STOP_ALL

Stops the plant and holds every active PCS at zero power.

Mode string STOP_ALL (EMS_OP_STOP_ALL)
Dispatcher ems_main.py → control_logic_updated.control_step_stop_all
Config block none, by design
Queue action set_power_kw (value 0.0)
Queue source tag stop_all
Status Implemented

Purpose

A safety action rather than a control strategy. Selecting this mode:

  1. Discards unapplied automatic power setpoints left behind by the other modes, so a stale command cannot be applied after the stop.
  2. Queues an explicit 0 kW for every active PCS.

Step 2 matters. Discarding alone would only empty the queue — each PCS would stay at whatever setpoint it last applied. Queuing zero is what actually stops the plant.

Why there is no config block

Every other mode is gated by functions.<Mode>.enabled. STOP_ALL deliberately is not:

Selecting a mode named "STOP_ALL" must never silently do nothing.

There is no functions.Stop_All block and no enable flag. If you select it, it acts. The only thing that can prevent it from running is the surrounding dispatch structure, described below.

Configuration

None. STOP_ALL has no entry in ems_control_setting.json.

Reachability

The branch sits in the normal dispatch chain, so it is skipped in exactly the two situations where normal dispatch is skipped anyway:

Situation Behaviour
is_diagnostic_test_active() Dispatch chain is skipped; the diagnostic interlock already queues its own zeros.
ems_control_mode == "external_control" The external bridge owns the PCS; dispatch chain is skipped.

In both cases ems_main.py continues the loop before reaching the mode branches.

Idempotency

control_step_stop_all runs every cycle. The power writer replaces (rather than appends) unapplied setpoints from the stop_all and control_logic sources, so repeated cycles keep exactly one pending 0 kW per PCS instead of stacking one per cycle.

This is also why the zeros use their own stop_all source rather than control_logic: the discard helper removes control_logic power commands, so a control_logic-sourced zero would be discarded by the next cycle's discard step before the PCS client could apply it.

Safety

  • Preserves manual/operator commands and mode_pq / mode_vf switches — the discard step only removes automatic control_logic power setpoints. Starting a STOP_ALL does not override an operator's manual command.
  • Zero is clamped through the same _pcs_connect_and_set_power_kw path as every other mode.
  • Failures are caught per cycle in ems_main.py and logged as [EMS][WARN] STOP_ALL failed: ... without killing the loop.

Review: confirm that preserving manual commands is the intended semantics for your emergency stop. If STOP_ALL is meant to be a hard stop that also overrides manual commands, the discard filter and source list need widening.

Outputs

  • discard_pending_automatic_power_commands() → removes queued control_logic power setpoints.
  • queue_diagnostic_zero_power_commands(source="stop_all") → one set_power_kw = 0.0 per active PCS, source stop_all.
  • Log line: [STOP_ALL] discarded N pending automatic setpoint(s); queued 0 kW for M active PCS.