VALLEY_FILLING

Charges the battery from the grid when site import is low, to fill demand valleys.

Mode string VALLEY_FILLING (EMS_OP_VALLEY_FILLING)
Dispatcher ems_main.py → control_logic_updated.control_step_valley_filling
Config block functions.Valley_Filling
Queue source tag control_logic (the writer's default)
Status Implemented

Purpose

A charge-only counterpart to peak shaving. When site import is below valley_threshold_kw it charges the battery to soak up cheap/low-demand periods, bounded by window caps and the SOC ceiling.

How it decides

required_charge_kw = max(0.0, valley_threshold_kw - import_kw)
  • Only acts inside an enabled charge_windows entry (timezone- and days_of_week-aware).
  • Only charges when the site is importing. If the site is exporting, no charging is triggered by the valley rule.
  • Applies the smallest of: required_charge_kw, charge_power_limit_kw, the active window's charge_cap_kw, and the per-PCS charge caps.
  • Hysteresis. If import sits inside the hysteresis band around the threshold, the previous setpoint is held (HOLD-LAST) rather than recalculated.
  • The command is written as a negative kW (charge).

Configuration

functions.Valley_Filling

Key Live value Meaning
enabled false Master switch.
valley_threshold_kw 75 Import level below which charging is wanted.
charge_power_limit_kw 120 Plant-wide charge ceiling.
max_soc_pct null Charge ceiling. Null ⇒ falls back to the PCS soc_limits.max_soc_pct.
min_soc_pct null Not used — this mode never discharges.
response_time_ms null Recorded; not used.
timezone Europe/Stockholm Timezone for window evaluation.
charge_windows[] 5 entries start, end, enabled, charge_cap_kw, days_of_week.
optional.hysteresis_kw 2 Deadband that triggers HOLD-LAST.
optional.conflict_rule discharge_overrides_charge Documented; this mode has no discharge path.

Safety

  • Returns when is_external_control_active(), when enabled is false, or with no active PCS.
  • SOC gate is charge-only: judged against max_soc_pct. min_soc_pct is deliberately ignored, so a low battery can still be filled.
  • Per-PCS caps from power_limits.max_charge_kw, further bounded by charge_cap_kw of the active window; final clamp inside _pcs_connect_and_set_power_kw.

Check: the second shipped window is 14:00 → 08:00, a window that wraps past midnight. Confirm the wrap is handled as you expect before enabling this mode.

Outputs

_pcs_connect_and_set_power_kw(cfg, pcs_id, -kw) → queue action set_power_kw, source control_logic.