Skip to content

Plant aggregate registers

Generated from EnergySyc_EMS_ES100Cx12S/emsConfig/ems/ems_register_full.json by EnergySyc_EMS_ES100Cx12S/tools/generate_register_map_docs.py. Do not edit by hand - re-run the generator after changing the register map.

These 12 registers are computed when read, never on a timer: the server evaluates them from the live values of the PCS blocks, so a total that nobody reads costs nothing. Sources marked active only skip units that are not reporting valid data.

Register Address Type Regs Access Device Notes
total_active_power_kw @32061 FLOAT32 2 RO - -
total_current_a @32063 FLOAT32 2 RO - -
pcs_online_count @32065 UINT16 1 RO - -
dc_voltage_avg_v @32066 FLOAT32 2 RO - -
dc_voltage_min_v @32068 FLOAT32 2 RO - -
dc_voltage_max_v @32070 FLOAT32 2 RO - -
dc_current_avg_a @32072 FLOAT32 2 RO - -
dc_current_max_a @32074 FLOAT32 2 RO - -
dc_current_min_a @32076 FLOAT32 2 RO - -
total_active_power_kw @32078 FLOAT32 2 RO - -
total_reactive_power_kvar @32080 FLOAT32 2 RO - -
reporting_pcs_count @32082 UINT16 1 RO - -

Definitions

Register Address Operation Source registers Unit
plant__power.total_active_power_kw @32061 sum(voltage*current/1000) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a kW
plant__power.total_current_a @32063 sum(current) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a A
plant__power.pcs_online_count @32065 count(voltage valid) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a count
plant__voltage.dc_voltage_avg_v @32066 mean(voltage) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a V
plant__voltage.dc_voltage_min_v @32068 min(voltage) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a V
plant__voltage.dc_voltage_max_v @32070 max(voltage) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a V
plant__current.dc_current_avg_a @32072 mean(current) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a A
plant__current.dc_current_max_a @32074 max(current) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a A
plant__current.dc_current_min_a @32076 min(current) pcs1..pcs12 . bc_battery_cluster: cluster_voltage_v, cluster_current_a A
plant__ac_power.total_active_power_kw @32078 sum(three_phase_total_active_power_kwh) pcs1..pcs12 . pcs: three_phase_total_active_power_kwh (active units only) kW
plant__ac_power.total_reactive_power_kvar @32080 sum(three_phase_total_reactive_power_kvar) pcs1..pcs12 . pcs: three_phase_total_reactive_power_kvar (active units only) kvar
plant__ac_power.reporting_pcs_count @32082 count(three_phase_total_active_power_kwh valid) pcs1..pcs12 . pcs: three_phase_total_active_power_kwh (active units only) count