EMS register map: address plan
Generated from EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_register_full.json by EnergySyc_EMS_ES100Cx12S/tools/generate_register_map_docs.py. Do not edit by hand - re-run the generator after changing the register map.
The map declares 6385 registers across 73 device blocks: 5879 read-only and 506
read-write. Values are served by the EMS Modbus server on port 1540 (unit 1) at
the addresses below - these are PDU addresses, so a client that shows
4xxxx holding-register numbers must add 40001.
Device blocks
| Block | Base | End | Regs | Nodes | Source map | Model | Detail page |
|---|---|---|---|---|---|---|---|
ac1 |
@25000 | @25084 | 85 | 56 | air_condition_unit/ac1/ac_register_full___ac_std.json |
AC_STD | Auxiliary devices |
ac2 |
@25085 | @25169 | 85 | 56 | air_condition_unit/ac2/ac_register_full___ac_std.json |
AC_STD | - |
ac3 |
@25170 | @25254 | 85 | 56 | air_condition_unit/ac3/ac_register_full___ac_std.json |
AC_STD | - |
ac4 |
@25255 | @25339 | 85 | 56 | air_condition_unit/ac4/ac_register_full___ac_std.json |
AC_STD | - |
ac5 |
@25340 | @25424 | 85 | 56 | air_condition_unit/ac5/ac_register_full___ac_std.json |
AC_STD | - |
ac6 |
@25425 | @25509 | 85 | 56 | air_condition_unit/ac6/ac_register_full___ac_std.json |
AC_STD | - |
bessEnergyMeter1 |
@25510 | @25609 | 100 | 55 | bess_energy_meter/bess_energy_meter1/bess_energy_meter_register_full.json |
default | - |
bmu1 |
@25610 | @25671 | 62 | 62 | bmu/bmu1/bmu_register_full___bmu100.json |
BMU100 | BMU units |
bmu10 |
@25672 | @25733 | 62 | 62 | bmu/bmu10/bmu_register_full___bmu100.json |
BMU100 | - |
bmu2 |
@25734 | @25795 | 62 | 62 | bmu/bmu2/bmu_register_full___bmu100.json |
BMU100 | - |
bmu3 |
@25796 | @25857 | 62 | 62 | bmu/bmu3/bmu_register_full___bmu100.json |
BMU100 | - |
bmu4 |
@25858 | @25919 | 62 | 62 | bmu/bmu4/bmu_register_full___bmu100.json |
BMU100 | - |
bmu5 |
@25920 | @25981 | 62 | 62 | bmu/bmu5/bmu_register_full___bmu100.json |
BMU100 | - |
bmu6 |
@25982 | @26043 | 62 | 62 | bmu/bmu6/bmu_register_full___bmu100.json |
BMU100 | - |
bmu7 |
@26044 | @26105 | 62 | 62 | bmu/bmu7/bmu_register_full___bmu100.json |
BMU100 | - |
bmu8 |
@26106 | @26167 | 62 | 62 | bmu/bmu8/bmu_register_full___bmu100.json |
BMU100 | - |
bmu9 |
@26168 | @26229 | 62 | 62 | bmu/bmu9/bmu_register_full___bmu100.json |
BMU100 | - |
door_sensor1 |
@26230 | @26241 | 12 | 12 | door_sensor/door_sensor1/door_sensor_register_full.json |
default | - |
door_sensor10 |
@26242 | @26253 | 12 | 12 | door_sensor/door_sensor10/door_sensor_register_full.json |
default | - |
door_sensor2 |
@26254 | @26265 | 12 | 12 | door_sensor/door_sensor2/door_sensor_register_full.json |
default | - |
door_sensor3 |
@26266 | @26277 | 12 | 12 | door_sensor/door_sensor3/door_sensor_register_full.json |
default | - |
door_sensor4 |
@26278 | @26289 | 12 | 12 | door_sensor/door_sensor4/door_sensor_register_full.json |
default | - |
door_sensor5 |
@26290 | @26301 | 12 | 12 | door_sensor/door_sensor5/door_sensor_register_full.json |
default | - |
door_sensor6 |
@26302 | @26313 | 12 | 12 | door_sensor/door_sensor6/door_sensor_register_full.json |
default | - |
door_sensor7 |
@26314 | @26325 | 12 | 12 | door_sensor/door_sensor7/door_sensor_register_full.json |
default | - |
door_sensor8 |
@26326 | @26337 | 12 | 12 | door_sensor/door_sensor8/door_sensor_register_full.json |
default | - |
door_sensor9 |
@26338 | @26349 | 12 | 12 | door_sensor/door_sensor9/door_sensor_register_full.json |
default | - |
ffrEnergyMeter1 |
@26350 | @26389 | 40 | 20 | ffr_energy_meter/ffrMeter1/ffrMeter_register_full.json |
default | - |
fss1 |
@26390 | @26459 | 70 | 57 | fire_safety_system/fss1/fss_register_full___fss_std.json |
FSS_STD | Auxiliary devices |
flood_sensor1 |
@26460 | @26461 | 2 | 2 | flood_sensor/flood_sensor1/flood_sensor_register_full.json |
default | - |
frequency_meter1 |
@26462 | @26485 | 24 | 12 | frequency_meter/frequency_meter1/frequencyMeter_register_full___me231.json |
ME231 | Meters |
grid_meter1 |
@26486 | @26525 | 40 | 20 | grid_energy_meter/grid_meter1/gridMeter_register_full___me231.json |
ME231 | Meters |
grid_meter10 |
@26526 | @26565 | 40 | 20 | grid_energy_meter/grid_meter10/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter11 |
@26566 | @26605 | 40 | 20 | grid_energy_meter/grid_meter11/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter12 |
@26606 | @26645 | 40 | 20 | grid_energy_meter/grid_meter12/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter2 |
@26646 | @26685 | 40 | 20 | grid_energy_meter/grid_meter2/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter3 |
@26686 | @26725 | 40 | 20 | grid_energy_meter/grid_meter3/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter4 |
@26726 | @26765 | 40 | 20 | grid_energy_meter/grid_meter4/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter5 |
@26766 | @26805 | 40 | 20 | grid_energy_meter/grid_meter5/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter6 |
@26806 | @26845 | 40 | 20 | grid_energy_meter/grid_meter6/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter7 |
@26846 | @26885 | 40 | 20 | grid_energy_meter/grid_meter7/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter8 |
@26886 | @26925 | 40 | 20 | grid_energy_meter/grid_meter8/gridMeter_register_full___me231.json |
ME231 | - |
grid_meter9 |
@26926 | @26965 | 40 | 20 | grid_energy_meter/grid_meter9/gridMeter_register_full___me231.json |
ME231 | - |
heat_sensor1 |
@26966 | @26967 | 2 | 1 | heat_sensor/heat_sensor1/heat_sensor_register_full.json |
default | - |
cooling1 |
@26968 | @27024 | 57 | 35 | liquid_cooling_unit/cooling1/cooling_register_full___cool_std.json |
COOL_STD | Auxiliary devices |
pcs1 |
@27025 | @27411 | 387 | 372 | pcs/pcs1/pcs_register_full___sinexcel_pws1_250k.json |
SINEXCEL_PWS1_250K | PCS units |
pcs10 |
@27412 | @27798 | 387 | 372 | pcs/pcs10/pcs_register_full___sinexcel_pws1_250k.json |
SINEXCEL_PWS1_250K | - |
pcs11 |
@27799 | @28185 | 387 | 372 | pcs/pcs11/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs12 |
@28186 | @28572 | 387 | 372 | pcs/pcs12/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs2 |
@28573 | @28959 | 387 | 372 | pcs/pcs2/pcs_register_full___sinexcel_pws1_250k.json |
SINEXCEL_PWS1_250K | - |
pcs3 |
@28960 | @29346 | 387 | 372 | pcs/pcs3/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs4 |
@29347 | @29733 | 387 | 372 | pcs/pcs4/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs5 |
@29734 | @30120 | 387 | 372 | pcs/pcs5/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs6 |
@30121 | @30507 | 387 | 372 | pcs/pcs6/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs7 |
@30508 | @30894 | 387 | 372 | pcs/pcs7/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs8 |
@30895 | @31281 | 387 | 372 | pcs/pcs8/pcs_register_full___epcs105.json |
EPCS105 | - |
pcs9 |
@31282 | @31668 | 387 | 372 | pcs/pcs9/pcs_register_full___epcs105.json |
EPCS105 | - |
sensor_block1 |
@31669 | @31681 | 13 | 7 | sensor_block/sensorB1/sensorB_register_full___sens_std.json |
SENS_STD | Auxiliary devices |
smoke_sensor1 |
@31682 | @31683 | 2 | 1 | smoke_sensor/smoke_sensor1/smoke_sensor_register_full.json |
default | - |
solar_meter1 |
@31684 | @31707 | 24 | 12 | solar_energy_meter/solar_meter1/solarMeter_register_full___me231.json |
ME231 | Meters |
solar_meter10 |
@31708 | @31731 | 24 | 12 | solar_energy_meter/solar_meter10/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter11 |
@31732 | @31755 | 24 | 12 | solar_energy_meter/solar_meter11/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter12 |
@31756 | @31779 | 24 | 12 | solar_energy_meter/solar_meter12/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter2 |
@31780 | @31803 | 24 | 12 | solar_energy_meter/solar_meter2/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter3 |
@31804 | @31827 | 24 | 12 | solar_energy_meter/solar_meter3/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter4 |
@31828 | @31851 | 24 | 12 | solar_energy_meter/solar_meter4/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter5 |
@31852 | @31875 | 24 | 12 | solar_energy_meter/solar_meter5/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter6 |
@31876 | @31899 | 24 | 12 | solar_energy_meter/solar_meter6/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter7 |
@31900 | @31923 | 24 | 12 | solar_energy_meter/solar_meter7/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter8 |
@31924 | @31947 | 24 | 12 | solar_energy_meter/solar_meter8/solarMeter_register_full___me231.json |
ME231 | - |
solar_meter9 |
@31948 | @31971 | 24 | 12 | solar_energy_meter/solar_meter9/solarMeter_register_full___me231.json |
ME231 | - |
temperature_sensor1 |
@31972 | @31979 | 8 | 4 | temperature_sensor/temperature_sensor1/temperature_sensor_register_full.json |
default | - |
ups1 |
@31980 | @32060 | 81 | 54 | ups/ups1/ups_register_full___ups_10k.json |
UPS_10K | Auxiliary devices |
Blocks are laid out contiguously from block_base (the map's structure.block_base,
currently 25000). A register inside a block keeps the address it has in the source
device map, shifted by the block base, so device_address = address - block base.
Data types
| Type | Registers | Encoding | Nodes |
|---|---|---|---|
| BOOL | 1 | 0 or 1 in one register | 3201 |
| UINT16 | 1 | unsigned 16-bit | 1370 |
| FLOAT32 | 2 | IEEE-754, high word first | 830 |
| INT16 | 1 | two's complement; served unsigned, sign-extend in the client | 348 |
| INT16U | 1 | unsigned 16-bit | 231 |
| BOOL16 | 1 | 0 or 1 in one register | 181 |
| UINT32 | 2 | unsigned 32-bit, high word first | 112 |
| BITMAP32 | 2 | 32-bit bitmap, high word first | 60 |
| ENUM16 | 1 | enum code in one register | 47 |
| INT32U | 2 | unsigned 32-bit, high word first | 5 |
EMS-owned categories
158 registers hold EMS control and status data at @1..@208; the remaining EMS
categories below keep the addresses they were first published with.
| Category | Nodes | Addresses |
|---|---|---|
| alarms | 13 | @2400..@13600 |
| currents | 5 | @3002..@24669 |
| energies | 7 | @2706..@2722 |
| frequency | 1 | @3110..@3110 |
| power | 12 | @3054..@3076 |
| power_factor | 4 | @3144..@3150 |
| voltages | 8 | @3020..@3036 |
Detail pages
| Area | Contents | Page |
|---|---|---|
| EMS control and settings | 158 registers, with settings paths | EMS control and status |
| EMS telemetry | preserved EMS categories (alarms, energies, currents, voltages, power, frequency, power factor) | EMS telemetry |
| PCS | remote-control registers for every unit, plus the full pcs1 listing | PCS units |
| BMU | battery management units | BMU units |
| Auxiliaries | UPS, air conditioning, cooling, fire suppression, sensor blocks | Auxiliary devices |
| Meters | grid, solar and frequency meters | Meters |
| Plant aggregates | computed plant totals | Plant aggregates |
Regenerate with python3 EnergySyc_EMS_ES100Cx12S/tools/generate_register_map_docs.py.