MANUAL

Applies a fixed operator-supplied setpoint directly to the PCS.

Mode string MANUAL (EMS_OP_MANUAL)
Dispatcher ems_main.py → control_logic_updated.control_step_manual
Config block functions.Manual_Operation
Queue source tag control_logic (the writer's default)
Status Implemented

Purpose

The simplest mode: the operator chooses STOP, CHARGE or DISCHARGE and a magnitude. No telemetry-driven decision, no time windows, no hysteresis — every cycle writes an explicit setpoint.

How it decides

operation_type Behaviour
STOP Writes 0 kW to every active PCS and returns.
CHARGE total_set_kw = -abs(power_setpoint_kw)
DISCHARGE total_set_kw = +abs(power_setpoint_kw)

Any other value ⇒ return (no action). A missing or non-positive power_setpoint_kw ⇒ return.

Configuration

functions.Manual_Operation

Key Live value Meaning
enabled false Master switch.
operation_type idle STOP | CHARGE | DISCHARGE. idle is not a valid action and causes a return.
power_setpoint_kw 67 Magnitude in kW for charge/discharge.
ramp_rate_kw_s 54 Recorded only; no ramp limiting is applied.
soc_limits {min: 67, max: 78} Can only tighten the general PCS limits (see below).
soc_recovery_target_pct 12 Recorded only; not used by the control step.
power_caps_kw {charge: null, discharge: 70} Plant-level caps; can only tighten the PCS limits.
mode_priority override-all Intent: manual outranks other functions.
telemetry_control object HMI/telemetry metadata; not used in control.
safety object Trip settings (trip_on_overtemperature, grid_fault_action: PCS_shutdown); metadata consumed elsewhere, not in this control step.

Limit tightening

Manual limits never loosen the hardware limits. Effective bounds are merged:

eff_min = max(general min_soc_pct, soc_limits.min_soc_pct)
eff_max = min(general max_soc_pct, soc_limits.max_soc_pct)

The per-PCS allocation cap is likewise min(power_limits.max_*_kw, power_caps_kw.*_cap_kw).

Safety

  • Returns when is_external_control_active(), when enabled is false, or when there are no active PCS.
  • Uses _soc_block_reason(soc, eff_min, eff_max, "charge"|"discharge") — direction aware: CHARGE is blocked at max_soc_pct, DISCHARGE is blocked at min_soc_pct. SOC-blocked PCS are force-written to 0 kW rather than left at their previous setpoint.
  • Final clamp inside _pcs_connect_and_set_power_kw.

Caution: this mode writes a setpoint every cycle with no ramping. Large power_setpoint_kw values step the PCS instantly.

Outputs

_pcs_connect_and_set_power_kw(cfg, pcs_id, ±kw) → queue action set_power_kw, source control_logic.