤ 6 s to 0 kW @3 = 18 and PCS setpoint 0
Return to idle @1 = 17 ≤ 1 s @3 = 17
Direct power command bridge @24000 effect in 0.1-3 s PCS setpoint register

There is no queue, no handshake register and no busy flag. The only delays that exist are the two poll periods: the EMS control loop (≈1 s) and the PCS client poll (≈1-3 s), which is why a power command takes up to a few seconds to become visible on the PCS measurement registers.

10. Direct external control of the BESS

Two interfaces can move power. Choose by what you need:

Interface Address Distributed by Use when
Operating modes (section 8) map @1 EMS, using the mode strategy you want the EMS to decide the power
External control bridge :1541 @24000 EMS, split across eligible PCS you need to command the plant power yourself

The bridge is started by the EMS backend as soon as the control mode becomes external_control, and stopped when it changes away. While it runs, the EMS does not execute any operating mode: it hands the PCS over and reports ems_operation_status = IDLE.

10.1 The command register

Item Value
Address 24000 (port 1541, unit 1)
Type unsigned 16-bit
Bit 15 direction: 0 = discharge, 1 = charge
Bits 0-14 magnitude
Scale 10 → 0.1 kW resolution
Range 0 to 32767 raw → 0.0 to 3276.7 kW
Zero stop: all eligible PCS are commanded to 0 kW
Write-back the register keeps the value you wrote; it is not cleared by the bridge

Encoding examples:

Command Raw value to write Hex
0 kW (stop) 0 0x0000
Discharge 25 kW 250 0x00FA
Discharge 50 kW 500 0x01F4
Charge 15 kW 32768 + 150 = 32918 0x8096
Charge 30 kW 32768 + 300 = 33068 0x812C

Do not use two's complement for the sign. The bridge decodes bit 15 as a direction flag with a magnitude in the low bits, so 0xFFCE (two's complement −50) is read as −32718 raw, i.e. −3271.8 kW, which the safety caps will reduce to the plant's configured charge limit.

Addresses other than 24000 on port 1541 return exception 02.

10.2 How the bridge distributes the command

The value you write is a plant setpoint. The bridge splits it every 100 ms:

  1. A PCS is eligible if its settings status is active, its SOC is known and the direction is allowed: charge requires SOC < max_soc_pct, discharge requires SOC > min_soc_pct. A PCS with unknown SOC is never used.
  2. The total is divided equally between the eligible PCS, respecting each unit's power_caps_kw; units that hit their cap release the remainder to the others.
  3. Active but ineligible PCS are explicitly commanded to 0 kW, so a unit that drops out of the SOC window is stopped rather than left at its last setpoint.
  4. If no PCS is eligible the result is 0 kW on every active unit — the plant stops rather than overcharging or over-discharging.

The command is applied to the PCS through the EMS's own command channel, so the PCS also applies its own clamps.

10.3 Confirming execution

There is no acknowledgement register on the bridge. Confirm at the PCS:

What Where
Applied setpoint per unit PCS setpoint register, appendix C (raw, 0.1 kW)
Actual power PCS three_phase_total_active_power_kwh / dc_power_kw
SOC moving in the commanded direction PCS SOC register
Bridge decision logs/external_control_bridge.log: the decode and eligible list

Verified end to end: +50 kW (raw 500) was split 25.0 kW to each of two eligible PCS within 20 s, 30 kW of charge was applied as −15.0 kW on each, and a written 0 kW stopped both.

10.4 Safety behaviour

Situation Behaviour
Communication loss to the controller The bridge holds the last command. Write 0 explicitly, or switch the control mode back to Internal_EMS/local_control from the device UI, which stops the bridge.
Command above the PCS cap Clamped to power_limits / power_caps_kw.
SOC leaves the allowed window That PCS is set to 0 kW immediately; the rest continue.
No eligible PCS Everything active is commanded to 0 kW.
Invalid address Exception 02.
Invalid direction bit pattern Interpreted as sign + magnitude as documented above; magnitudes above 32767 are not expressible.

11. Worked examples

Each example states the registers, the values, the sequence, what to monitor and the expected response. R = read, W = write.

Example 1 — Start Peak Shaving

Prerequisite: control mode = scada_control (operator action).

# Action Register Value
1 R @2 expect 1
2 W functions.Peak_Shaving.enabled 1
3 W functions.Peak_Shaving threshold(s) per site requirement
4 W @1 2
5 R @3 expect 2

Expected response: the EMS starts dispatching Peak Shaving within ~1 s; the PCS setpoint registers show the charge/discharge power the strategy chose. Verified: @3 = 2 within 1.0 s.

Example 2 — Stop Peak Shaving

# Action Register Value
1 W @1 18 (STOP_ALL)
2 R @3 expect 18
3 R PCS setpoint registers expect 0
4 W (optional) @1 17 (IDLE)

Verified: status 18 within 1.0 s, PCS setpoints 0 within 6 s.

Example 3 — Change from Peak Shaving to Frequency Regulation

# Action Register Value
1 W functions.Frequency_Regulation.enabled 1
2 W functions.Frequency_Regulation deadband / droop per site requirement
3 W @1 10
4 R @3 expect 10

No stop is required between modes. Verified: the EMS left FREQUENCY_REGULATION and entered PEAK_SHAVING (and back) with one register write each.

Example 4 — Change from EMS control to direct external power control

# Action Register Value
1 W @1 18 (STOP_ALL); confirm @3 = 18 and PCS 0 kW
2 Operator device UI control mode external_control
3 R @2 expect 2
4 R @3 expect 17 (IDLE, bridge owns the PCS)
5 W bridge @24000 0
6 R PCS setpoint registers expect 0 — then send your first setpoint

Verified: after the switch the bridge was listening on port 1541 within 1 s and the EMS reported IDLE; the EMS stopped executing operating modes.

Example 5 — Charge the BESS at a specified power

Bridge running (external_control). To charge at 30 kW:

# Action Register Value
1 W @24000 (port 1541) 33068 = 0x812C (bit 15 set + 300)
2 R @24000 expect 33068
3 R PCS setpoint registers expect negative values, sum = −30.0 kW
4 R PCS SOC expect slowly rising

Verified: 30 kW of charge was applied as −15.0 kW on each of two eligible PCS (0.1 kW units).

Example 6 — Discharge the BESS at a specified power

# Action Register Value
1 W @24000 (port 1541) 500 = 0x01F4 (bit 15 clear + 500)
2 R PCS setpoint registers expect positive values, sum = +50.0 kW

Verified: each of two eligible PCS received +25.0 kW.

Example 7 — Set power to zero and leave external control

# Action Register Value
1 W @24000 (port 1541) 0
2 R PCS setpoint registers expect 0 on every unit
3 Operator device UI control mode Internal_EMS (local_control)
4 R @2 expect 0 — the bridge is now stopped

Verified: 0 kW on both PCS within 20 s, bridge stopped, port 1541 closed.

Example 8 — Return the EMS to a safe default state

# Action Register Value
1 W bridge @24000 0 (if external control was used)
2 W @1 18 (STOP_ALL)
3 R @3 expect 18; PCS power 0
4 W @1 17 (IDLE)
5 Operator device UI control mode Internal_EMS if external control is no longer needed
6 R @1 / @2 / @3 expect the intended steady state

This is the state the delivered system ships in, except that it ships running Peak Shaving (@1 = 2).

12. Fault handling and troubleshooting

12.1 Modbus exceptions

Code Meaning Likely cause here
01 Illegal function Function code not 3, 6 or 16; or 5 with an out-of-range coil
02 Illegal data address Address 0 or above 32082 on port 1540; on the bridge, address 0 or above 24000
03 Illegal data value Write outside the register width
04 Server failure The map file could not be read; check logs/ems_modbus_server_error.log
11 Gateway target failed to respond You are addressing the EMS through a gateway

12.2 Accepted-looking writes that did nothing

  1. Control mode is local. Address 2 reads 0. Fix: ask the operator to switch the control mode (9.1).
  2. Value not in the enum. The register snapped back. Fix: read the enum in appendix A and rewrite.
  3. Register is read-only. Measurements and ems_operation_status cannot be written.
  4. Mode has no strategy in this build (section 8). Status will follow the value, but no power flows.

12.3 Command accepted, no power flowing

Check Register / file Expected
Function enabled functions.<Mode>.enabled 1
PCS active general_settings.pcs.pcsN.status active
SOC known PCS SOC register, appendix C a plausible percentage, not 0 with an empty battery
SOC window general_settings.pcs.pcsN.soc_limits charge needs SOC < max, discharge needs SOC > min
Power limits general_settings.pcs.pcsN.power_limits non-zero charge/discharge limits
EMS log logs/ the dispatch line names the eligible PCS; eligible=NONE means the SOC gate excluded all of them

12.4 Communication loss

Interface Behaviour Recovery
Map server (1540) Independent of the controller. The EMS keeps running its last mode and the last settings. Reconnect and read @1/@3 to resynchronise.
Bridge (1541) Holds the last command it received. The EMS itself is unaffected. Write 0, or switch the control mode away from external control.
PCS to EMS The PCS drops out of the eligible set and is commanded to 0 kW. No action; it rejoins when SOC/status allow.

12.5 Alarms and faults

Alarms are per unit and read-only: pcsN__bc.alarm* / pcsN__*.fault* flags, pcsN__fire_detector, plus the alarm validity words at 2400-2572. The EMS does not expose an aggregate fault register, so an integrator should poll the PCS alarm flags it cares about, plus ems_operation_status (@3) to detect an unexpected mode change.

13. Known limitations

# Limitation Impact / workaround
1 The control mode (@2) cannot be set over Modbus. Someone with access to the device UI must enable external/SCADA control once.
2 Writing a PCS control register on the map (for example @27324, pcs1's active_power_set_kw) records the value in that PCS's device register map and the register reads back, but the map is not a general pass-through to the hardware: the EMS applies PCS commands through its own sequence executor. For direct power control use the bridge (section 10). Treat the map's PCS control registers as the EMS's internal control surface.
3 plant__ac_power.reporting_pcs_count counts every PCS that returns a reading, including zeros. Do not use it as an "online" indicator; read the PCS voltage/power registers instead.
4 Function codes 1, 2, 4 and 5 are answered with zero data. Use 3, 6 and 16 only.
5 A mode without a control strategy (13-16) is accepted by @1 and reported by @3. Do not treat @3 as proof that power is being controlled; check the PCS.
6 SOC/SOH are whole percent while neighbouring power registers are 0.1 kW on the same device, and pcs1-pcs4 declare a device-wide scale of 0.1. The per-register scale in the device map is authoritative; see section 3.3.

14. Validation report

The procedures in this document were run against the live Docker stack (ems-backend container, map server on port 1540, bridge on port 1541, BESS simulator published on 1501-1515). The EMS was left in its as-found state afterwards; the settings file checksum returned to its original value (5ad3e4cabc7927265ca7d1a821e6c946).

Status of this section. This run was performed against an earlier map. The map was regenerated on 2026-10-07 and now declares 6,385 registers ending at @32082; the addresses in the table below have been re-pointed to that map, but the checks themselves have not been re-run. The EMS served a different map at the time of writing (it was serving an earlier map). The settings checksum quoted above also predates the register_map re-stamp and no longer matches the current settings file. Re-run tools/ems_modbus_validation.py --phase reads after the new map is deployed before quoting any result in this section.

Check Result
Connect to the map server, read @1..@5 PASS — [2, 0, 2, 2, 1]
Read the EMS running-mode register (@3) PASS — PEAK_SHAVING
Requested mode (@1) matches the settings file PASS — @1 = 2, settings PEAK_SHAVING
Read plant aggregates (@32061..@32082) PASS — computed on read
Read PCS telemetry: SOC, SOH, power, voltage, current, frequency PASS — pcs1 SOC 46 %, pcs2 SOC 48 %, SOH 95 %, 50.00 Hz
Unmapped address inside the map PASS — reads 0
Out-of-range address (@32083) PASS — exception 02
Address 0 PASS — exception 02
Unsupported function code (0x2A) PASS — exception 01
Write while control mode is local PASS — refused, register unchanged
Write the control-mode register (@2) PASS — refused (a device-side operator action)
Write a read-only register (@3) PASS — refused
Configure a mode setting (@4 = 3) PASS — accepted, persisted in the settings file
Start FREQUENCY_REGULATION (@1 = 10) PASS — @3 = 10 in 1.0 s
Change to PEAK_SHAVING (@1 = 2) PASS — @3 = 2 in 1.0 s
Reject an invalid mode (@1 = 99) PASS — register snapped back, settings untouched
Stop all (@1 = 18) PASS — @3 = 18 in 0.5 s, PCS setpoints 0
Return to idle (@1 = 17) PASS — @3 = 17 in 0.5 s
Switch control mode to external_control PASS — @2 = 2, bridge listening within 1 s
Bridge command register accepts +50 kW PASS — read back 500
PCS units execute the discharge command PASS — 25.0 kW on each of two units
PCS units execute the charge command PASS — −15.0 kW on each
Zero command stops the PCS PASS — 0 on both units
Bridge rejects an out-of-range address PASS — exception 02
Map accepts a PCS setpoint write in external control PASS — @27324 read back
Restore the as-found state PASS — @1 = 2, @2 = 0, bridge stopped, settings checksum identical

Totals: 36 checks, 36 passed, 0 failed, 0 skipped — 15 read, protocol and write-rule checks, then 21 operating-mode, direct-control and bridge checks.

One timing detail is worth knowing when you drive these procedures yourself: after the control mode returns to local control, @3 briefly still reports the mode the EMS was last running (IDLE, written by the stop in the previous step) before the EMS re-reads the settings file and resumes PEAK_SHAVING. Both @1 and the settings file were already correct at that moment; @3 settled to 2 within a few seconds. Treat @3 as eventually consistent with the settings file — poll it rather than reading it once immediately after a change.

Reproduce with the harness described in appendix F.

15. Revision and sources

Item Value
Register map source EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_register_full.json
Settings source EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_control_setting.json
Map server EMS_template_codes/ems_modbus_server_dynamic_nofilter_v14.py
External control bridge EnergySyc_EMS_ES100Cx12S/ems_external_control_bridge.py
EMS control loop EnergySyc_EMS_ES100Cx12S/ems_main.py
Table generator EnergySyc_EMS_ES100Cx12S/tools/generate_external_integration_guide.py

Regenerate this document after changing the register map or the settings file:

cd EnergySyc_EMS_ES100Cx12S
python3 tools/generate_external_integration_guide.py

Appendix A: EMS settings registers

Every read-write EMS setting, with the settings key it maps to and the value this configuration delivers. Write these to configure an operating mode; the mode reads them from the settings file on its next control cycle. Type and register-width follow section 3.2.

Setting Address Type Regs Access Delivered value / enum
ems_operation_mode @1 INT16U 1 RW 0 = MANUAL, 1 = ARBITRAGE, 2 = PEAK_SHAVING, 3 = VALLEY_FILLING, 4 = SCHEDULED_CHARGE_DISCHARGE, 5 = BACKUP, 6 = BACKUP_PEAK_SHAVING, 7 = BACKUP_FREQUENCY_REGULATION, 8 = POWER_FACTOR_CORRECTION, 9 = VOLTAGE_SUPPORT, 10 = FREQUENCY_REGULATION, 11 = ANTI_BACKFLOW, 12 = MAINTENANCE, 13 = ENERGY_OPTIMIZATION, 14 = POWER_NODE_ENERGY_SHARING, 15 = GRID_SYNC, 16 = DYNAMIC_LOAD_BALANCING, 17 = IDLE, 18 = STOP_ALL, 19 = PAYLOAD_DIAGNOSTIC_TEST
ems_control_mode @2 INT16U 1 RW 0 = local_control, 1 = scada_control, 2 = external_control
ems_operation_status @3 INT16U 1 RO 0 = MANUAL, 1 = ARBITRAGE, 2 = PEAK_SHAVING, 3 = VALLEY_FILLING, 4 = SCHEDULED_CHARGE_DISCHARGE, 5 = BACKUP, 6 = BACKUP_PEAK_SHAVING, 7 = BACKUP_FREQUENCY_REGULATION, 8 = POWER_FACTOR_CORRECTION, 9 = VOLTAGE_SUPPORT, 10 = FREQUENCY_REGULATION, 11 = ANTI_BACKFLOW, 12 = MAINTENANCE, 13 = ENERGY_OPTIMIZATION, 14 = POWER_NODE_ENERGY_SHARING, 15 = GRID_SYNC, 16 = DYNAMIC_LOAD_BALANCING, 17 = IDLE, 18 = STOP_ALL, 19 = PAYLOAD_DIAGNOSTIC_TEST
control_settings.ems_refresh_rate_hz @4 INT16U 1 RW 2
active_function_count @5 INT16U 1 RO {'metadata': {'schema_version': '20251020.113351', 'file_type': None, 'generated_at': '2026-10-06T18:57:59.165Z', 'source_system': None, 'gateway_id': 'GTW-ems100CX', 'device_id': None, 'description': None}, 'rom': {'restapi': {'enabled': True, 'scada_url': '', 'api_key': '', 'polling_interval_ms': None}, 'soap': {'enabled': True, 'scada_url': '', 'api_key': '', 'polling_interval_ms': None}, 'iccp': {'enabled': True, 'scada_url': '', 'api_key': '', 'polling_interval_ms': None}}, 'device': {'device_id': '', 'gateway_id': 'GTW-ems100CX', 'debug_enabled': False, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 5, 'poll_interval_ms': 3000, 'save_interval_ms': 6000, 'log_level': 'INFO', 'ems_key': 'devicetab', 'endianness': 'big', 'scale': 7.45, 'datatype': 'BITMAP32'}}, 'diagnostic_test_mode': {'Selected_radio_button_name': None, 'mode_number': None, 'test_status_active': False, 'date-time': '', 'min_soc': 45, 'max_soc': 55, 'number_of_cycles': 1, 'multi_select': {'modes': [], 'scheduled_time': ''}, 'soh_estimation': {'min_soc': 20, 'max_soc': 100, 'reference_capacity_kwh': 215, 'number_of_cycles': 1}, 'soc_validation': {'min_soc': 0, 'max_soc': 100, 'tolerance_pct': 2, 'settle_time_sec': 60}, 'cell_balancing_test': {'min_soc': 45, 'max_soc': 55, 'number_of_cycles': 1}, 'internal_resistance_test': {'min_soc': 20, 'max_soc': 80, 'pulse_current_a': 50, 'pulse_duration_sec': 10, 'pulse_direction': 'discharge', 'settle_time_sec': 5, 'rest_time_sec': 5, 'number_of_pulses': 3, 'max_pack_resistance_mohm': 50, 'max_cell_resistance_mohm': 10, 'max_resistance_deviation_pct': 20, 'min_pack_voltage_v': 20, 'max_pack_voltage_v': 35, 'max_cell_temp_c': 45, 'cell_voltage_start_register': 1860, 'cell_voltage_count': 8, 'cell_voltage_scale_mv': 1, 'dc_current_register': 1801, 'dc_current_scale_a': 0.1}, 'thermal_response_test': {'min_soc': 20, 'max_soc': 80, 'target_temp_c': 45, 'duration_sec': 300, 'heat_load_kw': 50, 'max_temp_c': 55, 'poll_interval_sec': 10, 'temp_register': 1500, 'temp_encoding': 'float32', 'temp_scale': 1}, 'ocv_check': {'min_soc': 0, 'max_soc': 100, 'rest_time_sec': 60, 'tolerance_v': 0.05}, 'self_discharge_test': {'min_soc': 0, 'max_soc': 100, 'duration_hours': 72, 'max_discharge_pct': 2, 'demo_wait_seconds': 60}, 'grid_synchronization_test': {'frequency_hz': 50, 'voltage_v': 400, 'phase_angle_deg': 0, 'sync_timeout_sec': 60}, 'efficiency_test': {'min_power_kw': 10, 'max_power_kw': 100, 'power_step_kw': 10, 'duration_sec': 60}, 'harmonics_thd_test': {'min_power_kw': 20, 'max_thd_pct': 5, 'duration_sec': 30}, 'response_time_test': {'setpoint_kw': 50, 'max_response_time_ms': 200, 'settling_tolerance_pct': 2}, 'isolation_test': {'test_voltage_v': 500, 'min_insulation_resistance_mohm': 1, 'duration_sec': 60}, 'cooling_fan_pump_test': {'duration_sec': 60, 'min_flow_rate_lpm': None, 'expected_rpm': None}, 'heat_exchanger_test': {'inlet_temp_c': 40, 'outlet_temp_c': 30, 'duration_sec': 120}, 'heater_functionality_test': {'target_temp_c': 35, 'max_power_kw': 10, 'duration_sec': 120}, 'breaker_contactor_test': {'number_of_cycles': 3, 'close_delay_ms': 100, 'open_delay_ms': 100}, 'fuse_integrity_check': {'continuity_threshold_ohm': 1, 'test_current_a': None}, 'fire_suppression_diagnostic': {'test_duration_sec': 30, 'agent_pressure_bar': None}, 'insulation_resistance_test': {'test_voltage_v': 500, 'min_resistance_mohm': 1, 'duration_sec': 60}, 'can_modbus_communication_test': {'protocol': 'modbus-tcp', 'packet_count': 100, 'timeout_ms': 1000}, 'scada_ems_bms_command_flow_test': {'command': 'power_setpoint', 'timeout_ms': 2000, 'verify_response': True}, 'alarm_event_reporting_test': {'alarm_code': None, 'expected_report_ms': 1000, 'verify_ack': True}, 'general_functionality_test': {'duration_sec': 300, 'checks': ['startup', 'shutdown', 'idle', 'charge', 'discharge']}, 'charge_discharge_cycling_test': {'min_soc': 0, 'max_soc': 100, 'number_of_cycles': 3, 'power_kw': 50}, 'peak_shaving_simulation': {'peak_threshold_kw': 80, 'duration_sec': 300, 'power_kw': 50}, 'black_start_test': {'min_soc': 50, 'ramp_up_time_sec': 30, 'target_power_kw': 50}, 'ffr_fcrd_test': {'frequency_hz': 50, 'deadband_hz': 0.05, 'duration_sec': 300}, 'multiple_schedule_tests': {'schedules': [], 'number_of_cycles': 1}, 'ffr_01_frequency_measurement_accuracy': {'frequency_hz': 50, 'tolerance_hz': 0.01, 'duration_sec': 60}, 'ffr_02_measurement_filter_latency': {'max_latency_ms': 50, 'duration_sec': 60}, 'ffr_03_time_sync_accuracy': {'max_offset_ms': 1, 'source': 'NTP'}, 'ffr_04_trigger_threshold_deadband': {'under_freq_hz': 49.8, 'over_freq_hz': 50.2, 'deadband_hz': 0.05}, 'ffr_05_activation_time': {'t90_ms': 1000, 't100_ms': 2000, 'setpoint_pct': 100}, 'ffr_06_initial_ramp_rate': {'min_ramp_rate_kw_s': 50, 'duration_sec': 30}, 'ffr_07_droop_gain_accuracy': {'droop_pct': 5, 'tolerance_pct': 2}, 'ffr_08_delivery_magnitude_accuracy': {'setpoint_pct': 100, 'tolerance_pct': 2}, 'ffr_09_hold_sustain_duration': {'hold_duration_sec': 900, 'setpoint_pct': 100}, 'ffr_10_energy_availability': {'min_soc_reserve_pct': 20, 'energy_required_kwh': 10}, 'ffr_11_thermal_soc_derating': {'max_temp_c': 45, 'min_soc_pct': 10}, 'ffr_12_ems_pcs_command_latency': {'max_latency_ms': 200, 'sample_count': 100}, 'ffr_13_recovery_to_baseline': {'recovery_ramp_kw_s': 50, 'oscillation_tolerance_pct': 2}, 'ffr_14_bidirectional_behavior': {'under_freq_hz': 49.8, 'over_freq_hz': 50.2}, 'ffr_15_saturation_clipping': {'max_power_kw': 100, 'min_power_kw': -100}, 'ffr_16_anti_islanding_ride_through': {'ride_through_ms': 500, 'grid_code': 'EN50549'}, 'ffr_17_comms_loss_fail_safe': {'fail_safe_power_kw': 0, 'timeout_ms': 2000}, 'ffr_18_telemetry_settlement': {'sample_rate_hz': 10, 'send_frequency_ms': 1000}, 'ffr_19_event_logging_evidence': {'log_format': 'jsonl', 'required_fields': ['timestamp', 'frequency_hz', 'power_kw']}, 'ffr_20_prequalification_replay': {'profile_file': '', 'duration_sec': 1800}, 'ffr_21_aggregation_coordination': {'unit_count': 12, 'response_delay_ms': 100}, 'ffr_22_metering_path_accuracy': {'tolerance_pct': 0.5, 'meter_id': None}, 'ffr_23_cyber_controls': {'enable_role': 'operator', 'disable_role': 'operator', 'require_confirm': True}}, 'ems_operation_mode': 'IDLE', 'ems_control_mode': 'Internal_EMS', 'ems_operation_status': 'IDLE', 'ui_state': {'active_tab': 'operation', 'radio_selected_function': 'IDLE', 'last_applied_timestamp': '2026-10-06T18:57:59.165Z', 'last_modified_by': 'ems_admin@gess.se'}, 'general_settings': {'pcs': {'pcs1': {'status': 'active', 'grid_mode': 'PQ', 'BESS_name': 'BESS300', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'reactive_power_limits': {'max_capacitive_kvar': None, 'max_inductive_kvar': None}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1501, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_1', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-001', 'model': 'epcs105', 'register_map': {'model': 'SINEXCEL_PWS1_250K', 'map_file': 'pcs/pcs1/pcs_register_full___sinexcel_pws1_250k.json', 'ems_block': 'pcs1', 'ems_base_address': 27025, 'ems_end_address': 27411, 'register_count': 387, 'category_prefix': 'pcs1', 'telemetry_categories': ['pcs1__bc', 'pcs1__bc_switch_quantities', 'pcs1__pcs', 'pcs1__bc_battery_cluster', 'pcs1__air_condition', 'pcs1__fire_detector', 'pcs1__auxiliary', 'pcs1__ems', 'pcs1__remote_control'], 'control_categories': ['pcs1__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs1/pcs_register_full.json'}}, 'pcs2': {'status': 'active', 'grid_mode': 'PQ', 'BESS_name': 'BESS350', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'reactive_power_limits': {'max_capacitive_kvar': None, 'max_inductive_kvar': None}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1502, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_2', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-002', 'model': 'epcs105', 'register_map': {'model': 'SINEXCEL_PWS1_250K', 'map_file': 'pcs/pcs2/pcs_register_full___sinexcel_pws1_250k.json', 'ems_block': 'pcs2', 'ems_base_address': 28573, 'ems_end_address': 28959, 'register_count': 387, 'category_prefix': 'pcs2', 'telemetry_categories': ['pcs2__bc', 'pcs2__bc_switch_quantities', 'pcs2__pcs', 'pcs2__bc_battery_cluster', 'pcs2__air_condition', 'pcs2__fire_detector', 'pcs2__auxiliary', 'pcs2__ems', 'pcs2__remote_control'], 'control_categories': ['pcs2__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs2/pcs_register_full.json'}}, 'pcs3': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS400', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1503, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_3', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-003', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs3/pcs_register_full___epcs105.json', 'ems_block': 'pcs3', 'ems_base_address': 28960, 'ems_end_address': 29346, 'register_count': 387, 'category_prefix': 'pcs3', 'telemetry_categories': ['pcs3__bc', 'pcs3__bc_switch_quantities', 'pcs3__pcs', 'pcs3__bc_battery_cluster', 'pcs3__air_condition', 'pcs3__fire_detector', 'pcs3__auxiliary', 'pcs3__ems', 'pcs3__remote_control'], 'control_categories': ['pcs3__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs3/pcs_register_full.json'}}, 'pcs4': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS409', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1504, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_4', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-004', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs4/pcs_register_full___epcs105.json', 'ems_block': 'pcs4', 'ems_base_address': 29347, 'ems_end_address': 29733, 'register_count': 387, 'category_prefix': 'pcs4', 'telemetry_categories': ['pcs4__bc', 'pcs4__bc_switch_quantities', 'pcs4__pcs', 'pcs4__bc_battery_cluster', 'pcs4__air_condition', 'pcs4__fire_detector', 'pcs4__auxiliary', 'pcs4__ems', 'pcs4__remote_control'], 'control_categories': ['pcs4__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs4/pcs_register_full.json'}}, 'pcs5': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS419', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1505, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_5', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-005', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs5/pcs_register_full___epcs105.json', 'ems_block': 'pcs5', 'ems_base_address': 29734, 'ems_end_address': 30120, 'register_count': 387, 'category_prefix': 'pcs5', 'telemetry_categories': ['pcs5__bc', 'pcs5__bc_switch_quantities', 'pcs5__pcs', 'pcs5__bc_battery_cluster', 'pcs5__air_condition', 'pcs5__fire_detector', 'pcs5__auxiliary', 'pcs5__ems', 'pcs5__remote_control'], 'control_categories': ['pcs5__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs5/pcs_register_full.json'}}, 'pcs6': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS206', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1506, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_6', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-006', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs6/pcs_register_full___epcs105.json', 'ems_block': 'pcs6', 'ems_base_address': 30121, 'ems_end_address': 30507, 'register_count': 387, 'category_prefix': 'pcs6', 'telemetry_categories': ['pcs6__bc', 'pcs6__bc_switch_quantities', 'pcs6__pcs', 'pcs6__bc_battery_cluster', 'pcs6__air_condition', 'pcs6__fire_detector', 'pcs6__auxiliary', 'pcs6__ems', 'pcs6__remote_control'], 'control_categories': ['pcs6__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs6/pcs_register_full.json'}}, 'pcs7': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS500', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1507, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_7', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-007', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs7/pcs_register_full___epcs105.json', 'ems_block': 'pcs7', 'ems_base_address': 30508, 'ems_end_address': 30894, 'register_count': 387, 'category_prefix': 'pcs7', 'telemetry_categories': ['pcs7__bc', 'pcs7__bc_switch_quantities', 'pcs7__pcs', 'pcs7__bc_battery_cluster', 'pcs7__air_condition', 'pcs7__fire_detector', 'pcs7__auxiliary', 'pcs7__ems', 'pcs7__remote_control'], 'control_categories': ['pcs7__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs7/pcs_register_full.json'}}, 'pcs8': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS700', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1508, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_8', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-008', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs8/pcs_register_full___epcs105.json', 'ems_block': 'pcs8', 'ems_base_address': 30895, 'ems_end_address': 31281, 'register_count': 387, 'category_prefix': 'pcs8', 'telemetry_categories': ['pcs8__bc', 'pcs8__bc_switch_quantities', 'pcs8__pcs', 'pcs8__bc_battery_cluster', 'pcs8__air_condition', 'pcs8__fire_detector', 'pcs8__auxiliary', 'pcs8__ems', 'pcs8__remote_control'], 'control_categories': ['pcs8__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs8/pcs_register_full.json'}}, 'pcs9': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS708', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1509, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_9', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-009', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs9/pcs_register_full___epcs105.json', 'ems_block': 'pcs9', 'ems_base_address': 31282, 'ems_end_address': 31668, 'register_count': 387, 'category_prefix': 'pcs9', 'telemetry_categories': ['pcs9__bc', 'pcs9__bc_switch_quantities', 'pcs9__pcs', 'pcs9__bc_battery_cluster', 'pcs9__air_condition', 'pcs9__fire_detector', 'pcs9__auxiliary', 'pcs9__ems', 'pcs9__remote_control'], 'control_categories': ['pcs9__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs9/pcs_register_full.json'}}, 'pcs10': {'status': 'active', 'grid_mode': 'PQ', 'BESS_name': 'BESS10', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1510, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_10', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-010', 'model': 'epcs105', 'register_map': {'model': 'SINEXCEL_PWS1_250K', 'map_file': 'pcs/pcs10/pcs_register_full___sinexcel_pws1_250k.json', 'ems_block': 'pcs10', 'ems_base_address': 27412, 'ems_end_address': 27798, 'register_count': 387, 'category_prefix': 'pcs10', 'telemetry_categories': ['pcs10__bc', 'pcs10__bc_switch_quantities', 'pcs10__pcs', 'pcs10__bc_battery_cluster', 'pcs10__air_condition', 'pcs10__fire_detector', 'pcs10__auxiliary', 'pcs10__ems', 'pcs10__remote_control'], 'control_categories': ['pcs10__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs10/pcs_register_full.json'}}, 'pcs11': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS12', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P4W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1511, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_11', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-011', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs11/pcs_register_full___epcs105.json', 'ems_block': 'pcs11', 'ems_base_address': 27799, 'ems_end_address': 28185, 'register_count': 387, 'category_prefix': 'pcs11', 'telemetry_categories': ['pcs11__bc', 'pcs11__bc_switch_quantities', 'pcs11__pcs', 'pcs11__bc_battery_cluster', 'pcs11__air_condition', 'pcs11__fire_detector', 'pcs11__auxiliary', 'pcs11__ems', 'pcs11__remote_control'], 'control_categories': ['pcs11__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs11/pcs_register_full.json'}}, 'pcs12': {'status': 'inactive', 'grid_mode': 'PQ', 'BESS_name': 'BESS45', 'rated_power_kw': 100, 'rated_energy_kwh': 215, 'soc_limits': {'min_soc_pct': 10, 'max_soc_pct': 80}, 'power_limits': {'max_charge_kw': 100, 'max_discharge_kw': 100}, 'grid_connection': {'ac_nominal_voltage_v': 400, 'frequency_hz': 50, 'phase_type': '3P3W'}, 'communication': {'protocol': 'modbus-tcp', 'ip_address': '', 'port': 502, 'rtu_or_can': None}, 'device': {'ip': 'bess-simulator-backend', 'port': 1512, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems_12', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'PCS-012', 'model': 'epcs105', 'register_map': {'model': 'EPCS105', 'map_file': 'pcs/pcs12/pcs_register_full___epcs105.json', 'ems_block': 'pcs12', 'ems_base_address': 28186, 'ems_end_address': 28572, 'register_count': 387, 'category_prefix': 'pcs12', 'telemetry_categories': ['pcs12__bc', 'pcs12__bc_switch_quantities', 'pcs12__pcs', 'pcs12__bc_battery_cluster', 'pcs12__air_condition', 'pcs12__fire_detector', 'pcs12__auxiliary', 'pcs12__ems', 'pcs12__remote_control'], 'control_categories': ['pcs12__control__remote_control'], 'control_register_count': 12, 'control_registers': ['start_stop_command', 'active_power_set_kw', 'start_stop_control_item', 'operation_mode_setting_item', 'scheduling_mode_item', 'pcs_switch_control_valid_when_8002_register_value_is_2_item', 'pcs_power_control_valid_when_8002_register_value_is_2_kw', 'pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item', 'ems_time_setting_item', 'ems_reset_pcs_item', 'ems_reset_bms_item', 'mode_pq_vf_command_item'], 'map_template': 'pcs/pcs12/pcs_register_full.json'}}}, 'fss': {'fss1': {'status': 'inactive', 'type': 'aerosol', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1518, 'unit_id': 40, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'fss', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'FIRE-FIGHTING-001', 'model': 'fss1', 'register_map': {'model': 'FSS_STD', 'map_file': 'fire_safety_system/fss1/fss_register_full___fss_std.json', 'ems_block': 'fss1', 'ems_base_address': 26390, 'ems_end_address': 26459, 'register_count': 70, 'category_prefix': 'fss1', 'telemetry_categories': ['fss1__sensors', 'fss1__status', 'fss1__alarms_counters', 'fss1__io', 'fss1__communication'], 'control_categories': ['fss1__control__setpoints', 'fss1__control__io', 'fss1__control__commands'], 'control_register_count': 22, 'control_registers': ['gas_pre_alarm_ppm', 'gas_alarm_ppm', 'smoke_pre_alarm_obscuration_percent', 'smoke_alarm_obscuration_percent', 'heat_pre_alarm_temp_c', 'heat_alarm_temp_c', 'release_delay_s', 'discharge_duration_s', 'cross_zone_logic', 'manual_release_enable', 'inhibit_release', 'abort_enabled', 'hush_duration_s', 'auto_reset_enabled', 'sounder_command', 'strobe_enable', 'command_system_reset', 'command_acknowledge', 'command_silence_sounder', 'command_manual_release', 'command_inhibit_toggle', 'command_test_mode'], 'map_template': 'fire_safety_system/fss1/fss_register_full.json'}}}, 'ac_units': {'ac1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 9, 'poll_interval_ms': 3000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_1', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-001', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac1/ac_register_full___ac_std.json', 'ems_block': 'ac1', 'ems_base_address': 25000, 'ems_end_address': 25084, 'register_count': 85, 'category_prefix': 'ac1', 'telemetry_categories': ['ac1__temperatures', 'ac1__pressures', 'ac1__humidity', 'ac1__status', 'ac1__alarms', 'ac1__power', 'ac1__runtime', 'ac1__io', 'ac1__communication'], 'control_categories': ['ac1__control__setpoints', 'ac1__control__fan', 'ac1__control__mode', 'ac1__control__io', 'ac1__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac1/ac_register_full.json'}}, 'ac2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 21, 'poll_interval_ms': 3000, 'save_interval_ms': 15000, 'log_level': 'CRITICAL', 'ems_key': 'ac_2', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-002', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac2/ac_register_full___ac_std.json', 'ems_block': 'ac2', 'ems_base_address': 25085, 'ems_end_address': 25169, 'register_count': 85, 'category_prefix': 'ac2', 'telemetry_categories': ['ac2__temperatures', 'ac2__pressures', 'ac2__humidity', 'ac2__status', 'ac2__alarms', 'ac2__power', 'ac2__runtime', 'ac2__io', 'ac2__communication'], 'control_categories': ['ac2__control__setpoints', 'ac2__control__fan', 'ac2__control__mode', 'ac2__control__io', 'ac2__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac2/ac_register_full.json'}}, 'ac3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 47, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_3', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-003', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac3/ac_register_full___ac_std.json', 'ems_block': 'ac3', 'ems_base_address': 25170, 'ems_end_address': 25254, 'register_count': 85, 'category_prefix': 'ac3', 'telemetry_categories': ['ac3__temperatures', 'ac3__pressures', 'ac3__humidity', 'ac3__status', 'ac3__alarms', 'ac3__power', 'ac3__runtime', 'ac3__io', 'ac3__communication'], 'control_categories': ['ac3__control__setpoints', 'ac3__control__fan', 'ac3__control__mode', 'ac3__control__io', 'ac3__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac3/ac_register_full.json'}}, 'ac4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_4', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-004', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac4/ac_register_full___ac_std.json', 'ems_block': 'ac4', 'ems_base_address': 25255, 'ems_end_address': 25339, 'register_count': 85, 'category_prefix': 'ac4', 'telemetry_categories': ['ac4__temperatures', 'ac4__pressures', 'ac4__humidity', 'ac4__status', 'ac4__alarms', 'ac4__power', 'ac4__runtime', 'ac4__io', 'ac4__communication'], 'control_categories': ['ac4__control__setpoints', 'ac4__control__fan', 'ac4__control__mode', 'ac4__control__io', 'ac4__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac4/ac_register_full.json'}}, 'ac5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ac_5', 'endianness': 'little', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-005', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac5/ac_register_full___ac_std.json', 'ems_block': 'ac5', 'ems_base_address': 25340, 'ems_end_address': 25424, 'register_count': 85, 'category_prefix': 'ac5', 'telemetry_categories': ['ac5__temperatures', 'ac5__pressures', 'ac5__humidity', 'ac5__status', 'ac5__alarms', 'ac5__power', 'ac5__runtime', 'ac5__io', 'ac5__communication'], 'control_categories': ['ac5__control__setpoints', 'ac5__control__fan', 'ac5__control__mode', 'ac5__control__io', 'ac5__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac5/ac_register_full.json'}}, 'ac6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1516, 'unit_id': 15, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'DEBUG', 'ems_key': 'ac_6', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'AC-UNIT-006', 'model': 'ACM1', 'register_map': {'model': 'AC_STD', 'map_file': 'air_condition_unit/ac6/ac_register_full___ac_std.json', 'ems_block': 'ac6', 'ems_base_address': 25425, 'ems_end_address': 25509, 'register_count': 85, 'category_prefix': 'ac6', 'telemetry_categories': ['ac6__temperatures', 'ac6__pressures', 'ac6__humidity', 'ac6__status', 'ac6__alarms', 'ac6__power', 'ac6__runtime', 'ac6__io', 'ac6__communication'], 'control_categories': ['ac6__control__setpoints', 'ac6__control__fan', 'ac6__control__mode', 'ac6__control__io', 'ac6__control__commands'], 'control_register_count': 16, 'control_registers': ['cooling_setpoint_c', 'heating_setpoint_c', 'supply_air_setpoint_c', 'humidity_setpoint_percent', 'deadband_c', 'fan_speed_percent', 'fan_mode', 'system_mode', 'occupancy_mode', 'digital_output_1_command', 'digital_output_2_command', 'analog_output_1_percent', 'analog_output_2_percent', 'command_on_off', 'command_reset_alarms', 'command_force_defrost'], 'map_template': 'air_condition_unit/ac6/ac_register_full.json'}}}, 'cooling_unit': {'cooling1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1517, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'cooling', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'LIQUID-COOLING-001', 'model': 'CL01', 'register_map': {'model': 'COOL_STD', 'map_file': 'liquid_cooling_unit/cooling1/cooling_register_full___cool_std.json', 'ems_block': 'cooling1', 'ems_base_address': 26968, 'ems_end_address': 27024, 'register_count': 57, 'category_prefix': 'cooling1', 'telemetry_categories': ['cooling1__temperatures', 'cooling1__flow_pressure', 'cooling1__status', 'cooling1__alarms', 'cooling1__power', 'cooling1__runtime', 'cooling1__communication'], 'control_categories': ['cooling1__control__setpoints', 'cooling1__control__mode'], 'control_register_count': 5, 'control_registers': ['setpoint_temp_c', 'min_temp_limit_c', 'max_temp_limit_c', 'operating_mode', 'setpoint_temp_apply'], 'map_template': 'liquid_cooling_unit/cooling1/cooling_register_full.json'}}}, 'solar_meters': {'solar_meter1': {'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1514, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'status': 'active', 'device_id': 'SOLAR-METER-001', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter1/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter1', 'ems_base_address': 31684, 'ems_end_address': 31707, 'register_count': 24, 'category_prefix': 'solar_meter1', 'telemetry_categories': ['solar_meter1__alarms', 'solar_meter1__energies', 'solar_meter1__currents', 'solar_meter1__voltages', 'solar_meter1__power', 'solar_meter1__frequency', 'solar_meter1__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter1/solarMeter_register_full.json'}}, 'solar_meter2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-002', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter2/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter2', 'ems_base_address': 31780, 'ems_end_address': 31803, 'register_count': 24, 'category_prefix': 'solar_meter2', 'telemetry_categories': ['solar_meter2__alarms', 'solar_meter2__energies', 'solar_meter2__currents', 'solar_meter2__voltages', 'solar_meter2__power', 'solar_meter2__frequency', 'solar_meter2__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter2/solarMeter_register_full.json'}}, 'solar_meter3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 3, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-003', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter3/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter3', 'ems_base_address': 31804, 'ems_end_address': 31827, 'register_count': 24, 'category_prefix': 'solar_meter3', 'telemetry_categories': ['solar_meter3__alarms', 'solar_meter3__energies', 'solar_meter3__currents', 'solar_meter3__voltages', 'solar_meter3__power', 'solar_meter3__frequency', 'solar_meter3__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter3/solarMeter_register_full.json'}}, 'solar_meter4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 4, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-004', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter4/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter4', 'ems_base_address': 31828, 'ems_end_address': 31851, 'register_count': 24, 'category_prefix': 'solar_meter4', 'telemetry_categories': ['solar_meter4__alarms', 'solar_meter4__energies', 'solar_meter4__currents', 'solar_meter4__voltages', 'solar_meter4__power', 'solar_meter4__frequency', 'solar_meter4__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter4/solarMeter_register_full.json'}}, 'solar_meter5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 5, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-005', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter5/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter5', 'ems_base_address': 31852, 'ems_end_address': 31875, 'register_count': 24, 'category_prefix': 'solar_meter5', 'telemetry_categories': ['solar_meter5__alarms', 'solar_meter5__energies', 'solar_meter5__currents', 'solar_meter5__voltages', 'solar_meter5__power', 'solar_meter5__frequency', 'solar_meter5__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter5/solarMeter_register_full.json'}}, 'solar_meter6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 6, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-006', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter6/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter6', 'ems_base_address': 31876, 'ems_end_address': 31899, 'register_count': 24, 'category_prefix': 'solar_meter6', 'telemetry_categories': ['solar_meter6__alarms', 'solar_meter6__energies', 'solar_meter6__currents', 'solar_meter6__voltages', 'solar_meter6__power', 'solar_meter6__frequency', 'solar_meter6__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter6/solarMeter_register_full.json'}}, 'solar_meter7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 7, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-007', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter7/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter7', 'ems_base_address': 31900, 'ems_end_address': 31923, 'register_count': 24, 'category_prefix': 'solar_meter7', 'telemetry_categories': ['solar_meter7__alarms', 'solar_meter7__energies', 'solar_meter7__currents', 'solar_meter7__voltages', 'solar_meter7__power', 'solar_meter7__frequency', 'solar_meter7__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter7/solarMeter_register_full.json'}}, 'solar_meter8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-008', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter8/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter8', 'ems_base_address': 31924, 'ems_end_address': 31947, 'register_count': 24, 'category_prefix': 'solar_meter8', 'telemetry_categories': ['solar_meter8__alarms', 'solar_meter8__energies', 'solar_meter8__currents', 'solar_meter8__voltages', 'solar_meter8__power', 'solar_meter8__frequency', 'solar_meter8__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter8/solarMeter_register_full.json'}}, 'solar_meter9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-009', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter9/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter9', 'ems_base_address': 31948, 'ems_end_address': 31971, 'register_count': 24, 'category_prefix': 'solar_meter9', 'telemetry_categories': ['solar_meter9__alarms', 'solar_meter9__energies', 'solar_meter9__currents', 'solar_meter9__voltages', 'solar_meter9__power', 'solar_meter9__frequency', 'solar_meter9__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter9/solarMeter_register_full.json'}}, 'solar_meter10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 10, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-010', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter10/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter10', 'ems_base_address': 31708, 'ems_end_address': 31731, 'register_count': 24, 'category_prefix': 'solar_meter10', 'telemetry_categories': ['solar_meter10__alarms', 'solar_meter10__energies', 'solar_meter10__currents', 'solar_meter10__voltages', 'solar_meter10__power', 'solar_meter10__frequency', 'solar_meter10__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter10/solarMeter_register_full.json'}}, 'solar_meter11': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 11, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-011', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter11/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter11', 'ems_base_address': 31732, 'ems_end_address': 31755, 'register_count': 24, 'category_prefix': 'solar_meter11', 'telemetry_categories': ['solar_meter11__alarms', 'solar_meter11__energies', 'solar_meter11__currents', 'solar_meter11__voltages', 'solar_meter11__power', 'solar_meter11__frequency', 'solar_meter11__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter11/solarMeter_register_full.json'}}, 'solar_meter12': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1603, 'unit_id': 12, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SOLAR-METER-012', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'solar_energy_meter/solar_meter12/solarMeter_register_full___me231.json', 'ems_block': 'solar_meter12', 'ems_base_address': 31756, 'ems_end_address': 31779, 'register_count': 24, 'category_prefix': 'solar_meter12', 'telemetry_categories': ['solar_meter12__alarms', 'solar_meter12__energies', 'solar_meter12__currents', 'solar_meter12__voltages', 'solar_meter12__power', 'solar_meter12__frequency', 'solar_meter12__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'solar_energy_meter/solar_meter12/solarMeter_register_full.json'}}}, 'frequency_meters': {'frequency_meter1': {'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1515, 'unit_id': 1, 'poll_interval_ms': 3000, 'save_interval_ms': 6000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'status': 'inactive', 'device_id': 'FREQUENCY-METER-001', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'frequency_meter/frequency_meter1/frequencyMeter_register_full___me231.json', 'ems_block': 'frequency_meter1', 'ems_base_address': 26462, 'ems_end_address': 26485, 'register_count': 24, 'category_prefix': 'frequency_meter1', 'telemetry_categories': ['frequency_meter1__alarms', 'frequency_meter1__energies', 'frequency_meter1__currents', 'frequency_meter1__voltages', 'frequency_meter1__power', 'frequency_meter1__frequency', 'frequency_meter1__power_factor'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'frequency_meter/frequency_meter1/frequencyMeter_register_full.json'}}}, 'grid_meters': {'grid_meter1': {'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1513, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'status': 'active', 'device_id': 'GRID-METER-001', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter1/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter1', 'ems_base_address': 26486, 'ems_end_address': 26525, 'register_count': 40, 'category_prefix': 'grid_meter1', 'telemetry_categories': ['grid_meter1__currents', 'grid_meter1__voltages', 'grid_meter1__power', 'grid_meter1__power_factor', 'grid_meter1__frequency', 'grid_meter1__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter1/gridMeter_register_full.json'}}, 'grid_meter2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-002', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter2/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter2', 'ems_base_address': 26646, 'ems_end_address': 26685, 'register_count': 40, 'category_prefix': 'grid_meter2', 'telemetry_categories': ['grid_meter2__currents', 'grid_meter2__voltages', 'grid_meter2__power', 'grid_meter2__power_factor', 'grid_meter2__frequency', 'grid_meter2__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter2/gridMeter_register_full.json'}}, 'grid_meter3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 3, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-003', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter3/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter3', 'ems_base_address': 26686, 'ems_end_address': 26725, 'register_count': 40, 'category_prefix': 'grid_meter3', 'telemetry_categories': ['grid_meter3__currents', 'grid_meter3__voltages', 'grid_meter3__power', 'grid_meter3__power_factor', 'grid_meter3__frequency', 'grid_meter3__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter3/gridMeter_register_full.json'}}, 'grid_meter4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 4, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-004', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter4/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter4', 'ems_base_address': 26726, 'ems_end_address': 26765, 'register_count': 40, 'category_prefix': 'grid_meter4', 'telemetry_categories': ['grid_meter4__currents', 'grid_meter4__voltages', 'grid_meter4__power', 'grid_meter4__power_factor', 'grid_meter4__frequency', 'grid_meter4__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter4/gridMeter_register_full.json'}}, 'grid_meter5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 5, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-005', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter5/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter5', 'ems_base_address': 26766, 'ems_end_address': 26805, 'register_count': 40, 'category_prefix': 'grid_meter5', 'telemetry_categories': ['grid_meter5__currents', 'grid_meter5__voltages', 'grid_meter5__power', 'grid_meter5__power_factor', 'grid_meter5__frequency', 'grid_meter5__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter5/gridMeter_register_full.json'}}, 'grid_meter6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 6, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-006', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter6/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter6', 'ems_base_address': 26806, 'ems_end_address': 26845, 'register_count': 40, 'category_prefix': 'grid_meter6', 'telemetry_categories': ['grid_meter6__currents', 'grid_meter6__voltages', 'grid_meter6__power', 'grid_meter6__power_factor', 'grid_meter6__frequency', 'grid_meter6__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter6/gridMeter_register_full.json'}}, 'grid_meter7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 7, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-007', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter7/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter7', 'ems_base_address': 26846, 'ems_end_address': 26885, 'register_count': 40, 'category_prefix': 'grid_meter7', 'telemetry_categories': ['grid_meter7__currents', 'grid_meter7__voltages', 'grid_meter7__power', 'grid_meter7__power_factor', 'grid_meter7__frequency', 'grid_meter7__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter7/gridMeter_register_full.json'}}, 'grid_meter8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-008', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter8/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter8', 'ems_base_address': 26886, 'ems_end_address': 26925, 'register_count': 40, 'category_prefix': 'grid_meter8', 'telemetry_categories': ['grid_meter8__currents', 'grid_meter8__voltages', 'grid_meter8__power', 'grid_meter8__power_factor', 'grid_meter8__frequency', 'grid_meter8__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter8/gridMeter_register_full.json'}}, 'grid_meter9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-009', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter9/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter9', 'ems_base_address': 26926, 'ems_end_address': 26965, 'register_count': 40, 'category_prefix': 'grid_meter9', 'telemetry_categories': ['grid_meter9__currents', 'grid_meter9__voltages', 'grid_meter9__power', 'grid_meter9__power_factor', 'grid_meter9__frequency', 'grid_meter9__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter9/gridMeter_register_full.json'}}, 'grid_meter10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 10, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-010', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter10/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter10', 'ems_base_address': 26526, 'ems_end_address': 26565, 'register_count': 40, 'category_prefix': 'grid_meter10', 'telemetry_categories': ['grid_meter10__currents', 'grid_meter10__voltages', 'grid_meter10__power', 'grid_meter10__power_factor', 'grid_meter10__frequency', 'grid_meter10__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter10/gridMeter_register_full.json'}}, 'grid_meter11': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 11, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-011', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter11/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter11', 'ems_base_address': 26566, 'ems_end_address': 26605, 'register_count': 40, 'category_prefix': 'grid_meter11', 'telemetry_categories': ['grid_meter11__currents', 'grid_meter11__voltages', 'grid_meter11__power', 'grid_meter11__power_factor', 'grid_meter11__frequency', 'grid_meter11__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter11/gridMeter_register_full.json'}}, 'grid_meter12': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1602, 'unit_id': 12, 'poll_interval_ms': 1000, 'save_interval_ms': 5000, 'log_level': 'INFO', 'endianness': 'big', 'ems_key': 'ems', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'GRID-METER-012', 'model': 'ME231', 'register_map': {'model': 'ME231', 'map_file': 'grid_energy_meter/grid_meter12/gridMeter_register_full___me231.json', 'ems_block': 'grid_meter12', 'ems_base_address': 26606, 'ems_end_address': 26645, 'register_count': 40, 'category_prefix': 'grid_meter12', 'telemetry_categories': ['grid_meter12__currents', 'grid_meter12__voltages', 'grid_meter12__power', 'grid_meter12__power_factor', 'grid_meter12__frequency', 'grid_meter12__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'grid_energy_meter/grid_meter12/gridMeter_register_full.json'}}}, 'door_sensors': {'door_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-001', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor1/door_sensor_register_full.json', 'ems_block': 'door_sensor1', 'ems_base_address': 26230, 'ems_end_address': 26241, 'register_count': 12, 'category_prefix': 'door_sensor1', 'telemetry_categories': ['door_sensor1__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor1/door_sensor_register_full.json'}}, 'door_sensor2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 2, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-002', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor2/door_sensor_register_full.json', 'ems_block': 'door_sensor2', 'ems_base_address': 26254, 'ems_end_address': 26265, 'register_count': 12, 'category_prefix': 'door_sensor2', 'telemetry_categories': ['door_sensor2__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor2/door_sensor_register_full.json'}}, 'door_sensor3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 3, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-003', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor3/door_sensor_register_full.json', 'ems_block': 'door_sensor3', 'ems_base_address': 26266, 'ems_end_address': 26277, 'register_count': 12, 'category_prefix': 'door_sensor3', 'telemetry_categories': ['door_sensor3__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor3/door_sensor_register_full.json'}}, 'door_sensor4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 4, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-004', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor4/door_sensor_register_full.json', 'ems_block': 'door_sensor4', 'ems_base_address': 26278, 'ems_end_address': 26289, 'register_count': 12, 'category_prefix': 'door_sensor4', 'telemetry_categories': ['door_sensor4__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor4/door_sensor_register_full.json'}}, 'door_sensor5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 5, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-005', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor5/door_sensor_register_full.json', 'ems_block': 'door_sensor5', 'ems_base_address': 26290, 'ems_end_address': 26301, 'register_count': 12, 'category_prefix': 'door_sensor5', 'telemetry_categories': ['door_sensor5__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor5/door_sensor_register_full.json'}}, 'door_sensor6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 6, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-006', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor6/door_sensor_register_full.json', 'ems_block': 'door_sensor6', 'ems_base_address': 26302, 'ems_end_address': 26313, 'register_count': 12, 'category_prefix': 'door_sensor6', 'telemetry_categories': ['door_sensor6__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor6/door_sensor_register_full.json'}}, 'door_sensor7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 7, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-007', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor7/door_sensor_register_full.json', 'ems_block': 'door_sensor7', 'ems_base_address': 26314, 'ems_end_address': 26325, 'register_count': 12, 'category_prefix': 'door_sensor7', 'telemetry_categories': ['door_sensor7__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor7/door_sensor_register_full.json'}}, 'door_sensor8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 8, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-008', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor8/door_sensor_register_full.json', 'ems_block': 'door_sensor8', 'ems_base_address': 26326, 'ems_end_address': 26337, 'register_count': 12, 'category_prefix': 'door_sensor8', 'telemetry_categories': ['door_sensor8__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor8/door_sensor_register_full.json'}}, 'door_sensor9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 9, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-009', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor9/door_sensor_register_full.json', 'ems_block': 'door_sensor9', 'ems_base_address': 26338, 'ems_end_address': 26349, 'register_count': 12, 'category_prefix': 'door_sensor9', 'telemetry_categories': ['door_sensor9__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor9/door_sensor_register_full.json'}}, 'door_sensor10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1520, 'unit_id': 10, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'DOOR-SENSOR-010', 'model': 'DS1', 'register_map': {'model': 'default', 'map_file': 'door_sensor/door_sensor10/door_sensor_register_full.json', 'ems_block': 'door_sensor10', 'ems_base_address': 26242, 'ems_end_address': 26253, 'register_count': 12, 'category_prefix': 'door_sensor10', 'telemetry_categories': ['door_sensor10__doors'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'door_sensor/door_sensor10/door_sensor_register_full.json'}}}, 'flood_sensors': {'flood_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1521, 'unit_id': 11, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'FLOOD-SENSOR-001', 'model': 'FS1', 'register_map': {'model': 'default', 'map_file': 'flood_sensor/flood_sensor1/flood_sensor_register_full.json', 'ems_block': 'flood_sensor1', 'ems_base_address': 26460, 'ems_end_address': 26461, 'register_count': 2, 'category_prefix': 'flood_sensor1', 'telemetry_categories': ['flood_sensor1__flood'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'flood_sensor/flood_sensor1/flood_sensor_register_full.json'}}}, 'smoke_detectors': {'smoke_detector1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1522, 'unit_id': 12, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SMOKE-DETECTOR-001', 'model': 'SS1', 'register_map': {'model': 'default', 'map_file': 'smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json', 'ems_block': 'smoke_sensor1', 'ems_base_address': 31682, 'ems_end_address': 31683, 'register_count': 2, 'category_prefix': 'smoke_sensor1', 'telemetry_categories': ['smoke_sensor1__alarms'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json'}}}, 'heat_sensors': {'heat_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1523, 'unit_id': 13, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'HEAT-SENSOR-001', 'model': 'HS1', 'register_map': {'model': 'default', 'map_file': 'heat_sensor/heat_sensor1/heat_sensor_register_full.json', 'ems_block': 'heat_sensor1', 'ems_base_address': 26966, 'ems_end_address': 26967, 'register_count': 2, 'category_prefix': 'heat_sensor1', 'telemetry_categories': ['heat_sensor1__alarms'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'heat_sensor/heat_sensor1/heat_sensor_register_full.json'}}}, 'temperature_sensors': {'temperature_sensor1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1524, 'unit_id': 14, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'TEMP-SENSOR-001', 'model': 'TS1', 'register_map': {'model': 'default', 'map_file': 'temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json', 'ems_block': 'temperature_sensor1', 'ems_base_address': 31972, 'ems_end_address': 31979, 'register_count': 8, 'category_prefix': 'temperature_sensor1', 'telemetry_categories': ['temperature_sensor1__temperatures'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json'}}}, 'sensor_blocks': {'sensor_block1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1525, 'unit_id': 15, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': 'ems', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'SENSOR-BLOCK-001', 'model': 'SB1', 'register_map': {'model': 'SENS_STD', 'map_file': 'sensor_block/sensorB1/sensorB_register_full___sens_std.json', 'ems_block': 'sensor_block1', 'ems_base_address': 31669, 'ems_end_address': 31681, 'register_count': 13, 'category_prefix': 'sensor_block1', 'telemetry_categories': ['sensor_block1__humidity', 'sensor_block1__light'], 'control_categories': ['sensor_block1__control__relay'], 'control_register_count': 1, 'control_registers': ['alarm_activation_relay'], 'map_template': 'sensor_block/sensorB1/sensorB_register_full.json'}}}, 'bmu_units': {'bmu1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1543, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P1', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu1/bmu_register_full___bmu100.json', 'ems_block': 'bmu1', 'ems_base_address': 25610, 'ems_end_address': 25671, 'register_count': 62, 'category_prefix': 'bmu1', 'telemetry_categories': ['bmu1__cell_voltage', 'bmu1__temperature_sensors', 'bmu1__status', 'bmu1__alarms'], 'control_categories': ['bmu1__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu1/bmu_register_full.json'}}, 'bmu2': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1544, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P2', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu2/bmu_register_full___bmu100.json', 'ems_block': 'bmu2', 'ems_base_address': 25734, 'ems_end_address': 25795, 'register_count': 62, 'category_prefix': 'bmu2', 'telemetry_categories': ['bmu2__cell_voltage', 'bmu2__temperature_sensors', 'bmu2__status', 'bmu2__alarms'], 'control_categories': ['bmu2__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu2/bmu_register_full.json'}}, 'bmu3': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1545, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P3', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu3/bmu_register_full___bmu100.json', 'ems_block': 'bmu3', 'ems_base_address': 25796, 'ems_end_address': 25857, 'register_count': 62, 'category_prefix': 'bmu3', 'telemetry_categories': ['bmu3__cell_voltage', 'bmu3__temperature_sensors', 'bmu3__status', 'bmu3__alarms'], 'control_categories': ['bmu3__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu3/bmu_register_full.json'}}, 'bmu4': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1546, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P4', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu4/bmu_register_full___bmu100.json', 'ems_block': 'bmu4', 'ems_base_address': 25858, 'ems_end_address': 25919, 'register_count': 62, 'category_prefix': 'bmu4', 'telemetry_categories': ['bmu4__cell_voltage', 'bmu4__temperature_sensors', 'bmu4__status', 'bmu4__alarms'], 'control_categories': ['bmu4__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu4/bmu_register_full.json'}}, 'bmu5': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1547, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P5', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu5/bmu_register_full___bmu100.json', 'ems_block': 'bmu5', 'ems_base_address': 25920, 'ems_end_address': 25981, 'register_count': 62, 'category_prefix': 'bmu5', 'telemetry_categories': ['bmu5__cell_voltage', 'bmu5__temperature_sensors', 'bmu5__status', 'bmu5__alarms'], 'control_categories': ['bmu5__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu5/bmu_register_full.json'}}, 'bmu6': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1548, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P6', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu6/bmu_register_full___bmu100.json', 'ems_block': 'bmu6', 'ems_base_address': 25982, 'ems_end_address': 26043, 'register_count': 62, 'category_prefix': 'bmu6', 'telemetry_categories': ['bmu6__cell_voltage', 'bmu6__temperature_sensors', 'bmu6__status', 'bmu6__alarms'], 'control_categories': ['bmu6__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu6/bmu_register_full.json'}}, 'bmu7': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1549, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P7', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu7/bmu_register_full___bmu100.json', 'ems_block': 'bmu7', 'ems_base_address': 26044, 'ems_end_address': 26105, 'register_count': 62, 'category_prefix': 'bmu7', 'telemetry_categories': ['bmu7__cell_voltage', 'bmu7__temperature_sensors', 'bmu7__status', 'bmu7__alarms'], 'control_categories': ['bmu7__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu7/bmu_register_full.json'}}, 'bmu8': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1550, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P8', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu8/bmu_register_full___bmu100.json', 'ems_block': 'bmu8', 'ems_base_address': 26106, 'ems_end_address': 26167, 'register_count': 62, 'category_prefix': 'bmu8', 'telemetry_categories': ['bmu8__cell_voltage', 'bmu8__temperature_sensors', 'bmu8__status', 'bmu8__alarms'], 'control_categories': ['bmu8__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu8/bmu_register_full.json'}}, 'bmu9': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1551, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P9', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu9/bmu_register_full___bmu100.json', 'ems_block': 'bmu9', 'ems_base_address': 26168, 'ems_end_address': 26229, 'register_count': 62, 'category_prefix': 'bmu9', 'telemetry_categories': ['bmu9__cell_voltage', 'bmu9__temperature_sensors', 'bmu9__status', 'bmu9__alarms'], 'control_categories': ['bmu9__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu9/bmu_register_full.json'}}, 'bmu10': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1552, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'Cl1_P10', 'model': 'generic_lfp_bms', 'register_map': {'model': 'BMU100', 'map_file': 'bmu/bmu10/bmu_register_full___bmu100.json', 'ems_block': 'bmu10', 'ems_base_address': 25672, 'ems_end_address': 25733, 'register_count': 62, 'category_prefix': 'bmu10', 'telemetry_categories': ['bmu10__cell_voltage', 'bmu10__temperature_sensors', 'bmu10__status', 'bmu10__alarms'], 'control_categories': ['bmu10__control__writeable_thresholds'], 'control_register_count': 6, 'control_registers': ['cell_overvoltage_threshold', 'cell_undervoltage_threshold', 'temperature_over_threshold', 'temperature_under_threshold', 'charge_current_limit', 'discharge_current_limit'], 'map_template': 'bmu/bmu10/bmu_register_full.json'}}}, 'ups_units': {'ups1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1530, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'ups_unit', 'model': 'UPS-X3000', 'register_map': {'model': 'UPS_10K', 'map_file': 'ups/ups1/ups_register_full___ups_10k.json', 'ems_block': 'ups1', 'ems_base_address': 31980, 'ems_end_address': 32060, 'register_count': 81, 'category_prefix': 'ups1', 'telemetry_categories': ['ups1__input', 'ups1__output', 'ups1__battery', 'ups1__status', 'ups1__alarms'], 'control_categories': ['ups1__control__control'], 'control_register_count': 5, 'control_registers': ['output_voltage_setpoint_v', 'battery_low_threshold_percent', 'shutdown_delay_min', 'battery_test_start', 'buzzer_enable'], 'map_template': 'ups/ups1/ups_register_full.json'}}}, 'bess_energy_meters': {'bessEnergyMeter1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1531, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': 'bessEnergyMeter1', 'model': 'Schneider PM8000', 'register_map': {'model': 'default', 'map_file': 'bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json', 'ems_block': 'bessEnergyMeter1', 'ems_base_address': 25510, 'ems_end_address': 25609, 'register_count': 100, 'category_prefix': 'bessEnergyMeter1', 'telemetry_categories': ['bessEnergyMeter1__alarms', 'bessEnergyMeter1__energies', 'bessEnergyMeter1__currents', 'bessEnergyMeter1__power', 'bessEnergyMeter1__power_factor'], 'control_categories': ['bessEnergyMeter1__control__voltages', 'bessEnergyMeter1__control__frequency'], 'control_register_count': 9, 'control_registers': ['voltage_ab_v', 'voltage_bc_v', 'voltage_ca_v', 'voltage_ll_avg_v', 'voltage_an_v', 'voltage_bn_v', 'voltage_cn_v', 'voltage_ln_avg_v', 'frequency_hz'], 'map_template': 'bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json'}}}, 'ffr_meters': {'ffrEnergyMeter1': {'status': 'inactive', 'communication': {'protocol': 'modbus-tcp', 'ip_address': ''}, 'device': {'ip': 'bess-simulator-backend', 'port': 1532, 'unit_id': 1, 'poll_interval_ms': 5000, 'save_interval_ms': 15000, 'log_level': 'INFO', 'ems_key': '', 'endianness': 'big', 'scale': 1, 'datatype': 'BITMAP32'}, 'device_id': None, 'model': None, 'register_map': {'model': 'default', 'map_file': 'ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json', 'ems_block': 'ffrEnergyMeter1', 'ems_base_address': 26350, 'ems_end_address': 26389, 'register_count': 40, 'category_prefix': 'ffrEnergyMeter1', 'telemetry_categories': ['ffrEnergyMeter1__currents', 'ffrEnergyMeter1__voltages', 'ffrEnergyMeter1__power', 'ffrEnergyMeter1__power_factor', 'ffrEnergyMeter1__frequency', 'ffrEnergyMeter1__energies'], 'control_categories': [], 'control_register_count': 0, 'control_registers': [], 'map_template': 'ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json'}}}}, 'protections': {'overvoltage_v': None, 'undervoltage_v': None, 'overcurrent_a': None, 'over_frequency_hz': None, 'under_frequency_hz': None, 'temperature_thresholds': {'cell_max_c': None, 'pcs_max_c': None, 'cabinet_max_c': None, 'cell_min_c': None, 'pcs_min_c': None, 'cabinet_min_c': None}, 'fire_suppression_integration': None, 'ems_bms_comm_timeout_ms': None}, 'monitoring_logging': {'data_push_interval_ms': None, 'logging_level': None, 'alarm_notifications': []}, 'functions': {'Manual_Operation': {'enabled': True, 'operation_type': 'charge', 'power_setpoint_kw': 150, 'ramp_rate_kw_s': 100, 'soc_limits': {'min_soc_pct': 50, 'max_soc_pct': 90}, 'soc_recovery_target_pct': 12, 'power_caps_kw': {'charge_cap_kw': 100, 'discharge_cap_kw': 90}, 'mode_priority': 'override-all', 'telemetry_control': {'control_channel': 'local-hmi', 'command_confirmation': True, 'status_feedback': 'mode'}, 'safety': {'trip_on_overvoltage': True, 'trip_on_undervoltage': True, 'trip_on_overtemperature': True, 'grid_fault_action': 'PCS_shutdown'}}, 'Arbitrage': {'enabled': False, 'timezone': 'Europe/Stockholm', 'tick': {'interval_seconds': 300, 'run_on_start': True, 'skip_cycles_log': True, 'zero_power_on_skip': True}, 'price_zone': 'SE4', 'price_currency': 'SEK', 'price_source': {'provider': 'elprisetjustnu', 'url_template': 'https.gess.se', 'timeout_ms': 4000, 'http': {'user_agent': 'GESS-EMS/1.0', 'headers': ''}, 'format': 'json_array', 'fields': {'time_start': 'time_start', 'time_end': 'time_end', 'price_sek': 'SEK_per_kWh', 'price_eur': 'EUR_per_kWh'}, 'resolution_minutes': 15, 'slot_mode': 'current_only'}, 'strategy': {'prefer_next_slot': True, 'min_spread': 0, 'buy_threshold': 0.1, 'sell_threshold': 0.12, 'buy_power_kw': 20, 'sell_power_kw': 20, 'tomorrow_plan': {'enabled': True, 'charge_cheapest_slots': 8, 'discharge_most_expensive_slots': 8, 'charge_power_kw': 20, 'discharge_power_kw': 20, 'tie_breaker': 'earlier_first'}}, 'optional': {'hysteresis': 0, 'conflict_rule': '', 'hysteresis_kw': 0}, 'ramp_rate_kw_s': 100}, 'Peak_Shaving': {'enabled': True, 'peak_threshold_kw': 50, 'discharge_power_limit_kw': 50, 'min_soc_pct': 10, 'recovery_soc_pct': 67, 'response_time_ms': 90, 'timezone': 'Europe/Stockholm', 'discharge_windows': [{'start': '13:00', 'end': '23:06', 'enabled': False, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '02:00', 'end': '08:50', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '10:00', 'end': '18:00', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'power_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}], 'charge_windows': [{'start': '01:00', 'end': '17:30', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '18:00', 'end': '23:00', 'enabled': False, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '01:00', 'end': '06:00', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}], 'optional': {'hysteresis_kw': 2, 'conflict_rule': 'discharge_overrides_charge'}, 'ramp_rate_kw_s': 100}, 'Valley_Filling': {'enabled': False, 'valley_threshold_kw': 75, 'charge_power_limit_kw': 120, 'max_soc_pct': None, 'min_soc_pct': None, 'response_time_ms': None, 'timezone': 'Europe/Stockholm', 'charge_windows': [{'start': '02:00', 'end': '22:00', 'enabled': True, 'charge_cap_kw': 100, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '14:00', 'end': '08:00', 'enabled': True, 'charge_cap_kw': 20, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '00:00', 'end': '08:00', 'enabled': True, 'charge_cap_kw': 20, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'charge_cap_kw': None, 'days_of_week': ['Mon']}], 'optional': {'hysteresis_kw': 2, 'conflict_rule': 'discharge_overrides_charge'}, 'ramp_rate_kw_s': 100}, 'Scheduled_Charge_Discharge': {'enabled': False, 'timezone': 'Europe/Stockholm', 'soc_limits': {'min_soc_pct': 40, 'max_soc_pct': 20}, 'power_limits': {'charge_power_limit_kw': 30, 'discharge_power_limit_kw': 30}, 'response_time_ms': 1, 'conflict_rule': 'discharge_overrides_charge', 'validation': {'prevent_overlaps': True, 'min_duration_minutes': 5, 'time_format': 'HH:MM'}, 'weekly': {'MonFri': [{'start': '12:50', 'end': '12:57', 'enabled': True, 'action': 'charge', 'powerSetpoint': 25.3, 'operationType': 'charge'}, {'start': '17:58', 'end': '19:05', 'enabled': True, 'action': 'discharge', 'powerSetpoint': 26, 'operationType': 'discharge'}, {'enabled': True, 'start': '01:00', 'end': '18:00', 'powerSetpoint': 25.1, 'action': 'charge', 'operationType': 'charge'}, {'enabled': False, 'start': '01:00', 'end': '17:04', 'powerSetpoint': 25.2, 'action': 'charge', 'operationType': 'charge'}, {'enabled': False, 'start': '11:00', 'end': '16:00', 'powerSetpoint': 25.3, 'action': 'charge', 'operationType': 'charge'}, {'enabled': False, 'start': '02:00', 'end': '12:00', 'powerSetpoint': 25.4, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '01:00', 'end': '16:00', 'powerSetpoint': 25.5, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '00:00', 'end': '17:00', 'powerSetpoint': 25.6, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '00:00', 'end': '12:00', 'powerSetpoint': 25.7, 'action': 'charge', 'operationType': 'charge'}, {'enabled': True, 'start': '02:00', 'end': '12:00', 'powerSetpoint': 25.8, 'action': 'discharge', 'operationType': 'discharge'}], 'Sat': [{'start': '04:00', 'end': '04:00', 'enabled': True, 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '11:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:04', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '01:00', 'end': '12:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': False, 'start': '08:01', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '15:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': False, 'start': '11:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}], 'Sun': [{'enabled': True, 'start': '11:00', 'end': '12:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'discharge', 'powerSetpoint': 25, 'operationType': 'discharge'}, {'enabled': True, 'start': '08:00', 'end': '14:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': True, 'start': '08:00', 'end': '15:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}, {'enabled': False, 'start': '08:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': 'charge'}]}, 'specific_dates': {'dates': '2026-09-24', 'entries': {'2026-09-24': [{'enabled': True, 'start': '10:00', 'end': '12:00', 'action': 'charge', 'powerSetpoint': 25, 'operationType': None}]}}, 'ramp_rate_kw_s': 100}, 'Backup': {'enabled': False, 'backup_power_setpoint_kw': None, 'min_soc_pct': None, 'recovery_soc_pct': None, 'response_time_ms': None, 'black_start_enable': True, 'grid_mode_switch': {'enabled': False, 'grid_loss_voltage_v': 100, 'grid_loss_frequency_hz_low': 47, 'grid_loss_frequency_hz_high': 53, 'switch_delay_s': 3}, 'power_dispatch': {'enabled': False}, 'priority_rule': 'backup_overrides_all', 'ramp_rate_kw_s': 100}, 'Backup_Peak_Shaving': {'enabled': False, 'priority_rule': 'backup_over_peak_shaving', 'peak_shaving_ref': 'Peak_Shaving'}, 'Backup_Frequency_Regulation': {'enabled': False, 'priority_rule': 'backup_over_frequency_regulation', 'frequency_regulation_ref': 'Peak_Shaving'}, 'Power_Factor_Correction': {'enabled': False, 'target_pf': 0.98, 'pf_deadband': 0.01, 'mode': 'auto', 'q_max_kvar': None, 'ramp_rate_limit_kvar_s': None, 'response_time_ms': None, 'soc_limits': {'min_soc_pct': None, 'max_soc_pct': None}, 'power_caps_kw': {'charge_cap_kw': None, 'discharge_cap_kw': None}, 'priority_rule': 'pf_correction_over_valley_arbitrage', 'reactive_power_actuation': {'enabled': False, 'register': None, 'scale_kvar_per_unit': None, 'sign_convention': 'positive_capacitive', 'rated_kva': None}}, 'Voltage_Support': {'enabled': False, 'nominal_voltage_v': 230, 'v_low_pu': 0.9, 'v1_pu': 0.98, 'v2_pu': 1.02, 'v_high_pu': 1.1, 'q_max_kvar': None, 'ramp_rate_limit_kvar_s': None, 'response_time_ms': None, 'soc_limits': {'min_soc_pct': None, 'max_soc_pct': None}, 'power_caps_kw': {'charge_cap_kw': None, 'discharge_cap_kw': None}, 'priority_rule': 'voltage_support_over_pf_correction', 'reactive_power_actuation': {'enabled': False, 'register': None, 'scale_kvar_per_unit': None, 'sign_convention': 'positive_capacitive', 'rated_kva': None}}, 'Frequency_Regulation': {'enabled': False, 'grid_mode': 'on-grid-only', 'droop_pct': 50, 'deadband_hz': 0.5, 'participation_pct': 7, 'response_time_ms': 6, 'ramp_rate_limit_kw_s': 67, 'soc_limits': {'min_soc_pct': 60, 'max_soc_pct': 50}, 'soc_recovery_target_pct': 50, 'power_caps_kw': {'charge_cap_kw': 50, 'discharge_cap_kw': 50}, 'frequency_measurement_interval_ms': 50, 'priority_rule': 'frequency_over_arbitrage_valley', 'telemetry_api': {'endpoint_url': '', 'api_key': '', 'send_frequency_ms': 1000, 'payload_schema_version': '1.1', 'timeout_ms': 30, 'retry_policy': {'retries': 3, 'backoff_ms': 500}, 'failover_behavior': 'last-setpoint'}, 'recharge_windows': [{'start': '22:00', 'end': '06:00', 'enabled': True, 'charge_cap_kw': None}, {'start': '12:00', 'end': '14:00', 'enabled': False, 'charge_cap_kw': None}, {'start': '', 'end': '', 'enabled': False, 'charge_cap_kw': None}, {'start': '', 'end': '', 'enabled': False, 'charge_cap_kw': None}, {'start': '', 'end': '', 'enabled': False, 'charge_cap_kw': None}], 'logging': {'enabled': True, 'format': 'jsonl', 'flush_interval_ms': 500, 'max_batch_records': 5000, 'rotate_every_seconds': 300, 'folder': 'setting'}, 'soc_source': {'type': 'lastValue_json', 'refresh_interval_ms': 500, 'folder': 'soc', 'file_pattern': 'soc', 'soc_key': '', 'missing_soc_behavior': 'allow'}, 'nominal_hz': 50}, 'Anti_Backflow': {'enabled': False, 'export_limit_kw': 50, 'response_time_ms': 50, 'ramp_rate_limit_kw_s': 60, 'soc_limits': {'min_soc_pct': 48, 'max_soc_pct': 30}, 'priority_rule': 'anti_backflow_over_arbitrage_freq', 'timezone': 'Europe/Stockholm', 'control_windows': [{'start': '00:00', 'end': '23:59', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri', 'Sat', 'Sun']}, {'start': '09:00', 'end': '17:00', 'enabled': True, 'export_cap_kw': 5, 'days_of_week': ['Mon', 'Tue', 'Wed', 'Thu', 'Fri']}, {'start': '', 'end': '', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon']}, {'start': '', 'end': '', 'enabled': True, 'export_cap_kw': 0, 'days_of_week': ['Mon']}], 'optional': {'specific_dates': '', 'fail_safe_behavior': 'clamp-zero', 'specific_date_controls': []}, 'ramp_rate_kw_s': 100}, 'Maintenance': {'hold_zero_power': True}, 'Energy_Optimization': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'energy_optimization_over_arbitrage_valley'}, 'Power_Node_Energy_Sharing': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'power_node_over_local_dispatch'}, 'Grid_Sync': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'grid_sync_over_grid_modes'}, 'Dynamic_Load_Balancing': {'enabled': False, 'spec_status': 'awaiting_specification', 'priority_rule': 'load_balancing_over_peak_shaving'}}, 'control_settings': {'ems_control_mode': 'Internal_EMS', 'ems_refresh_rate_hz': 2, 'ems_refresh_rate_options_hz': [0.5, 1, 2, 5, 10]}}
functions.Manual_Operation.enabled @6 INT16U 1 RW 1 (true)
functions.Manual_Operation.power_setpoint_kw @7 INT16U 1 RW 150
functions.Manual_Operation.ramp_rate_kw_s @8 INT16U 1 RW 100
functions.Manual_Operation.soc_limits.min_soc_pct @9 INT16U 1 RW 50
functions.Manual_Operation.soc_limits.max_soc_pct @10 INT16U 1 RW 90
functions.Manual_Operation.soc_recovery_target_pct @11 INT16U 1 RW 12
functions.Manual_Operation.power_caps_kw.charge_cap_kw @12 INT16U 1 RW 100
functions.Manual_Operation.power_caps_kw.discharge_cap_kw @13 INT16U 1 RW 90
functions.Manual_Operation.telemetry_control.command_confirmation @14 INT16U 1 RW 1 (true)
functions.Manual_Operation.safety.trip_on_overvoltage @15 INT16U 1 RW 1 (true)
functions.Manual_Operation.safety.trip_on_undervoltage @16 INT16U 1 RW 1 (true)
functions.Manual_Operation.safety.trip_on_overtemperature @17 INT16U 1 RW 1 (true)
functions.Arbitrage.enabled @18 INT16U 1 RW 0 (false)
functions.Arbitrage.tick.interval_seconds @19 INT16U 1 RW 300
functions.Arbitrage.tick.run_on_start @20 INT16U 1 RW 1 (true)
functions.Arbitrage.tick.skip_cycles_log @21 INT16U 1 RW 1 (true)
functions.Arbitrage.tick.zero_power_on_skip @22 INT16U 1 RW 1 (true)
functions.Arbitrage.price_source.timeout_ms @23 INT16U 1 RW 4000
functions.Arbitrage.price_source.resolution_minutes @24 INT16U 1 RW 15
functions.Arbitrage.strategy.prefer_next_slot @25 INT16U 1 RW 1 (true)
functions.Arbitrage.strategy.min_spread @26 INT16U 1 RW 0
functions.Arbitrage.strategy.buy_threshold @27 FLOAT32 2 RW 0.1
functions.Arbitrage.strategy.sell_threshold @29 FLOAT32 2 RW 0.12
functions.Arbitrage.strategy.buy_power_kw @31 INT16U 1 RW 20
functions.Arbitrage.strategy.sell_power_kw @32 INT16U 1 RW 20
functions.Arbitrage.strategy.tomorrow_plan.enabled @33 INT16U 1 RW 1 (true)
functions.Arbitrage.strategy.tomorrow_plan.charge_cheapest_slots @34 INT16U 1 RW 8
functions.Arbitrage.strategy.tomorrow_plan.discharge_most_expensive_slots @35 INT16U 1 RW 8
functions.Arbitrage.strategy.tomorrow_plan.charge_power_kw @36 INT16U 1 RW 20
functions.Arbitrage.strategy.tomorrow_plan.discharge_power_kw @37 INT16U 1 RW 20
functions.Arbitrage.optional.hysteresis @38 INT16U 1 RW 0
functions.Arbitrage.optional.hysteresis_kw @39 INT16U 1 RW 0
functions.Arbitrage.ramp_rate_kw_s @40 INT16U 1 RW 100
functions.Peak_Shaving.enabled @41 INT16U 1 RW 1 (true)
functions.Peak_Shaving.peak_threshold_kw @42 INT16U 1 RW 50
functions.Peak_Shaving.discharge_power_limit_kw @43 INT16U 1 RW 50
functions.Peak_Shaving.min_soc_pct @44 INT16U 1 RW 10
functions.Peak_Shaving.recovery_soc_pct @45 INT16U 1 RW 67
functions.Peak_Shaving.response_time_ms @46 INT16U 1 RW 90
functions.Peak_Shaving.optional.hysteresis_kw @47 INT16U 1 RW 2
functions.Peak_Shaving.ramp_rate_kw_s @48 INT16U 1 RW 100
functions.Valley_Filling.enabled @49 INT16U 1 RW 0 (false)
functions.Valley_Filling.valley_threshold_kw @50 INT16U 1 RW 75
functions.Valley_Filling.charge_power_limit_kw @51 INT16U 1 RW 120
functions.Valley_Filling.max_soc_pct @52 FLOAT32 2 RW -
functions.Valley_Filling.min_soc_pct @54 FLOAT32 2 RW -
functions.Valley_Filling.response_time_ms @56 FLOAT32 2 RW -
functions.Valley_Filling.optional.hysteresis_kw @58 INT16U 1 RW 2
functions.Valley_Filling.ramp_rate_kw_s @59 INT16U 1 RW 100
functions.Scheduled_Charge_Discharge.enabled @60 INT16U 1 RW 0 (false)
functions.Scheduled_Charge_Discharge.soc_limits.min_soc_pct @61 INT16U 1 RW 40
functions.Scheduled_Charge_Discharge.soc_limits.max_soc_pct @62 INT16U 1 RW 20
functions.Scheduled_Charge_Discharge.power_limits.charge_power_limit_kw @63 INT16U 1 RW 30
functions.Scheduled_Charge_Discharge.power_limits.discharge_power_limit_kw @64 INT16U 1 RW 30
functions.Scheduled_Charge_Discharge.response_time_ms @65 INT16U 1 RW 1
functions.Scheduled_Charge_Discharge.validation.prevent_overlaps @66 INT16U 1 RW 1 (true)
functions.Scheduled_Charge_Discharge.validation.min_duration_minutes @67 INT16U 1 RW 5
functions.Scheduled_Charge_Discharge.ramp_rate_kw_s @68 INT16U 1 RW 100
functions.Backup.enabled @69 INT16U 1 RW 0 (false)
functions.Backup.backup_power_setpoint_kw @70 FLOAT32 2 RW -
functions.Backup.min_soc_pct @72 FLOAT32 2 RW -
functions.Backup.recovery_soc_pct @74 FLOAT32 2 RW -
functions.Backup.response_time_ms @76 FLOAT32 2 RW -
functions.Backup.black_start_enable @78 INT16U 1 RW 1 (true)
functions.Backup.grid_mode_switch.enabled @79 INT16U 1 RW 0 (false)
functions.Backup.grid_mode_switch.grid_loss_voltage_v @80 INT16U 1 RW 100
functions.Backup.grid_mode_switch.grid_loss_frequency_hz_low @81 INT16U 1 RW 47
functions.Backup.grid_mode_switch.grid_loss_frequency_hz_high @82 INT16U 1 RW 53
functions.Backup.grid_mode_switch.switch_delay_s @83 INT16U 1 RW 3
functions.Backup.power_dispatch.enabled @84 INT16U 1 RW 0 (false)
functions.Backup.ramp_rate_kw_s @85 INT16U 1 RW 100
functions.Backup_Peak_Shaving.enabled @86 INT16U 1 RW 0 (false)
functions.Backup_Frequency_Regulation.enabled @87 INT16U 1 RW 0 (false)
functions.Power_Factor_Correction.enabled @88 INT16U 1 RW 0 (false)
functions.Power_Factor_Correction.target_pf @89 FLOAT32 2 RW 0.98
functions.Power_Factor_Correction.pf_deadband @91 FLOAT32 2 RW 0.01
functions.Power_Factor_Correction.q_max_kvar @93 FLOAT32 2 RW -
functions.Power_Factor_Correction.ramp_rate_limit_kvar_s @95 FLOAT32 2 RW -
functions.Power_Factor_Correction.response_time_ms @97 FLOAT32 2 RW -
functions.Power_Factor_Correction.soc_limits.min_soc_pct @99 FLOAT32 2 RW -
functions.Power_Factor_Correction.soc_limits.max_soc_pct @101 FLOAT32 2 RW -
functions.Power_Factor_Correction.power_caps_kw.charge_cap_kw @103 FLOAT32 2 RW -
functions.Power_Factor_Correction.power_caps_kw.discharge_cap_kw @105 FLOAT32 2 RW -
functions.Power_Factor_Correction.reactive_power_actuation.enabled @107 INT16U 1 RW 0 (false)
functions.Power_Factor_Correction.reactive_power_actuation.register @108 FLOAT32 2 RW -
functions.Power_Factor_Correction.reactive_power_actuation.scale_kvar_per_unit @110 FLOAT32 2 RW -
functions.Power_Factor_Correction.reactive_power_actuation.rated_kva @112 FLOAT32 2 RW -
functions.Voltage_Support.enabled @114 INT16U 1 RW 0 (false)
functions.Voltage_Support.nominal_voltage_v @115 INT16U 1 RW 230
functions.Voltage_Support.v_low_pu @116 FLOAT32 2 RW 0.9
functions.Voltage_Support.v1_pu @118 FLOAT32 2 RW 0.98
functions.Voltage_Support.v2_pu @120 FLOAT32 2 RW 1.02
functions.Voltage_Support.v_high_pu @122 FLOAT32 2 RW 1.1
functions.Voltage_Support.q_max_kvar @124 FLOAT32 2 RW -
functions.Voltage_Support.ramp_rate_limit_kvar_s @126 FLOAT32 2 RW -
functions.Voltage_Support.response_time_ms @128 FLOAT32 2 RW -
functions.Voltage_Support.soc_limits.min_soc_pct @130 FLOAT32 2 RW -
functions.Voltage_Support.soc_limits.max_soc_pct @132 FLOAT32 2 RW -
functions.Voltage_Support.power_caps_kw.charge_cap_kw @134 FLOAT32 2 RW -
functions.Voltage_Support.power_caps_kw.discharge_cap_kw @136 FLOAT32 2 RW -
functions.Voltage_Support.reactive_power_actuation.enabled @138 INT16U 1 RW 0 (false)
functions.Voltage_Support.reactive_power_actuation.register @139 FLOAT32 2 RW -
functions.Voltage_Support.reactive_power_actuation.scale_kvar_per_unit @141 FLOAT32 2 RW -
functions.Voltage_Support.reactive_power_actuation.rated_kva @143 FLOAT32 2 RW -
functions.Frequency_Regulation.enabled @145 INT16U 1 RW 0 (false)
functions.Frequency_Regulation.droop_pct @146 INT16U 1 RW 50
functions.Frequency_Regulation.deadband_hz @147 FLOAT32 2 RW 0.5
functions.Frequency_Regulation.participation_pct @149 INT16U 1 RW 7
functions.Frequency_Regulation.response_time_ms @150 INT16U 1 RW 6
functions.Frequency_Regulation.ramp_rate_limit_kw_s @151 INT16U 1 RW 67
functions.Frequency_Regulation.soc_limits.min_soc_pct @152 INT16U 1 RW 60
functions.Frequency_Regulation.soc_limits.max_soc_pct @153 INT16U 1 RW 50
functions.Frequency_Regulation.soc_recovery_target_pct @154 INT16U 1 RW 50
functions.Frequency_Regulation.power_caps_kw.charge_cap_kw @155 INT16U 1 RW 50
functions.Frequency_Regulation.power_caps_kw.discharge_cap_kw @156 INT16U 1 RW 50
functions.Frequency_Regulation.frequency_measurement_interval_ms @157 INT16U 1 RW 50
functions.Frequency_Regulation.telemetry_api.send_frequency_ms @158 INT16U 1 RW 1000
functions.Frequency_Regulation.telemetry_api.timeout_ms @159 INT16U 1 RW 30
functions.Frequency_Regulation.telemetry_api.retry_policy.retries @160 INT16U 1 RW 3
functions.Frequency_Regulation.telemetry_api.retry_policy.backoff_ms @161 INT16U 1 RW 500
functions.Frequency_Regulation.logging.enabled @162 INT16U 1 RW 1 (true)
functions.Frequency_Regulation.logging.flush_interval_ms @163 INT16U 1 RW 500
functions.Frequency_Regulation.logging.max_batch_records @164 INT16U 1 RW 5000
functions.Frequency_Regulation.logging.rotate_every_seconds @165 INT16U 1 RW 300
functions.Frequency_Regulation.soc_source.refresh_interval_ms @166 INT16U 1 RW 500
functions.Frequency_Regulation.nominal_hz @167 INT16U 1 RW 50
functions.Anti_Backflow.enabled @168 INT16U 1 RW 0 (false)
functions.Anti_Backflow.export_limit_kw @169 INT16U 1 RW 50
functions.Anti_Backflow.response_time_ms @170 INT16U 1 RW 50
functions.Anti_Backflow.ramp_rate_limit_kw_s @171 INT16U 1 RW 60
functions.Anti_Backflow.soc_limits.min_soc_pct @172 INT16U 1 RW 48
functions.Anti_Backflow.soc_limits.max_soc_pct @173 INT16U 1 RW 30
functions.Anti_Backflow.ramp_rate_kw_s @174 INT16U 1 RW 100
functions.Maintenance.hold_zero_power @175 INT16U 1 RW 1 (true)
functions.Energy_Optimization.enabled @176 INT16U 1 RW 0 (false)
functions.Power_Node_Energy_Sharing.enabled @177 INT16U 1 RW 0 (false)
functions.Grid_Sync.enabled @178 INT16U 1 RW 0 (false)
functions.Dynamic_Load_Balancing.enabled @179 INT16U 1 RW 0 (false)
protections.overvoltage_v @180 FLOAT32 2 RW -
protections.undervoltage_v @182 FLOAT32 2 RW -
protections.overcurrent_a @184 FLOAT32 2 RW -
protections.over_frequency_hz @186 FLOAT32 2 RW -
protections.under_frequency_hz @188 FLOAT32 2 RW -
protections.temperature_thresholds.cell_max_c @190 FLOAT32 2 RW -
protections.temperature_thresholds.pcs_max_c @192 FLOAT32 2 RW -
protections.temperature_thresholds.cabinet_max_c @194 FLOAT32 2 RW -
protections.temperature_thresholds.cell_min_c @196 FLOAT32 2 RW -
protections.temperature_thresholds.pcs_min_c @198 FLOAT32 2 RW -
protections.temperature_thresholds.cabinet_min_c @200 FLOAT32 2 RW -
protections.fire_suppression_integration @202 FLOAT32 2 RW -
protections.ems_bms_comm_timeout_ms @204 FLOAT32 2 RW -
monitoring_logging.data_push_interval_ms @206 FLOAT32 2 RW -
monitoring_logging.logging_level @208 FLOAT32 2 RW -

Appendix B: PCS remote-control registers

One row per PCS register that the map exposes for control. Map address is the address on port 1540; PCS register is the address in the PCS's own register numbering. In external-control mode the EMS drives the PCS through this block; an integrator writing it directly should read section 13, limitation 2.

Unit Register Map address PCS register Type
pcs1 start_stop_command @27025 @20657 INT16
pcs1 active_power_set_kw @27324 @23415 INT16
pcs1 start_stop_control_item @27399 @28000 INT16
pcs1 operation_mode_setting_item @27400 @28001 INT16
pcs1 scheduling_mode_item @27401 @28002 INT16
pcs1 pcs_switch_control_valid_when_8002_register_value_is_2_item @27402 @28003 INT16
pcs1 pcs_power_control_valid_when_8002_register_value_is_2_kw @27403 @28004 INT16
pcs1 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @27404 @28005 INT16
pcs1 ems_time_setting_item @27405 @28006 UINT32
pcs1 ems_reset_pcs_item @27407 @28007 UINT16
pcs1 ems_reset_bms_item @27408 @28008 UINT16
pcs1 mode_pq_vf_command_item @27411 @40582 INT16
pcs10 start_stop_command @27412 @20657 INT16
pcs10 active_power_set_kw @27711 @23415 INT16
pcs10 start_stop_control_item @27786 @28000 INT16
pcs10 operation_mode_setting_item @27787 @28001 INT16
pcs10 scheduling_mode_item @27788 @28002 INT16
pcs10 pcs_switch_control_valid_when_8002_register_value_is_2_item @27789 @28003 INT16
pcs10 pcs_power_control_valid_when_8002_register_value_is_2_kw @27790 @28004 INT16
pcs10 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @27791 @28005 INT16
pcs10 ems_time_setting_item @27792 @28006 UINT32
pcs10 ems_reset_pcs_item @27794 @28007 UINT16
pcs10 ems_reset_bms_item @27795 @28008 UINT16
pcs10 mode_pq_vf_command_item @27798 @40582 INT16
pcs11 start_stop_command @27799 @657 INT16
pcs11 active_power_set_kw @28098 @3415 INT16
pcs11 start_stop_control_item @28173 @8000 INT16
pcs11 operation_mode_setting_item @28174 @8001 INT16
pcs11 scheduling_mode_item @28175 @8002 INT16
pcs11 pcs_switch_control_valid_when_8002_register_value_is_2_item @28176 @8003 INT16
pcs11 pcs_power_control_valid_when_8002_register_value_is_2_kw @28177 @8004 INT16
pcs11 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @28178 @8005 INT16
pcs11 ems_time_setting_item @28179 @8006 UINT32
pcs11 ems_reset_pcs_item @28181 @8007 UINT16
pcs11 ems_reset_bms_item @28182 @8008 UINT16
pcs11 mode_pq_vf_command_item @28185 @20582 INT16
pcs12 start_stop_command @28186 @657 INT16
pcs12 active_power_set_kw @28485 @3415 INT16
pcs12 start_stop_control_item @28560 @8000 INT16
pcs12 operation_mode_setting_item @28561 @8001 INT16
pcs12 scheduling_mode_item @28562 @8002 INT16
pcs12 pcs_switch_control_valid_when_8002_register_value_is_2_item @28563 @8003 INT16
pcs12 pcs_power_control_valid_when_8002_register_value_is_2_kw @28564 @8004 INT16
pcs12 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @28565 @8005 INT16
pcs12 ems_time_setting_item @28566 @8006 UINT32
pcs12 ems_reset_pcs_item @28568 @8007 UINT16
pcs12 ems_reset_bms_item @28569 @8008 UINT16
pcs12 mode_pq_vf_command_item @28572 @20582 INT16
pcs2 start_stop_command @28573 @20657 INT16
pcs2 active_power_set_kw @28872 @23415 INT16
pcs2 start_stop_control_item @28947 @28000 INT16
pcs2 operation_mode_setting_item @28948 @28001 INT16
pcs2 scheduling_mode_item @28949 @28002 INT16
pcs2 pcs_switch_control_valid_when_8002_register_value_is_2_item @28950 @28003 INT16
pcs2 pcs_power_control_valid_when_8002_register_value_is_2_kw @28951 @28004 INT16
pcs2 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @28952 @28005 INT16
pcs2 ems_time_setting_item @28953 @28006 UINT32
pcs2 ems_reset_pcs_item @28955 @28007 UINT16
pcs2 ems_reset_bms_item @28956 @28008 UINT16
pcs2 mode_pq_vf_command_item @28959 @40582 INT16
pcs3 start_stop_command @28960 @657 INT16
pcs3 active_power_set_kw @29259 @3415 INT16
pcs3 start_stop_control_item @29334 @8000 INT16
pcs3 operation_mode_setting_item @29335 @8001 INT16
pcs3 scheduling_mode_item @29336 @8002 INT16
pcs3 pcs_switch_control_valid_when_8002_register_value_is_2_item @29337 @8003 INT16
pcs3 pcs_power_control_valid_when_8002_register_value_is_2_kw @29338 @8004 INT16
pcs3 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @29339 @8005 INT16
pcs3 ems_time_setting_item @29340 @8006 UINT32
pcs3 ems_reset_pcs_item @29342 @8007 UINT16
pcs3 ems_reset_bms_item @29343 @8008 UINT16
pcs3 mode_pq_vf_command_item @29346 @20582 INT16
pcs4 start_stop_command @29347 @657 INT16
pcs4 active_power_set_kw @29646 @3415 INT16
pcs4 start_stop_control_item @29721 @8000 INT16
pcs4 operation_mode_setting_item @29722 @8001 INT16
pcs4 scheduling_mode_item @29723 @8002 INT16
pcs4 pcs_switch_control_valid_when_8002_register_value_is_2_item @29724 @8003 INT16
pcs4 pcs_power_control_valid_when_8002_register_value_is_2_kw @29725 @8004 INT16
pcs4 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @29726 @8005 INT16
pcs4 ems_time_setting_item @29727 @8006 UINT32
pcs4 ems_reset_pcs_item @29729 @8007 UINT16
pcs4 ems_reset_bms_item @29730 @8008 UINT16
pcs4 mode_pq_vf_command_item @29733 @20582 INT16
pcs5 start_stop_command @29734 @657 INT16
pcs5 active_power_set_kw @30033 @3415 INT16
pcs5 start_stop_control_item @30108 @8000 INT16
pcs5 operation_mode_setting_item @30109 @8001 INT16
pcs5 scheduling_mode_item @30110 @8002 INT16
pcs5 pcs_switch_control_valid_when_8002_register_value_is_2_item @30111 @8003 INT16
pcs5 pcs_power_control_valid_when_8002_register_value_is_2_kw @30112 @8004 INT16
pcs5 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @30113 @8005 INT16
pcs5 ems_time_setting_item @30114 @8006 UINT32
pcs5 ems_reset_pcs_item @30116 @8007 UINT16
pcs5 ems_reset_bms_item @30117 @8008 UINT16
pcs5 mode_pq_vf_command_item @30120 @20582 INT16
pcs6 start_stop_command @30121 @657 INT16
pcs6 active_power_set_kw @30420 @3415 INT16
pcs6 start_stop_control_item @30495 @8000 INT16
pcs6 operation_mode_setting_item @30496 @8001 INT16
pcs6 scheduling_mode_item @30497 @8002 INT16
pcs6 pcs_switch_control_valid_when_8002_register_value_is_2_item @30498 @8003 INT16
pcs6 pcs_power_control_valid_when_8002_register_value_is_2_kw @30499 @8004 INT16
pcs6 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @30500 @8005 INT16
pcs6 ems_time_setting_item @30501 @8006 UINT32
pcs6 ems_reset_pcs_item @30503 @8007 UINT16
pcs6 ems_reset_bms_item @30504 @8008 UINT16
pcs6 mode_pq_vf_command_item @30507 @20582 INT16
pcs7 start_stop_command @30508 @657 INT16
pcs7 active_power_set_kw @30807 @3415 INT16
pcs7 start_stop_control_item @30882 @8000 INT16
pcs7 operation_mode_setting_item @30883 @8001 INT16
pcs7 scheduling_mode_item @30884 @8002 INT16
pcs7 pcs_switch_control_valid_when_8002_register_value_is_2_item @30885 @8003 INT16
pcs7 pcs_power_control_valid_when_8002_register_value_is_2_kw @30886 @8004 INT16
pcs7 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @30887 @8005 INT16
pcs7 ems_time_setting_item @30888 @8006 UINT32
pcs7 ems_reset_pcs_item @30890 @8007 UINT16
pcs7 ems_reset_bms_item @30891 @8008 UINT16
pcs7 mode_pq_vf_command_item @30894 @20582 INT16
pcs8 start_stop_command @30895 @657 INT16
pcs8 active_power_set_kw @31194 @3415 INT16
pcs8 start_stop_control_item @31269 @8000 INT16
pcs8 operation_mode_setting_item @31270 @8001 INT16
pcs8 scheduling_mode_item @31271 @8002 INT16
pcs8 pcs_switch_control_valid_when_8002_register_value_is_2_item @31272 @8003 INT16
pcs8 pcs_power_control_valid_when_8002_register_value_is_2_kw @31273 @8004 INT16
pcs8 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @31274 @8005 INT16
pcs8 ems_time_setting_item @31275 @8006 UINT32
pcs8 ems_reset_pcs_item @31277 @8007 UINT16
pcs8 ems_reset_bms_item @31278 @8008 UINT16
pcs8 mode_pq_vf_command_item @31281 @20582 INT16
pcs9 start_stop_command @31282 @657 INT16
pcs9 active_power_set_kw @31581 @3415 INT16
pcs9 start_stop_control_item @31656 @8000 INT16
pcs9 operation_mode_setting_item @31657 @8001 INT16
pcs9 scheduling_mode_item @31658 @8002 INT16
pcs9 pcs_switch_control_valid_when_8002_register_value_is_2_item @31659 @8003 INT16
pcs9 pcs_power_control_valid_when_8002_register_value_is_2_kw @31660 @8004 INT16
pcs9 pcs_timeout_shutdown_valid_when_8002_register_value_is_2_item @31661 @8005 INT16
pcs9 ems_time_setting_item @31662 @8006 UINT32
pcs9 ems_reset_pcs_item @31664 @8007 UINT16
pcs9 ems_reset_bms_item @31665 @8008 UINT16
pcs9 mode_pq_vf_command_item @31668 @20582 INT16

Appendix C: PCS addresses per unit

Every PCS block has the same layout, so the address of a register on unit N is base(N) + offset. The offsets below are measured from pcs1.

Unit Block base Block end Model SOC SOH Setpoint Run/stop command AC active power DC power
pcs1 @27025 @27411 SINEXCEL_PWS1_250K @27299 @27300 @27324 @27025 @27339 @27347
pcs10 @27412 @27798 SINEXCEL_PWS1_250K @27686 @27687 @27711 @27412 @27726 @27734
pcs11 @27799 @28185 EPCS105 @28073 @28074 @28098 @27799 @28113 @28121
pcs12 @28186 @28572 EPCS105 @28460 @28461 @28485 @28186 @28500 @28508
pcs2 @28573 @28959 SINEXCEL_PWS1_250K @28847 @28848 @28872 @28573 @28887 @28895
pcs3 @28960 @29346 EPCS105 @29234 @29235 @29259 @28960 @29274 @29282
pcs4 @29347 @29733 EPCS105 @29621 @29622 @29646 @29347 @29661 @29669
pcs5 @29734 @30120 EPCS105 @30008 @30009 @30033 @29734 @30048 @30056
pcs6 @30121 @30507 EPCS105 @30395 @30396 @30420 @30121 @30435 @30443
pcs7 @30508 @30894 EPCS105 @30782 @30783 @30807 @30508 @30822 @30830
pcs8 @30895 @31281 EPCS105 @31169 @31170 @31194 @30895 @31209 @31217
pcs9 @31282 @31668 EPCS105 @31556 @31557 @31581 @31282 @31596 @31604

C.1 Block layout

Block Base End Regs Nodes Source map Model
ac1 @25000 @25084 85 56 air_condition_unit/ac1/ac_register_full___ac_std.json AC_STD
ac2 @25085 @25169 85 56 air_condition_unit/ac2/ac_register_full___ac_std.json AC_STD
ac3 @25170 @25254 85 56 air_condition_unit/ac3/ac_register_full___ac_std.json AC_STD
ac4 @25255 @25339 85 56 air_condition_unit/ac4/ac_register_full___ac_std.json AC_STD
ac5 @25340 @25424 85 56 air_condition_unit/ac5/ac_register_full___ac_std.json AC_STD
ac6 @25425 @25509 85 56 air_condition_unit/ac6/ac_register_full___ac_std.json AC_STD
bessEnergyMeter1 @25510 @25609 100 55 bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json default
bmu1 @25610 @25671 62 62 bmu/bmu1/bmu_register_full___bmu100.json BMU100
bmu10 @25672 @25733 62 62 bmu/bmu10/bmu_register_full___bmu100.json BMU100
bmu2 @25734 @25795 62 62 bmu/bmu2/bmu_register_full___bmu100.json BMU100
bmu3 @25796 @25857 62 62 bmu/bmu3/bmu_register_full___bmu100.json BMU100
bmu4 @25858 @25919 62 62 bmu/bmu4/bmu_register_full___bmu100.json BMU100
bmu5 @25920 @25981 62 62 bmu/bmu5/bmu_register_full___bmu100.json BMU100
bmu6 @25982 @26043 62 62 bmu/bmu6/bmu_register_full___bmu100.json BMU100
bmu7 @26044 @26105 62 62 bmu/bmu7/bmu_register_full___bmu100.json BMU100
bmu8 @26106 @26167 62 62 bmu/bmu8/bmu_register_full___bmu100.json BMU100
bmu9 @26168 @26229 62 62 bmu/bmu9/bmu_register_full___bmu100.json BMU100
door_sensor1 @26230 @26241 12 12 door_sensor/door_sensor1/door_sensor_register_full.json default
door_sensor10 @26242 @26253 12 12 door_sensor/door_sensor10/door_sensor_register_full.json default
door_sensor2 @26254 @26265 12 12 door_sensor/door_sensor2/door_sensor_register_full.json default
door_sensor3 @26266 @26277 12 12 door_sensor/door_sensor3/door_sensor_register_full.json default
door_sensor4 @26278 @26289 12 12 door_sensor/door_sensor4/door_sensor_register_full.json default
door_sensor5 @26290 @26301 12 12 door_sensor/door_sensor5/door_sensor_register_full.json default
door_sensor6 @26302 @26313 12 12 door_sensor/door_sensor6/door_sensor_register_full.json default
door_sensor7 @26314 @26325 12 12 door_sensor/door_sensor7/door_sensor_register_full.json default
door_sensor8 @26326 @26337 12 12 door_sensor/door_sensor8/door_sensor_register_full.json default
door_sensor9 @26338 @26349 12 12 door_sensor/door_sensor9/door_sensor_register_full.json default
ffrEnergyMeter1 @26350 @26389 40 20 ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json default
fss1 @26390 @26459 70 57 fire_safety_system/fss1/fss_register_full___fss_std.json FSS_STD
flood_sensor1 @26460 @26461 2 2 flood_sensor/flood_sensor1/flood_sensor_register_full.json default
frequency_meter1 @26462 @26485 24 12 frequency_meter/frequency_meter1/frequencyMeter_register_full___me231.json ME231
grid_meter1 @26486 @26525 40 20 grid_energy_meter/grid_meter1/gridMeter_register_full___me231.json ME231
grid_meter10 @26526 @26565 40 20 grid_energy_meter/grid_meter10/gridMeter_register_full___me231.json ME231
grid_meter11 @26566 @26605 40 20 grid_energy_meter/grid_meter11/gridMeter_register_full___me231.json ME231
grid_meter12 @26606 @26645 40 20 grid_energy_meter/grid_meter12/gridMeter_register_full___me231.json ME231
grid_meter2 @26646 @26685 40 20 grid_energy_meter/grid_meter2/gridMeter_register_full___me231.json ME231
grid_meter3 @26686 @26725 40 20 grid_energy_meter/grid_meter3/gridMeter_register_full___me231.json ME231
grid_meter4 @26726 @26765 40 20 grid_energy_meter/grid_meter4/gridMeter_register_full___me231.json ME231
grid_meter5 @26766 @26805 40 20 grid_energy_meter/grid_meter5/gridMeter_register_full___me231.json ME231
grid_meter6 @26806 @26845 40 20 grid_energy_meter/grid_meter6/gridMeter_register_full___me231.json ME231
grid_meter7 @26846 @26885 40 20 grid_energy_meter/grid_meter7/gridMeter_register_full___me231.json ME231
grid_meter8 @26886 @26925 40 20 grid_energy_meter/grid_meter8/gridMeter_register_full___me231.json ME231
grid_meter9 @26926 @26965 40 20 grid_energy_meter/grid_meter9/gridMeter_register_full___me231.json ME231
heat_sensor1 @26966 @26967 2 1 heat_sensor/heat_sensor1/heat_sensor_register_full.json default
cooling1 @26968 @27024 57 35 liquid_cooling_unit/cooling1/cooling_register_full___cool_std.json COOL_STD
pcs1 @27025 @27411 387 372 pcs/pcs1/pcs_register_full___sinexcel_pws1_250k.json SINEXCEL_PWS1_250K
pcs10 @27412 @27798 387 372 pcs/pcs10/pcs_register_full___sinexcel_pws1_250k.json SINEXCEL_PWS1_250K
pcs11 @27799 @28185 387 372 pcs/pcs11/pcs_register_full___epcs105.json EPCS105
pcs12 @28186 @28572 387 372 pcs/pcs12/pcs_register_full___epcs105.json EPCS105
pcs2 @28573 @28959 387 372 pcs/pcs2/pcs_register_full___sinexcel_pws1_250k.json SINEXCEL_PWS1_250K
pcs3 @28960 @29346 387 372 pcs/pcs3/pcs_register_full___epcs105.json EPCS105
pcs4 @29347 @29733 387 372 pcs/pcs4/pcs_register_full___epcs105.json EPCS105
pcs5 @29734 @30120 387 372 pcs/pcs5/pcs_register_full___epcs105.json EPCS105
pcs6 @30121 @30507 387 372 pcs/pcs6/pcs_register_full___epcs105.json EPCS105
pcs7 @30508 @30894 387 372 pcs/pcs7/pcs_register_full___epcs105.json EPCS105
pcs8 @30895 @31281 387 372 pcs/pcs8/pcs_register_full___epcs105.json EPCS105
pcs9 @31282 @31668 387 372 pcs/pcs9/pcs_register_full___epcs105.json EPCS105
sensor_block1 @31669 @31681 13 7 sensor_block/sensorB1/sensorB_register_full___sens_std.json SENS_STD
smoke_sensor1 @31682 @31683 2 1 smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json default
solar_meter1 @31684 @31707 24 12 solar_energy_meter/solar_meter1/solarMeter_register_full___me231.json ME231
solar_meter10 @31708 @31731 24 12 solar_energy_meter/solar_meter10/solarMeter_register_full___me231.json ME231
solar_meter11 @31732 @31755 24 12 solar_energy_meter/solar_meter11/solarMeter_register_full___me231.json ME231
solar_meter12 @31756 @31779 24 12 solar_energy_meter/solar_meter12/solarMeter_register_full___me231.json ME231
solar_meter2 @31780 @31803 24 12 solar_energy_meter/solar_meter2/solarMeter_register_full___me231.json ME231
solar_meter3 @31804 @31827 24 12 solar_energy_meter/solar_meter3/solarMeter_register_full___me231.json ME231
solar_meter4 @31828 @31851 24 12 solar_energy_meter/solar_meter4/solarMeter_register_full___me231.json ME231
solar_meter5 @31852 @31875 24 12 solar_energy_meter/solar_meter5/solarMeter_register_full___me231.json ME231
solar_meter6 @31876 @31899 24 12 solar_energy_meter/solar_meter6/solarMeter_register_full___me231.json ME231
solar_meter7 @31900 @31923 24 12 solar_energy_meter/solar_meter7/solarMeter_register_full___me231.json ME231
solar_meter8 @31924 @31947 24 12 solar_energy_meter/solar_meter8/solarMeter_register_full___me231.json ME231
solar_meter9 @31948 @31971 24 12 solar_energy_meter/solar_meter9/solarMeter_register_full___me231.json ME231
temperature_sensor1 @31972 @31979 8 4 temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json default
ups1 @31980 @32060 81 54 ups/ups1/ups_register_full___ups_10k.json UPS_10K

Appendix D: Key operating values per PCS

Addresses are for pcs1; add the offset in appendix C for another unit.

Value Register pcs1 address Offset Type Wire unit Engineering value
SOC bc_battery_cluster.soc_state_of_charge_item @27299 +274 UINT16 percent raw
SOH bc_battery_cluster.soh_state_of_health_item @27300 +275 UINT16 percent raw
Applied power setpoint control.remote_control.active_power_set_kw @27324 +299 INT16 0.1 kW, signed raw / 10 kW
Battery cluster voltage bc_battery_cluster.cluster_voltage_v @27295 +270 UINT16 0.1 V raw / 10 V
Battery cluster current bc_battery_cluster.cluster_current_a @27296 +271 INT16 0.1 A, signed raw / 10 A
BMS DC current bc_battery_cluster.dc_current_a @27285 +260 INT16 0.1 A, signed raw / 10 A
AC active power pcs.three_phase_total_active_power_kwh @27339 +314 INT16 0.1 kW, signed raw / 10 kW
AC reactive power pcs.three_phase_total_reactive_power_kvar @27340 +315 INT16 0.1 kvar, signed raw / 10 kvar
DC power (PCS side) pcs.dc_power_kw @27347 +322 INT16 0.1 kW, signed raw / 10 kW
DC voltage pcs.dc_voltage_v @27348 +323 INT16 0.1 V, signed raw / 10 V
Grid frequency auxiliary.grid_frequency_hz @27386 +361 FLOAT32 Hz raw
Max allowed charge power bc_battery_cluster.maximum_allowable_charging_power_kw @27297 +272 UINT16 kW raw
Max allowed discharge power bc_battery_cluster.maximum_allowable_discharging_power_kw @27298 +273 UINT16 kW raw
PCS run/stop status pcs.pcs_start_stop_status @27350 +325 UINT16 code raw
PCS grid-connected pcs.pcs_grid_connected_status @27351 +326 UINT16 0/1 raw
PCS alarm present pcs.pcs_alarm_present @27353 +328 UINT16 0/1 raw
PCS fault present pcs.pcs_fault_present @27354 +329 UINT16 0/1 raw
PCS communication status pcs.communication_status @27355 +330 UINT16 code raw
BMS communication status bc_battery_cluster.communication_status @27320 +295 UINT16 code raw
BMS alarm level ½/3 bc_battery_cluster.bms_level_3_alarm @27323 +298 UINT16 code raw

Appendix E: Plant aggregates

These registers are computed when read, never cached, from the live PCS values. They are read-only. Where the source PCS reports zeros (a simulator that does not model voltage or current, for example) the aggregate is zero as well: the EMS does not invent values it does not measure.

Register Address Operation Unit Source Units aggregated
plant__power.total_active_power_kw @32061 sum(voltage*current/1000) kW bc_battery_cluster . - 12 PCS
plant__power.total_current_a @32063 sum(current) A bc_battery_cluster . - 12 PCS
plant__power.pcs_online_count @32065 count(voltage valid) count bc_battery_cluster . - 12 PCS
plant__voltage.dc_voltage_avg_v @32066 mean(voltage) V bc_battery_cluster . - 12 PCS
plant__voltage.dc_voltage_min_v @32068 min(voltage) V bc_battery_cluster . - 12 PCS
plant__voltage.dc_voltage_max_v @32070 max(voltage) V bc_battery_cluster . - 12 PCS
plant__current.dc_current_avg_a @32072 mean(current) A bc_battery_cluster . - 12 PCS
plant__current.dc_current_max_a @32074 max(current) A bc_battery_cluster . - 12 PCS
plant__current.dc_current_min_a @32076 min(current) A bc_battery_cluster . - 12 PCS
plant__ac_power.total_active_power_kw @32078 sum(three_phase_total_active_power_kwh) kW pcs . three_phase_total_active_power_kwh (active units only) 12 PCS
plant__ac_power.total_reactive_power_kvar @32080 sum(three_phase_total_reactive_power_kvar) kvar pcs . three_phase_total_reactive_power_kvar (active units only) 12 PCS
plant__ac_power.reporting_pcs_count @32082 count(three_phase_total_active_power_kwh valid) count pcs . three_phase_total_active_power_kwh (active units only) 12 PCS

Appendix F: Validation harness

The checks in section 14 are produced by EnergySyc_EMS_ES100Cx12S/tools/ems_modbus_validation.py, which talks to the map server and the bridge the way a third-party controller would. It is safe to re-run: the control phase snapshots the settings file, restores the as-found mode and control mode, and prints one PASS/FAIL line per check.

Phase Covers Mutates
--phase reads connection, EMS status, aggregates, PCS telemetry, protocol edge cases, write-refusal rules no
--phase control mode start / stop / change, settings writes, external control bridge, PCS execution yes, restores the as-found state
# the run behind section 14, in one pass
python3 tools/ems_modbus_validation.py --phase all --host <ems-host> \
    --ssh-host root@<ems-host> \
    --settings /opt/gess-stack/ems/backend/app/EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_control_setting.json

# non-mutating, no host access needed
python3 tools/ems_modbus_validation.py --phase reads --host <ems-host>

# mutating only; --ssh-host is needed only to change ems_control_mode (an operator action)
python3 tools/ems_modbus_validation.py --phase control --host <ems-host> \
    --ssh-host root@<ems-host> \
    --settings /opt/gess-stack/ems/backend/app/EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_control_setting.json \
    --sim-ports 1501,1502

A check is a PASS only when the EMS confirms the effect: a mode is confirmed by ems_operation_status (@3), a setting by reading the register back, a bridge command by reading the PCS setpoint registers. Checks that cannot run in a given environment (no host access, PCS simulators unreachable) are reported as SKIPPED, never as PASS.